GAS-230 · Lesson 7 of 12 · 26 min
Combustion and ventilation air
▶ Video coming soon A video version of this lesson is on the way.
On Friday, October 2, Rosa and Jonah answered a call from a young couple in Stinson, below the Mountain, who had just finished their basement. Their contractor had built a neat utility room around the furnace and the water heater, about 2.4 m by 1.8 m, with drywall on every side, a solid door with weatherstripping "to keep the noise down", and a new laminate floor right up to the appliances. Since then the water heater's flame looked "lazy and orange" to the owner, the hot water ran out sooner, and the room smelled faintly sharp when the door was closed. Rosa held a smoke pencil at the water heater's draft hood with the door shut: the smoke rolled out into the room. With the door open, it was drawn straight in. "They built a beautiful closet," she said, "and forgot that two of the things in it breathe."
GAS-120 introduced what the code says about air supply. This lesson goes deeper: why appliances need air, how much they use, how air supply openings and ducts are sized and built, and the mistakes renovations make.
Three kinds of air
An appliance that burns room air needs three kinds of it. Combustion air supplies the oxygen the burner needs, about 9.6 volumes of air for every volume of natural gas in theory, and more in practice because every burner runs with excess air. Dilution air is drawn into a draft hood or barometric damper along with the flue gas, as lesson 2 showed, and can be as much again. Ventilation air carries away the heat that escapes from the appliance's casing, its vent connector and its hot water tank, so the room does not overheat and the controls, wiring and gas valve stay within their temperature ratings. A direct-vent appliance needs only ventilation air, and some need none if their casing stays cool.
Worked problem
How long would the utility room's air last?
The utility room is 2.4 m by 1.8 m with a 2.3 m ceiling. Its fan-assisted furnace is rated 23 kW and runs with about 60 in 100 excess air; its natural-draft water heater uses about 33.3 m³/h of room air, as lesson 2 calculated for a water heater of the same size. Estimate how many minutes the room's air would last if no air came in.
Show solution
- Room volume:
- \[2.4 \times 1.8 \times 2.3 = 9.94 \text{ m}^3\]
- Furnace gas and air:
- \[\frac{23 \times 3.6}{37.5} = 2.21 \text{ m}^3\text{/h} \qquad 2.21 \times 9.57 \times 1.6 = 33.8 \text{ m}^3\text{/h}\]
- Total air used:
- \[33.8 + 33.3 = 67.1 \text{ m}^3\text{/h}\]
- Time:
- \[\frac{9.94}{67.1} = 0.148 \text{ h} \approx 8.9 \text{ min}\]
Answer: With both appliances running, they would use the room's entire volume of air in about nine minutes. In reality air leaks in under the door and through gaps, but not fast enough: the room goes negative, the water heater's draft hood spills, the flame starves and turns lazy, and carbon monoxide rises. That was exactly what the smoke pencil showed.
Where the air comes from
In an older, leaky house, an open basement full of appliances usually gets enough air through the cracks of the building itself, because cold outside air leaks in all the time through the rim joist, around windows and doors and through the foundation, as lesson 1's stack effect described. The codes recognize this: in a space large enough compared with the input of the appliances in it, in a building that is not unusually airtight, the infiltration through the building is treated as the air supply. Once the appliances are shut into a small room, or the house is made much tighter with new windows, spray-foamed rim joists and sealed attic hatches, that assumption no longer holds, and the air has to be supplied on purpose: through openings to other parts of the house that have enough air, or through openings or ducts to the outdoors.
CSA B149.1 sets out the air supply requirements in its venting and air supply section. As GAS-120 explained, the required openings depend on the total input of the appliances in the space, whether they have draft control devices such as draft hoods or barometric dampers, whether they are in an enclosure or an open area, and how airtight the building is. For smaller installations the code provides tables that give the free area of the air supply opening or duct for a given input; for larger installations it gives rules based on so much free area per unit of input. Enclosures also need ventilation openings so the heat can escape. The Ontario amendments change some of these provisions, so Bayline's apprentices size every air supply from the code as adopted in Ontario and from the appliance instructions, never from a rule of thumb.
Sizing the air supply in the basement
Rosa did not guess. Back in the van she sized the air supply from the code as adopted in Ontario, using the total input of the two appliances, the fact that the water heater had a draft hood, and the fact that the utility room was now an enclosure in a house the renovation had made noticeably tighter. To practise the same method without copying the code's tables, Jonah used Bayline's sample practice table below, which follows the same idea with invented numbers.
| Total input up to | Sample free area, appliances with draft control | Sample free area, no draft control |
|---|---|---|
| 20 kW | 9,000 mm² | 4,500 mm² |
| 30 kW | 12,500 mm² | 6,500 mm² |
| 40 kW | 15,500 mm² | 8,000 mm² |
| 50 kW | 18,500 mm² | 9,500 mm² |
Worked problem
Sizing the air supply
The furnace is 23 kW and the water heater 11.7 kW, and the water heater has a draft hood. Using the sample practice table, find the free area of the outdoor air supply and the smallest standard round duct, in 25 mm steps, that provides it.
Show solution
- Total input:
- \[23 + 11.7 = 34.7 \text{ kW}\]
- Enter the sample table at the next row up, 40 kW, appliances with draft control:
- \[15{,}500 \text{ mm}^2\]
- Diameter of a round duct with that area:
- \[d = \sqrt{\frac{4A}{\pi}} = \sqrt{\frac{4 \times 15{,}500}{3.1416}} = \sqrt{19{,}735} = 140 \text{ mm}\]
- Next standard size:
- \[150 \text{ mm}\]
Answer: On the sample table, the outdoor air duct needs 15,500 mm² of free area, which a 150 mm round duct provides. Rosa's real calculation, from the code, gave the same duct size.
Free area: what the grille lets through
Every opening's size in the code is a free area: the actual open area through which air can pass, after the grille's blades, the screen and the frame are taken out. A grille that measures 300 mm by 150 mm across its face might have only half or two-thirds of that as free area. Grille makers state the free area of each model; where it is unknown, the code as adopted tells the installer how to treat the grille. Screens on outdoor openings must not be finer than 6 mm mesh, because fine screens clog with lint, insects and frost.
Worked problem
How big a grille gives the free area?
Rosa wants door grilles with at least 20,000 mm² of free area each for ventilation between the utility room and the basement. The grilles she carries have a stated free area of 60 in 100 of their face. What is the smallest face area, and does a 300 mm by 125 mm grille work?
Show solution
- Face area needed:
- \[\frac{20{,}000}{0.60} = 33{,}333 \text{ mm}^2\]
- Face area of the grille:
- \[300 \times 125 = 37{,}500 \text{ mm}^2 \ge 33{,}333\]
- Its free area:
- \[37{,}500 \times 0.60 = 22{,}500 \text{ mm}^2\]
Answer: A 300 mm by 125 mm grille gives 22,500 mm² of free area, enough for the 20,000 mm² target.
Building the air supply
An outdoor air duct is built of rigid metal duct, sealed at its joints, run as directly as practical. It is usually insulated, because cold air in winter will form condensation on the outside of the duct and can freeze nearby water pipes; many installers end the duct inside the room close to the floor, with a loop or a drop that keeps cold air from spilling across the room while the appliances are off. The outdoor opening is protected by a screened hood, placed where snow and leaves will not block it, away from vents and exhausts that could contaminate the air, and higher than the expected snow. Square or rectangular ducts must not be so flat that they choke: the codes set a minimum dimension, commonly 75 mm.
Two rules about air supplies come up again and again. Manual dampers are not allowed in combustion air openings or ducts, because someone will close them. Motorized dampers are allowed only if they are interlocked so that the burners cannot fire unless the dampers are proven fully open. And the openings themselves must be labelled and kept clear: Bayline sticks a small label on each grille reading that it supplies air to gas appliances and must not be covered or blocked, because the most common cause of a failed air supply in an older house is a homeowner who stuffed a towel into a cold, drafty grille.
| Problem | What it causes |
|---|---|
| Appliances enclosed in a small, tight room | Negative room pressure, spillage, starved flames, CO |
| New windows, sealed rim joists and attic | Less infiltration; the house no longer supplies the air the code assumed |
| Grille blocked by boxes, a towel or insulation | The air supply no longer exists |
| Combustion air drawn from a laundry, salon or pool room | Chlorine and fluorine compounds that corrode heat exchangers |
| Air duct ending near a water line | Frozen pipes in cold weather |
| Outdoor hood buried in snow or leaves | No air on the coldest days |
Air quality matters too
The air supplied to a burner must be clean as well as plentiful. Vapours from bleach, laundry detergents and fabric softeners, paint strippers, hair-salon chemicals, refrigerants, swimming-pool chemicals and some aerosols contain chlorine or fluorine compounds. When these pass through a flame they form acids that condense on cooler surfaces and attack heat exchangers, vent connectors and burners, often leaving a white powder or rusty scale. A furnace beside a laundry room in a busy household can corrode in a few years. Appliance instructions warn against these locations and often require outdoor combustion air where contaminants are present, which is one more reason Bayline prefers direct-vent appliances.
Checking an existing air supply on a service call
Most air supply problems are found not on new installations but on routine service calls, years after a renovation. Bayline's maintenance checklist asks the technician to look at the appliance space with fresh eyes every time. Has the room changed since the last visit? A new wall, a new door, a new laundry, a new workshop or storage shelves packed against the furnace all change the air supply. Are the openings and ducts still there, still clear and still the size they were? Is the outdoor hood blocked, crushed or painted over? Is the duct insulated and intact, or has a mouse made a nest in it? Has the house been tightened, with new windows, doors, insulation or a heat recovery ventilator, and is the ventilator balanced? Has an appliance been added, such as a gas dryer or a second water heater, so that the total input is now higher than the opening was sized for?
The technician then tests what the eye cannot see. With the door to the appliance room closed, as the owner normally keeps it, and the appliances running, a smoke test at each draft hood shows whether the room's pressure lets the vents draw. A digital manometer with one tube in the room and the other under the door, or to the outdoors, shows how far the room goes negative when the burners fire and when the house's fans run, which lesson 8 develops into a full worst-case test. And the analyzer, which lessons 9 and 10 cover, shows whether a starved burner is making carbon monoxide. A starved flame is often the first clue: yellow tips, a flame that lifts and wanders, soot on the burner, or a water heater whose hot water runs out sooner than it used to because its burner is not getting enough air to fire at its rating.
A room that runs hot is the other clue. If the walls, the ceiling joists or the top of the furnace cabinet feel very warm, or if the room is noticeably hotter than the rest of the basement, ventilation air is not carrying the heat away. Gas valve bodies, control boards and wiring all have temperature ratings, and a closet that cooks them shortens their life and can trip limits. Bayline records the room temperature with the other readings when a room feels warm, and treats a hot room as an air supply problem until proven otherwise.
Back in the basement
The owners agreed to the work that afternoon. Bayline installed a 150 mm insulated outdoor air duct from a screened hood high on the back wall, ending near the utility room floor, and two door grilles for ventilation, each labelled. With the door closed and the furnace and water heater both firing, Rosa's smoke test showed the draft hood drawing within 30 seconds, the water heater's flame stood blue and sharp, and the flue gas carbon monoxide was low. She told the owners to leave the grilles and the duct alone, and to call before finishing any more of the basement.
Common mistakes
MistakeAssuming a finished basement still gets enough air from leakage.
InsteadEnclosing appliances or tightening the house removes the infiltration the code assumed; size an air supply.
MistakeUsing a grille's face size as its free area.
InsteadUse the stated free area, or the code's assumption when it is unknown.
MistakeInstalling a manual damper in a combustion air duct.
InsteadManual dampers are not allowed; motorized ones must be interlocked.
MistakeRunning an uninsulated outdoor air duct beside water pipes.
InsteadInsulate the duct and keep it away from pipes that could freeze.
MistakeTaking combustion air from a laundry or pool room.
InsteadContaminated air corrodes appliances; use outdoor air or a direct-vent appliance.
Summary and key terms
- Appliances that burn room air need combustion air, dilution air for draft hoods and ventilation air to remove heat; together they can use a small room's air in minutes.
- In a large space in a leaky building the codes treat infiltration as the supply, but enclosures and tight houses need deliberate openings to other spaces or to the outdoors.
- CSA B149.1 sizes the air supply from the total input, the appliance types, enclosure and building tightness, using its tables and rules as adopted in each province. Sizes are free areas, after grilles and screens.
- Manual dampers are not allowed, motorized dampers must be interlocked, ducts are insulated and openings labelled and kept clear.
- Combustion air must also be free of chlorine and fluorine compounds.
- Combustion air
- Air that supplies oxygen to a burner.
- Ventilation air
- Air that removes heat from around an appliance and its space.
- Free area
- The open area of an opening after grilles and screens are taken into account.
- Enclosure
- A small room or closet containing appliances.
- Infiltration
- Outdoor air leaking into a building through cracks and gaps.
- Outdoor air duct
- A duct bringing air from outdoors to an appliance space.
- Interlocked damper
- A motorized damper that must be proven open before burners can fire.
Practice problems
Work each problem on paper first, then reveal the answer to check.
What are the three kinds of air a draft-hood appliance in a room needs?
Show answer
Combustion, dilution and ventilation air.
Why can a renovation create an air supply problem in a house that had none?
Show answer
Enclosing the appliances or tightening the house removes the infiltration they relied on.
What is free area?
Show answer
The open area of an opening after grilles and screens are taken out.
Why are manual dampers not allowed in combustion air ducts?
Show answer
Someone will close them.
Name two sources of contaminated combustion air.
Show answer
Laundry chemicals and pool or salon chemicals.