GAS-120 · Lesson 10 of 12 · 22 min
Propane storage, cylinders and tank setbacks
▶ Video coming soon A video version of this lesson is on the way.
A week after the leak at the farm pit, the same customer near Grove City called Bayline again. She wanted to retire the row of 100 pound cylinders behind her farmhouse and switch to a single 500 gallon tank, large enough to add a standby generator. Luis Ferreira took Jonah to look. Before he even opened the truck door, Luis was pacing the yard: from the back wall of the house, from the kitchen window, from the dryer vent, from the property line along the lane. "The propane company owns the tank and sets it," he said. "But if we pick a spot that doesn't meet the setbacks, we wasted everybody's morning. So we check first."
This lesson introduces the code for propane storage and handling: NFPA 58, the Liquefied Petroleum Gas Code. It covers the types of containers, how cylinders are filled and handled, the general rules for where cylinders and tanks may go, and how the storage code divides responsibility with the installation code. Propane systems are studied in depth in a later course; here the aim is to know what the storage code covers and how to read its location rules.
Two codes, one system
Propane systems are covered by two sets of rules. NFPA 58 governs LP-gas storage, handling and transfer: cylinders and tanks, their valves and fittings, where they may be placed, piping and regulators that are part of the container installation, filling, and bulk plants. In Ohio, NFPA 58 is brought in through the Ohio Fire Code, enforced by the State Fire Marshal and local fire departments. The IFGC or RCO governs the building piping, appliances, venting and air supply downstream of the second-stage regulator outlet. The current editions of NFPA 58 and NFPA 54 are 2024; check which edition the Ohio Fire Code references.
Responsibility is usually divided in the field too. The propane supplier normally owns, sets and fills the tank, installs the first-stage regulator, and is responsible for the container installation. The gas contractor installs the piping, the second-stage regulator where agreed, the appliances and their venting. Both must make sure the parts meet. A tank in the wrong place is the supplier's problem to fix, but a contractor who designs the house piping around a tank location that cannot be approved has caused the problem.
Cylinders and tanks
Propane containers come in two broad types. A cylinder is a portable container built to a transport specification, the Department of Transportation's (DOT), such as a barbecue cylinder, a forklift cylinder or the 100 pound cylinders often used at houses. Cylinders are usually filled by weight at a filling station or exchanged, and they must be requalified at intervals; one past its requalification date must not be refilled. A tank is a larger stationary container built to the ASME pressure vessel code, and stamped with its ASME data plate, filled on site from a delivery truck. Tank sizes are given as water capacity in US gallons in both countries, so a 500 gallon tank is commonly called a 500 US gallon tank.
Containers are never filled full. Liquid propane expands a great deal as it warms, so every container is filled to leave vapor space, typically to about 80 in 100 of its volume. Tanks have a fixed maximum liquid level gauge, a small bleeder valve whose dip tube marks the maximum fill level, and a float gauge. Small cylinders for vapor service, such as barbecue cylinders, must have an overfilling prevention device (OPD), recognized by its triangular handwheel. Every container has a pressure relief valve in the vapor space that opens if the pressure gets too high, discharging propane to the air.
Worked problem
How much energy is in the tank?
The new tank has a water capacity of 500 gallons and will be filled to 80 in 100 of its volume. Propane holds about 91,500 Btu per gallon. How many hours could the full charge run an 80,000 Btu/h furnace alone?
Show solution
- Find the volume of propane in a full fill:
- \[500 \times 0.80 = 400 \text{ gal}\]
- Find the energy it holds:
- \[400 \times 91{,}500 = 36{,}600{,}000 \text{ Btu}\]
- Convert the furnace input to the same units per hour and divide:
- \[\frac{36{,}600{,}000}{80{,}000} \approx 458 \text{ h}\]
Answer: A full fill would run the furnace alone for about 458 hours at full fire, a little under three weeks of continuous running. Real use is spread over the season and shared with other appliances, and the supplier plans deliveries so the tank never runs low. Luis uses figures like these to explain why the generator and the furnace together need a larger tank or more frequent fills.
Where cylinders may go
The storage code keeps propane containers outdoors in almost all cases. Propane vapor is heavier than air and flows to low points, so a leak indoors can fill a basement. Cylinders connected to a building system are set outdoors on a firm, level, noncombustible base, upright so that the relief valve stays in the vapor space, and protected from vehicles and from falling ice and snow. Only a few specific uses, such as certain small cylinders in permitted occupancies, construction heaters and some industrial uses, may bring cylinders indoors, under strict limits.
The code sets distances from cylinders to building openings, sources of ignition and air intakes, measured from the relief valve discharge and, for cylinders filled on site, from the filling connection, because those are the places propane can escape. A cylinder's relief valve must not be close to a building opening below it, such as a basement window, where heavy vapor could flow in. The distances are larger for cylinders filled on site than for cylinders exchanged and taken away to be filled, because propane is vented during filling. Sources of ignition include air conditioner condensers, electrical outlets, dryer vents, appliance vent terminals and direct-vent air intakes.
Where tanks may go
For tanks, NFPA 58 provides a table of minimum separation distances that grow with the tank's water capacity. For aboveground ASME tanks, the table requires at least 10 feet from a building and from the line of adjoining property that can be built on for tanks of 125 to 500 gallons, and 25 feet for tanks of 501 to 2,000 gallons, with larger distances for bigger tanks. Smaller containers have no minimum to the building in the table, but the rules on relief valves, filling connections and openings still apply. Underground tanks up to 2,000 gallons need 10 feet. Separate rules measure from the relief valve discharge and the filling connection to building openings, sources of ignition and mechanical air intakes. Check the edition the Ohio Fire Code adopts and its notes, which allow some reductions.
Worked problem
Checking a proposed tank location
Luis measures a proposed spot 8 feet from the back wall of the farmhouse and 30 feet from the lane, which is also the property line. The tank is 500 gallons. Does the spot meet NFPA 58, and how far must the tank move?
Show solution
- Compare the distance to the building with the minimum:
- \[8 \text{ ft} < 10 \text{ ft}\]
- Find how far it must move away from the house:
- \[10 - 8 = 2 \text{ ft}\]
- Check that moving it keeps the property line distance:
- \[30 - 2 = 28 \text{ ft} \ge 10 \text{ ft}\]
- Check the relief valve and filling connection:
- Luis then measures from the tank's relief valve and fill connection to the basement window, the dryer vent and the new generator's air intake, and compares each with its own minimum.
Answer: The tank must move at least 2 feet farther from the house, which still leaves ample distance to the lane. Luis marks a new spot with paint, notes that the generator must be placed so its exhaust and intake keep their distances from the tank's relief valve, and sends the sketch to the propane supplier.
Regulators, piping and putting propane into service
Propane leaves the tank at its vapor pressure, which rises and falls with temperature, from a few hundred kilopascals on a cold day to well over 150 psi on a hot one. The codes require two-stage regulation for most building systems: a first-stage regulator at the tank reduces the pressure to about 10 psi, and a second-stage regulator at the building reduces it to appliance pressure, about 11 in. w.c.. Some systems use an integral two-stage regulator at the tank. Regulator vents must point down or be protected from rain, ice and insects, and must be placed away from building openings as the code requires.
Underground tanks and their buried steel piping need corrosion protection, usually by coating and sacrificial anodes. Tanks in flood areas must be anchored so that they cannot float away. Piping from the tank to the building follows the material rules of lesson 5, with plastic allowed underground only between the regulators where the code and the pipe certification permit.
When a propane system has been shut off or has run out of gas, it is not simply turned back on. The codes require a leak check of the system before service is restored, because appliance pilots may have gone out and valves may have been left open. NFPA 58 requires a leak check after an interruption of service, and most suppliers will not refill a tank that has run empty until a qualified person performs one. Every appliance is then relit and checked.
Propane appliances under the installation code
Downstream of the second-stage regulator, a propane system follows the same installation code as natural gas, with a few differences that matter. Appliances must be set up for propane, with the right orifices and regulator settings, and carry the conversion label if they were converted. Piping is sized from propane tables. And because propane is heavier than air, the codes restrict propane appliances in basements and pits in some situations and require extra care with relief valve discharges, regulator vents and the location of appliances below grade. Check the adopted code before installing a propane appliance in a basement.
Standby generators fueled by propane are increasingly common on rural properties like the one near Grove City. The generator is an appliance with a large input, so the tank, the regulators and the piping must be sized for it running together with the furnace and other loads on a cold day. The tank's ability to vaporize liquid into gas falls as the temperature drops, so a tank that is large enough on paper may not supply a big load in deep cold. The supplier sizes the tank and regulator for the peak load, and the contractor sizes the piping. The generator's exhaust and air intake must also keep their distances from the tank's relief valve and filling connection and from the building's openings.
Handling and transporting cylinders
Cylinders are carried to job sites in service vehicles every day. The rules for transporting them come from transport regulations as well as the storage code: cylinders secured upright in a ventilated space, valves closed and plugged or capped, and quantities kept within the limits for the vehicle. Never carry cylinders in a closed car trunk or a closed van without ventilation, and never leave them in a hot vehicle. When a cylinder is connected or disconnected at a site, check the connection for leaks before leaving, and close the cylinder valve on any cylinder that is not in use.
Common mistakes
MistakeStoring a spare cylinder in the basement.
InsteadKeep cylinders outdoors, except for the few uses the code allows indoors.
MistakeMeasuring tank setback from the regulator instead of the tank.
InsteadMeasure from the container shell for buildings and property lines, and from the relief valve and filling connection for openings and ignition sources.
MistakeLying a vapor cylinder on its side.
InsteadKeep it upright so the relief valve stays in the vapor space.
MistakeRefilling an out-of-date cylinder.
InsteadDo not fill a cylinder past its requalification date.
MistakeTurning gas back on after a run-out without checking.
InsteadLeak check the system, then relight and check every appliance.
Summary and key terms
- NFPA 58, brought in by the Ohio Fire Code, governs LP-gas storage, handling and transfer; the IFGC or RCO governs the building piping and appliances after the second-stage regulator. Cylinders are portable, filled by weight or exchanged, and must be requalified; tanks are stationary ASME containers filled on site and rated in US gallons.
- Containers are filled to about 80 in 100 to leave vapor space.
- Containers stay outdoors.
- Setbacks are measured from the container to buildings and property lines, and from relief valves and filling connections to openings, ignition sources and intakes.
- NFPA 58 requires 10 feet for 125 to 500 gallon aboveground tanks and 25 feet for 501 to 2,000 gallons. Systems use two-stage regulation and need a leak check after any interruption.
- Cylinder
- A portable propane container built to a transport specification, filled by weight or exchanged.
- Tank
- A stationary ASME propane container filled on site, rated by water capacity in US gallons.
- Vapor space
- The space left above the liquid in a container so the liquid can expand.
- Overfilling prevention device
- A device in small vapor cylinders that stops filling at the safe level.
- Setback
- A minimum separation distance between a container or its fittings and buildings, property lines, openings or ignition sources.
- Two-stage regulation
- Reducing tank pressure first at the container and again at the building to appliance pressure.
Practice problems
Work each problem on paper first, then reveal the answer to check.
Which code covers the propane tank, and which covers the house piping?
Show answer
NFPA 58 covers the tank; the IFGC or RCO covers the building piping and appliances.
Why are containers never filled full?
Show answer
Liquid propane expands as it warms and needs vapor space.
From which points are distances to building openings and ignition sources measured?
Show answer
The relief valve discharge and the filling connection.
Why must a propane cylinder stay upright?
Show answer
So that its relief valve stays in the vapor space.
What must happen before gas is restored after a propane run-out?
Show answer
A leak check of the system, then relighting and checking each appliance.
Lesson quiz · 5 questions
Score 60% or more to complete this lesson.