Propane was Luis's own subject, and on the second half of November 10 Maureen handed him the marker. "You've set more tanks than anyone here," she said. "Teach it. Grant asks the questions." Luis started with the Vandermeer job from GAS-240, the underground tank in Carlisle that he and Jonah had set in September, and drew the system on the whiteboard from the tank to the range: tank, first-stage regulator, the polyethylene line under the lawn, the second-stage regulator on the house wall, the furnace, the tankless water heater and the range. "Everything on the exam about propane," he said, "is on this drawing somewhere, or it's about the cylinder you bring the barbecue to fill."

This lesson reviews GAS-240, with the propane material of GAS-110, GAS-120 and GAS-210. It covers propane's properties and vapour pressure, cylinders and tanks, siting, regulation, vaporization, filling, underground tanks, construction heaters, vehicle fuel systems and emergencies. The Canadian separation distances, the vaporization chart and the line capacity table in GAS-240 were invented samples; the code's own tables apply on the exam.

Properties and vapour pressure

Propane is stored as a liquid under its own vapour pressure, which depends only on the temperature of the liquid, not on how full the container is. A cylinder on a warm day is at a higher pressure than the same cylinder on a cold day, whether it is nearly full or nearly empty. That is why a pressure gauge on a tank tells you the temperature, not the contents, and why contents are read from a float gauge or by weight.

Approximate vapour pressure of pure propane, from GAS-240. Commercial propane with a little butane is slightly lower.
Liquid temperature−40 °C−30 °C−20 °C−10 °C0 °C10 °C20 °C30 °C40 °C
Vapour pressure, kPa gauge10671432443735367359791,268

Several numbers from GAS-240 come up again and again: one volume of liquid makes about 270 volumes of vapour; propane's specific gravity as a vapour is about 1.52, so it sinks; its flammable range is 2.1 to 9.5 in 100; its heating value is about 25.3 MJ per litre of liquid and about 93 MJ/m³ of vapour; and its liquid expands strongly as it warms, which is why containers are never filled completely.

Cylinders and tanks

Cylinders are portable containers built to Transport Canada specifications and marked with their specification, water capacity, tare weight and date of manufacture. They must be requalified before refilling once the date on them is more than 10 years old, and every 10 years after that. Small vapour-withdrawal cylinders such as barbecue cylinders have an overfilling prevention device (OPD) and a triangular handwheel that identifies it. Tanks are larger containers built to the ASME pressure vessel code, filled on site, with a relief valve, a fill valve, a vapour service valve, a liquid level gauge and a float gauge; Ontario's code adoption document requires recorded inspections of tanks at least every 10 years and sets the schedule for rebuilding or replacing relief valves.

Containers are filled to about 80 in 100 of their volume at normal temperatures, or by weight to the filling density, about 42 in 100 of the water capacity, so that the liquid has room to expand. A cylinder filled to the top in a cool plant can become liquid-full as it warms, and its relief valve will open and release liquid, which makes a large flammable cloud.

Worked problem

How much gas is in the tank?

The Vandermeer tank holds 3,785 L of water. It was filled to 80 in 100 in September. How many litres of propane did it hold, and roughly how long would that run the 26 kW furnace alone at full fire, using 25.3 MJ per litre?

Show solution
  1. Propane in the tank:
  2. \[3{,}785 \times 0.80 = 3{,}028 \text{ L}\]
  3. Energy:
  4. \[3{,}028 \times 25.3 \approx 76{,}610 \text{ MJ}\]
  5. Furnace input in MJ/h:
  6. \[26 \times 3.6 = 93.6 \text{ MJ/h}\]
  7. Hours:
  8. \[\frac{76{,}610}{93.6} \approx 818 \text{ h}\]

Answer: About 3,028 L, enough for about 818 hours of the furnace at full fire. In practice the tank also feeds the water heater and range, and the supplier refills it before it falls below about 20 in 100.

Siting

Where a tank or cylinder may go is set by B149.2: separation distances from buildings, property lines, building openings, sources of ignition and other tanks, which grow with the container's size, and distances from the relief valve discharge and the filling connection. GAS-240 practised with an invented sample table; on the exam, use the code's own table. Siting also includes protection from vehicles, access for the delivery truck and hose, clearance from overhead power lines, and firm level support. Gwen Talbot's spot by the barn under a power line in GAS-240 failed on two of those.

Regulation and vaporization

Propane systems use two-stage regulation. The first-stage regulator at the tank reduces tank pressure, which may be over 1,000 kPa on a hot day, to a typical 70 kPa. The second-stage regulator at the building reduces that to appliance pressure, typically about 2.6 to 2.75 kPa. The Vandermeer system commissioned at 2.62 kPa flowing and 2.92 kPa at lock-up. Two stages keep the appliance pressure steady as tank pressure changes with the weather, and they protect the house piping if one regulator fails. The codes require two-stage regulation for most fixed piping systems, which is why the Selkirk/Buckeye Lake cottage got a new pair.

A curve of propane vapour pressure against liquid temperature. The horizontal axis runs from minus 40 to 40 degrees Celsius, the vertical from 0 to 1,300 kPa gauge. The curve rises slowly at first, through 10 kPa at minus 40 and 143 kPa at minus 20, then steeply, through 373 kPa at 0, 735 kPa at 20 and 1,268 kPa at 40. A shaded band below about 70 kPa is labelled: below the first-stage outlet pressure, the system cannot deliver full flow. A note says: on a cold night the tank's own temperature can fall below the air temperature as liquid boils off.
Propane vapour pressure rises steeply with temperature. On very cold days it can fall close to what the regulators need.

A tank delivers vapour only as fast as its liquid can boil, and boiling takes heat, which comes through the tank's wetted wall from the air or the ground. The vaporization rate therefore falls with the outdoor temperature and with the liquid level, because less wall is wetted. A small tank or a pair of cylinders that is ample in October can starve a large load on the coldest night, with frost on the container at the liquid line and appliances locking out on low pressure, as the greenhouse heater near Binbrook did in January 2026. The fix is a larger tank, more containers drawing together, or a vaporizer, sized from the maker's and the code's data.

Underground tanks, construction heat and vehicles

Underground tanks are steel buried in soil, so they are protected from corrosion by their coating and by cathodic protection: magnesium anodes connected to the tank corrode instead of it. The protection is checked by measuring the tank-to-soil potential with a reference electrode; a reading that is not negative enough means the anodes are spent or disconnected, as at the golf clubhouse in GAS-240, where a broken anode wire left the tank at −0.62 V until new anodes brought it to −0.98 V. In Ontario, people who fill containers or set up construction heaters need a record of training for that task. Construction heaters burn propane in partly enclosed spaces, so they need the clearances, ventilation and CO monitoring the code and the maker require, and a torpedo heater in a closed basement, as at the Northvale site in GAS-240, produces carbon monoxide fast. Propane vehicle fuel systems, including forklift cylinders, follow B149.5, with fuel systems inspected every five years by a certified technician at a registered conversion centre.

Leak checks and emergencies

Every propane system is leak checked whenever it is opened or the gas has run out, because a run-out may mean an appliance pilot was left open. The usual method is a pressure test of the low-pressure piping: pressurize, close the supply, and watch a gauge or manometer for a drop over the test time, then find any leak with solution or a detector. The Brennans' farmhouse in GAS-240 failed its leak check at 2.25 dropping to 2.10 kPa because of a cracked flare nut at the fireplace valve. In an emergency, a propane leak is treated as more dangerous than natural gas, because the vapour sinks into basements, drains and low ground and stays there. Shut off the container if it can be done safely, keep ignition sources away, get people out and upwind or uphill, and call emergency services and the supplier.

Converting appliances between gases

Conversion questions combine the propane facts with the appliance facts of GAS-210. An appliance built for natural gas has orifices sized to pass the right volume of a light, low-energy gas at a low manifold pressure. Propane carries about two and a half times the energy per volume, is heavier, and is supplied at a higher manifold pressure, so the same orifice on propane would badly overfire the burner. A conversion therefore changes the orifices, the regulator setting or spring and sometimes the pilot orifice and air shutters, all together, and only with the maker's conversion kit. The Wobbe index explains why: natural gas is about 48.4 MJ/m³ and propane about 75.8 MJ/m³ on the Wobbe scale used in GAS-210, a ratio of about 1.57, so a propane orifice must pass much less volume than the natural gas one for the same heat.

Worked problem

Why the orifice gets smaller

GAS-210's range conversion changed a natural gas orifice of 2.08 mm to a propane orifice of 1.28 mm. By what factor did the orifice area shrink?

Show solution
  1. Area is proportional to diameter squared:
  2. \[\frac{1.28^2}{2.08^2} = \frac{1.638}{4.326} \approx 0.38\]

Answer: The propane orifice has a little under four tenths of the natural gas orifice's area. That, together with the higher manifold pressure and propane's higher heating value, gives about the same input. A rough exam check: a propane orifice is always much smaller than the natural gas one for the same appliance.

Every conversion ends with the label the kit supplies, filled in and fixed to the appliance, showing the gas, the date and who did it, and with a full start-up: pressures, clocked input where possible, flame appearance and combustion readings. In Ontario, B149.1 and O. Reg. 212/01 allow conversion only with the certified kit and instructions, by a certificate holder. A conversion with drilled orifices is not allowed, and an exam option that suggests drilling or tightening an orifice to change gases is always wrong.

Cylinder handling questions

Questions about cylinders tend to test a few practical rules. Cylinders are stored and used upright, valve up, with the relief valve in the vapour space, except cylinders designed for liquid withdrawal such as forklift cylinders, which have their own position. They are kept outdoors or in ventilated cabinets, away from building openings, heat and ignition sources, and never stored indoors in a house beyond the small sizes the code allows. They are transported secured, upright and with the valve closed and plugged where required. And a cylinder out of its requalification date is not refilled, as Bayline's cylinder cage audit in GAS-240 found with one of the farm's retired cylinders.

Questions this topic produces

Propane questions on the exam fall into a few patterns, and Luis's whiteboard drawing covered all of them:

  • Pressure and temperature: what happens to tank pressure on a cold night, and why the float gauge, not the pressure gauge, shows the contents.
  • Filling: why containers are filled to about 80 in 100, and what happens to an overfilled cylinder as it warms.
  • Regulation: which regulator is at the tank and which at the building, and the typical pressure after each.
  • Vaporization: why a system that works in October fails in January, and what fixes it.
  • Siting and containers: distances, requalification dates, OPDs and which way up a cylinder is used.
  • Hazards: why a propane leak is treated as more dangerous than a natural gas leak, and where the detector goes.

Common mistakes

  • MistakeReading a tank's contents from its pressure gauge.

    InsteadPressure follows temperature; read contents from the float gauge or by weight.

  • MistakeFilling a container to the top.

    InsteadFill to about 80 in 100 by volume, or by weight to the filling density.

  • MistakeUsing a single-stage regulator on a new system.

    InsteadUse two-stage regulation.

  • MistakeExpecting a small tank to supply a large load on the coldest day.

    InsteadSize containers for vaporization at the design low temperature.

  • MistakeSkipping the leak check after a run-out.

    InsteadLeak check every time the gas has run out or the system was opened.

  • MistakeTreating a propane leak like a natural gas leak.

    InsteadPropane sinks and pools; ventilate low places and keep ignition sources away.

Summary and key terms

  • Propane is stored as a liquid under a vapour pressure that depends on temperature only, from about 10 kPa at −40 °C to about 1,268 kPa at 40 °C.
  • One volume of liquid makes about 270 of vapour; the vapour sinks; containers are filled to about 80 in 100.
  • Transport Canada cylinders are requalified 10 years from manufacture and every 10 years; small vapour cylinders have an OPD.
  • Tanks are ASME vessels, inspected at least every 10 years under the Ontario CAD.
  • Siting follows B149.2's tables.
  • Two-stage regulation gives about 70 kPa after the first stage and about 2.6 to 2.75 kPa at the appliances.
  • Vaporization falls with temperature and liquid level.
  • Underground tanks need cathodic protection.
  • Filling and construction heater set-up need a record of training; vehicle fuel systems follow B149.5.
  • Leak check after every run-out, and treat propane leaks as pooling hazards.
Vapour pressure
The pressure of propane vapour above its liquid in a closed container, set by the liquid's temperature.
Requalification
The periodic inspection or test a cylinder must pass before it may be refilled after its due date.
Overfilling prevention device
A float-operated valve in small vapour-withdrawal cylinders that stops filling at about 80 in 100.
Two-stage regulation
A first-stage regulator at the container and a second-stage regulator at the building, reducing pressure in two steps.
Vaporization rate
The rate at which a container can turn liquid propane into vapour, limited by heat flowing through its wetted wall.
Cathodic protection
Protecting buried steel from corrosion by connecting anodes that corrode in its place.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. Why does a tank's pressure gauge not show how much propane is left?

    Show answer

    Vapour pressure depends on temperature, not on the amount of liquid.

  2. To about what fraction of their volume are propane containers filled?

    Show answer

    About 80 in 100.

  3. What two pressures does two-stage regulation produce in a typical system?

    Show answer

    About 70 kPa after the first stage and about 2.6 to 2.75 kPa at the appliances.

  4. Why can a propane system fail on the coldest night of the year?

    Show answer

    The container cannot vaporize liquid fast enough at low temperature and low liquid level.

  5. What protects an underground steel tank from corrosion?

    Show answer

    Its coating and cathodic protection by sacrificial anodes.

Lesson quiz · 5 questions