GAS-350 · Lesson 10 of 12 · 41 min

Calculation practice

▶ Video coming soon A video version of this lesson is on the way.

On the Thursday after the last certification night, Maureen e-mailed Luis and Grant a single page: a formula sheet, followed by twenty problems with no answers. "Every one of these is a calculation from the program," she wrote. "Do them with a calculator and nothing else, against a clock, then check them against the worked answers in the course. For every one you get wrong, write down which trap caught you." Luis got sixteen. The four he missed were a unit conversion, a test pressure that ignored the minimum, an air-free CO calculated with the wrong oxygen, and a pipe size read from the shorter column. "Those are the four everyone misses," Maureen said. "Which is why they're on every exam."

This lesson is a workbook. It starts with the formula sheet, then works through problems from every part of the program, grouped by topic, each with the trap its wrong answers are usually built on. The sizing table is the program's invented practice table; the combustion air rate marked sample is invented too. Real work uses the code's tables and rates.

The formula sheet

A one-page formula sheet laid out in four boxes. Box one, gas flow and input: flow equals dial volume divided by seconds, times 3,600; input in kW equals flow in cubic metres per hour times heating value in MJ per cubic metre, divided by 3.6; natural gas 37.5 MJ per cubic metre, propane 93. Box two, pressure: 1 kPa is about 4.02 inches of water column; 1 psi is about 6.89 kPa; flow varies as the square root of pressure. Box three, combustion: air-free CO equals measured CO times 20.9 over 20.9 minus O2; excess air is about O2 over 20.9 minus O2. Box four, electrical and air: VA equals volts times amps; airflow in litres per second equals kW divided by 1.2 times 1.005 times the temperature rise.
The formula sheet Maureen gave her group. Every problem in this lesson uses one or more of these.

Input and flow

Worked problem

1. Clocking a natural gas appliance

A boiler is the only appliance running. The meter's 0.05 m³ test dial turns once in 45 s. Natural gas, 37.5 MJ/m³. What is the input?

Show solution
  1. Flow:
  2. \[\frac{0.05}{45} \times 3{,}600 = 4.0 \text{ m}^3/\text{h}\]
  3. Energy:
  4. \[4.0 \times 37.5 = 150 \text{ MJ/h}\]
  5. Input:
  6. \[\frac{150}{3.6} \approx 41.7 \text{ kW}\]

Answer: About 41.7 kW. The trap: forgetting the 3,600, which gives 0.0011 m³ per second and an answer a thousand times too small, or forgetting to divide MJ/h by 3.6.

Worked problem

2. Clocking a propane appliance

A propane appliance is the only one on the meter. The 0.05 m³ dial turns once in 120 s. Propane vapour, 93 MJ/m³. What is the input?

Show solution
  1. Flow:
  2. \[\frac{0.05}{120} \times 3{,}600 = 1.5 \text{ m}^3/\text{h}\]
  3. Energy:
  4. \[1.5 \times 93 = 139.5 \text{ MJ/h}\]
  5. Input:
  6. \[\frac{139.5}{3.6} \approx 38.8 \text{ kW}\]

Answer: About 38.8 kW. The trap: using the natural gas heating value, which gives 15.6 kW.

Worked problem

3. Correcting for an elevated-pressure meter

At Iron Kettle Brewing in GAS-330, the meter ran at 14 kPa gauge, with 100.0 kPa atmospheric pressure and gas at 10 °C, giving a combined correction factor of 1.1450. The 0.1 m³ dial turned in 12.8 s. What were the uncorrected and the real inputs?

Show solution
  1. Actual flow:
  2. \[\frac{0.1}{12.8} \times 3{,}600 = 28.13 \text{ m}^3/\text{h}\]
  3. Uncorrected input:
  4. \[28.13 \times \frac{37.5}{3.6} = 293 \text{ kW}\]
  5. Standard flow:
  6. \[28.13 \times 1.1450 = 32.21 \text{ m}^3/\text{h}\]
  7. Real input:
  8. \[32.21 \times \frac{37.5}{3.6} \approx 335.5 \text{ kW}\]

Answer: The kettle was really firing about 335.5 kW against a plate of 293 kW, overfired by about 14.5 in 100. The trap: forgetting the correction, which makes an overfired appliance look right.

Pressure

Worked problem

4. Overfiring by manifold pressure

A church hall boiler's manifold pressure is found at 1.05 kPa against a rating plate of 0.87 kPa. Flow varies as the square root of pressure. By roughly how much is it overfired?

Show solution
  1. Flow ratio:
  2. \[\sqrt{\frac{1.05}{0.87}} \approx 1.099\]

Answer: About 10 in 100 overfired, as in GAS-230. The trap: taking the pressure ratio itself, 1.21, as the flow ratio, which gives 21 in 100.

Worked problem

5. Unit conversion

A service delivers gas at 35 kPa. Express it in psi and in inches of water column.

Show solution
  1. In psi:
  2. \[\frac{35}{6.89} \approx 5.1 \text{ psi}\]
  3. In inches of water column:
  4. \[35 \times 4.02 \approx 141 \text{ in. w.c.}\]

Answer: About 5.1 psi or 141 in. w.c. The trap: multiplying by 27.7, the psi factor, instead of by 4.02.

Worked problem

6. Reducing a burner's input by pressure

A burner set at 0.87 kPa manifold pressure is to be turned down by 10 in 100 of its input, within the maker's allowed range. What manifold pressure gives that?

Show solution
  1. Input varies as the square root of pressure, so the pressure varies as the square of the input:
  2. \[0.87 \times 0.90^2 = 0.87 \times 0.81 \approx 0.70 \text{ kPa}\]

Answer: About 0.70 kPa. The trap: reducing the pressure by 10 in 100, to 0.78 kPa, which reduces the input by only about 5 in 100.

Combustion

Worked problem

7. Air-free CO

A fan-assisted furnace reads 8.2 in 100 O₂ and 38 ppm CO as measured. What is the air-free CO?

Show solution
  1. \[38 \times \frac{20.9}{20.9 - 8.2} = 38 \times \frac{20.9}{12.7} \approx 63 \text{ ppm}\]

Answer: About 63 ppm, the Mountview/Clintonville furnace from GAS-230. The trap: dividing by 20.9 minus the CO₂ reading, or using 21 instead of 20.9, which changes the answer slightly and can matter on a question with close options.

Worked problem

8. Excess air

A power burner reads 4.5 in 100 O₂. Roughly how much excess air is it running?

Show solution
  1. \[\frac{4.5}{20.9 - 4.5} = \frac{4.5}{16.4} \approx 0.27\]

Answer: About 27 in 100 excess air, a little above the typical power burner range of 15 to 25. The trap: answering 4.5, the oxygen reading itself.

Worked problem

9. Flue gas loss

A boiler's flue gas is 150 °C above the boiler room temperature and its CO₂ is 9.0 in 100. Using the rule of thumb from GAS-310, the dry flue gas loss is about 0.38 × ΔT ÷ CO₂ with ΔT in °C. What is the loss?

Show solution
  1. \[\frac{0.38 \times 150}{9.0} \approx 6.3\]

Answer: About 6.3 in 100 of the fuel's heat lost as dry flue gas. Lower the stack temperature or raise the CO₂ and the loss falls.

Worked problem

10. A worker's exposure

A technician's CO monitor logs 120 minutes at 18 ppm, 30 minutes at 70 ppm and 330 minutes at 3 ppm in an 8-hour shift. What is the time-weighted average?

Show solution
  1. \[\frac{120 \times 18 + 30 \times 70 + 330 \times 3}{480} = \frac{2{,}160 + 2{,}100 + 990}{480} \approx 10.9 \text{ ppm}\]

Answer: About 10.9 ppm, below Ontario's 25 ppm workplace limit. The trap: averaging the three readings without weighting them by time, which gives 30 ppm.

Piping and air supply

Worked problem

11. Sizing a main for a new load

A house has a 26 kW furnace and a 58 kW tankless water heater on a main whose longest length is 16 m. Using the practice table, what size is the main from the meter?

Show solution
  1. Load:
  2. \[26 + 58 = 84 \text{ kW}\]
  3. Column: next longer than 16 m is 18 m.
  4. In the 18 m column, 1 in. carries 70 kW, too little; 1-1/4 in. carries 147 kW.

Answer: 1-1/4 in., as the Fairhaven house needed in GAS-120 once its tankless heater was counted. The trap: using the shorter column, or forgetting how large a tankless heater's input is.

Worked problem

12. A sample combustion air fan

A boiler room has 300 kW of appliances. Using GAS-320's sample rate of 0.56 L/s per kW, what fan airflow would the practice method give? (Sample rate, for practice only.)

Show solution
  1. \[300 \times 0.56 = 168 \text{ L/s}\]

Answer: 168 L/s at the sample rate, with the fan interlocked and its airflow proven. On the exam, use the code's own requirement.

Electrical, air and propane

Quick problems. Cover the last two columns, work each one, then check.
ProblemWorkingAnswer and trap
13. Three zone valves at 0.30 A and a gas valve at 0.50 A on a 40 VA, 24 V transformer. Is it overloaded? What about a fourth zone?(3 × 0.30 + 0.50) × 24 = 33.6 VA; with four zones, (4 × 0.30 + 0.50) × 24 = 40.8 VAThree zones are within rating; four exceed 40 VA. Trap: forgetting to multiply by 24 V.
14. A 120 V igniter measures 60 Ω hot. What current and power?I = 120 ÷ 60 = 2.0 A; P = 120 × 2.0 = 240 W2.0 A and 240 W. Trap: using the cold resistance, which is different.
15. A furnace delivers 16.9 kW with a 30 °C rise. What is the airflow?16.9 ÷ (1.2 × 1.005 × 30) ≈ 0.467 m³/sAbout 467 L/s, the Okoye furnace in GAS-210. Trap: using input instead of output.
16. A propane cylinder holds 108 kg of water. What mass of propane may it hold at a filling density of 42 in 100?108 × 0.42 ≈ 45.4 kgAbout 45 kg, a standard 45 kg cylinder. Trap: using 80 in 100, which is a volume figure.
17. 2 L of liquid propane leaks into a closed room 3 m × 2.5 m × 2.4 m and vaporizes. What is the average concentration?2 × 270 = 540 L = 0.54 m³; room 18 m³; 0.54 ÷ 18 = 0.030About 3.0 in 100, inside propane's 2.1 to 9.5 range. Trap: forgetting the 270 expansion.
18. A purge must give at least four volume changes, and the fan moves the chamber volume in 22 s. What is the shortest purge?4 × 22 = 88 s88 s, in this example. Trap: dividing instead of multiplying. Real purge times come from the burner's certification.
19. A vent connector runs 3.5 m. What minimum rise does it need?3.5 × 20 = 70 mm70 mm. Trap: using 20 mm for the whole run.
20. A boiler's output is 240 kW. A relief valve rated 147 kW is fitted. Is it acceptable?The relief capacity must be at least the outputNo, as at Riverdale in GAS-320. Trap: comparing the valve with the input instead of the output, or not checking at all.

Working method

Maureen's advice for calculation questions on the exam is the same for every problem. Write the formula before the numbers. Write the units beside every number and cancel them as you go; a wrong unit at the end shows a wrong step. Estimate before you calculate: a house furnace is tens of kilowatts or tens of thousands of Btu per hour, not thousands; a manifold pressure is about 1 kPa, not 35. Then compare your answer with your estimate before choosing an option. If your answer is not among the options, do not choose the nearest one; look for the step you skipped, because the options are built from the steps people skip.

Three problems to try alone

Work these without looking at the answers, which follow each one.

  • A. A furnace's plate says 26 kW. You clock it at 0.05 m³ in 64 s. Is it overfired, underfired or about right? Answer: 0.05 ÷ 64 × 3,600 = 2.81 m³/h; × 37.5 ÷ 3.6 ≈ 29.3 kW, about 13 in 100 overfired.
  • B. An appliance reads 7.5 in 100 O₂ and 90 ppm CO. Another reads 3.0 in 100 O₂ and 80 ppm CO. Which is producing more carbon monoxide relative to its fuel? Answer: 90 × 20.9 ÷ 13.4 ≈ 140 ppm air-free; 80 × 20.9 ÷ 17.9 ≈ 93 ppm air-free. The first.
  • C. A section of the practice table's 30 m column must carry 50 kW. What size? Answer: 1/2 in. carries 13 kW, 3/4 in. 29 kW, 1 in. 53 kW; 1 in.

If you got all three, the formula sheet is working for you. If you missed one, find which trap from this lesson caught you and add it to your error log.

Using the calculator well

Exam calculators are simple, and the mistakes made with them are predictable. Enter long expressions in pieces and write down each intermediate result, so that a slip can be found. Do not round until the last step: rounding 28.125 to 28 and then multiplying by 1.1450 and 10.4 gives a different answer from the one the options were built on. Keep the units of the question: if the question is in kilopascals, answer in kilopascals, and if the options are in kW, convert the MJ/h at the end. And check the answer against the estimate you made before you started.

Common mistakes

  • MistakeForgetting the 3,600 seconds in an hour when clocking.

    InsteadFlow per hour is dial volume divided by seconds, times 3,600.

  • MistakeTaking the pressure ratio as the flow ratio.

    InsteadFlow varies as the square root of pressure.

  • MistakeForgetting the correction at elevated pressure.

    InsteadMultiply by the pressure and temperature factors.

  • MistakeAveraging exposures without weighting by time.

    InsteadMultiply each reading by its minutes and divide by the shift length.

  • MistakeReading the sizing table at the shorter length.

    InsteadAlways the exact or next longer length.

  • MistakeChoosing the nearest option when your answer is not listed.

    InsteadFind the step you skipped; the options are built from skipped steps.

Summary and key terms

  • Flow equals dial volume divided by seconds times 3,600; kW equals m³/h times MJ/m³ divided by 3.6, with 37.5 MJ/m³ for natural gas and 93 for propane.
  • At elevated pressure, multiply by the pressure and temperature factors. 1 kPa is about 4.02 in. w.c.; 1 psi is about 6.89 kPa.
  • Flow varies as the square root of pressure, so pressure varies as the square of the input.
  • Air-free CO is CO × 20.9 ÷ (20.9 − O₂); excess air is about O₂ ÷ (20.9 − O₂); dry flue gas loss is about 0.38 × ΔT ÷ CO₂ with ΔT in °C.
  • Time-weighted averages weight each reading by its minutes.
  • Size pipe from the exact or next longer column.
  • VA = V × I.
  • Airflow equals output divided by (1.2 × 1.005 × rise).
  • Propane expands about 270 times, and cylinders are filled by weight to about 42 in 100 of water capacity.
  • Write formulas and units, estimate first, and look for the skipped step.
Correction factor
The product of the pressure and temperature factors that converts a meter's actual volume to standard volume.
Square-root rule
The relationship that flow through an orifice varies as the square root of the pressure across it.
Filling density
The largest mass of propane a container may hold, as a fraction of the mass of water it could hold.
Estimate
A rough answer worked out first, used to check that the exact answer is reasonable.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. Why must you estimate before calculating on the exam?

    Show answer

    So that an answer with a wrong step, which will usually be among the options, stands out.

  2. A 0.05 m³ dial turns in 30 s. What is the flow?

    Show answer

    6.0 m³/h.

  3. By what factor must the manifold pressure change to cut input by a fifth?

    Show answer

    0.8² = 0.64, so to about 64 in 100 of the original pressure.

  4. A reading is 5.0 in 100 O₂ and 30 ppm CO. What is the air-free CO?

    Show answer

    30 × 20.9 ÷ 15.9 ≈ 39 ppm.

  5. What is the airflow trap in a temperature-rise problem?

    Show answer

    Using the input instead of the output.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.