GAS-210 · Lesson 11 of 12 · 23 min
Annual service and maintenance
▶ Video coming soon A video version of this lesson is on the way.
Bayline's maintenance plan customers get one visit a year, and most of those visits fall between September and November, before the cold weather. On Thursday, October 29, Rosa gave Jonah his first full maintenance visit to lead, at a 1980s house on Sherman Avenue South with a condensing furnace, an atmospheric storage water heater and a direct-vent fireplace. She would watch, help where asked and sign at the end. Jonah had Bayline's service checklist on a tablet, three pages long. "Don't rush the list and don't skip lines because last year was fine," Rosa said in the van. "The point of annual service is that something changes in a year. Your job is to find what changed."
This lesson covers the routine service of residential gas appliances: why it matters, what is checked on each appliance, the measurements that make a service visit more than a cleaning, and the records that let the next technician see what changed. Diagnosing faults once they appear is the subject of GAS-340; this lesson is about finding them before they appear.
Why annual service matters
Gas appliances fail slowly and then suddenly. A filter loads with dust over months, a heat exchanger cracks after years of hot cycles, a condensate trap fills with sludge, a flame arrestor clogs with lint, a vent terminal is buried by a new deck, a bird nests in an intake. Each of these starts as a small change that a careful technician can see and fix in minutes, and each can end in a no-heat call on the coldest night, a flooded basement, or carbon monoxide in the house. Annual service is the routine that catches them in between.
Service also keeps appliances efficient: a furnace with a dirty filter, a blower wheel caked with dust or burners out of adjustment burns more gas for the same heat. And it keeps warranties valid, because most manufacturers require regular maintenance by a qualified technician and may ask for records. In Ontario, there is no law requiring homeowners to have their gas appliances serviced, but TSSA, Enbridge Gas and manufacturers all recommend yearly service by a certified gas technician.
The order of a service visit
Bayline's checklist starts before any appliance is touched. On arrival, the technician walks in with a CO monitor switched on and notes the reading at the door, in the furnace room and near the appliances, because a reading taken after the doors are open and appliances are running tells less. They ask the customer whether anything has changed: a renovation, new windows, a new range hood, a smell, a noise, headaches. They check the CO alarms. Only then do they start on the appliances, beginning with a look at how each is operating before anything is cleaned, so that the as-found condition is recorded.
Servicing a furnace
On the furnace, the technician checks and replaces the filter, inspects the vent and intake from the furnace to the terminations outdoors for damage, sagging, separated joints, blockage and clearances, and checks that nothing new has been built or planted near the terminals. With power and gas off, they inspect the burners for rust, dust and debris and the igniter for cracks, and clean the flame sensor as its instructions allow, recording its signal later; GAS-220 explains what the signal means. They check the inducer and the pressure switch hoses for cracks and water, and on a condensing furnace they remove, clean and refill the condensate trap, flush the drain, and check the neutralizer's media and any condensate pump.
They inspect the heat exchanger as far as the instructions and access allow, using a light and mirror or a camera, looking for cracks, holes, rust-through and soot, and they watch the flames when the blower starts: a flame that moves, lifts or changes colour when the blower comes on is a classic sign of a breached heat exchanger. The blower wheel and motor are checked for dust and wear, the run capacitor measured on PSC motors as GAS-130 showed, and the motor current compared with the nameplate. With the furnace running, the technician measures the inlet and manifold pressures, the temperature rise and the external static pressure, takes a combustion analysis and checks that the safety controls work. The thermostat's operation and any humidifier or air cleaner are checked last.
Worked problem
A filter changes the static pressure
On arrival, Jonah measures +75 Pa in the supply and −115 Pa in the return, against a plate maximum of 125 Pa. After replacing the filter, the return reads −50 Pa and the supply is unchanged. What was the external static pressure before and after?
Show solution
- Before, adding the readings without regard to sign:
- \[75 + 115 = 190 \text{ Pa}\]
- After:
- \[75 + 50 = 125 \text{ Pa}\]
Answer: The dirty filter had pushed the static pressure to 190 Pa, half as much again as the maximum, starving the heat exchanger of air. With a clean filter it was back to 125 Pa. Jonah recorded both readings so the customer could see what the filter had been doing, and recommended changing it every three months.
Servicing a storage water heater
On an atmospheric water heater, the first check is the draft: with the water heater firing and the house's exhaust appliances running, the technician checks for spillage at the draft hood with a smoke pencil or mirror, and inspects the vent connector for slope, joints and corrosion. They look at the burner flame through the sight glass, and on an FVIR heater they clean the flame arrestor or air inlet screen, the part that clogs with lint and dust. They check the gas control for error codes, the thermocouple or igniter, and the gas connection for leaks.
On the water side, the technician lifts the T&P valve lever briefly to confirm it opens and reseats, and checks that the discharge line is intact and unobstructed. Where the instructions call for it, they drain a few litres from the bottom to remove sediment, which insulates the tank bottom, makes the burner roar or rumble and shortens the tank's life. Every few years, the anode rod is pulled and inspected, and replaced if it is consumed. They check the water temperature at a tap and the mixing valve, if there is one, and the expansion tank's charge.
At the Sherman Avenue house, the water heater was the find of the day. It sat in a laundry room beside the dryer, and its air inlet screen was matted with lint. The flame was lazy and yellow-tipped, and Jonah's analyzer at the draft hood showed a high carbon monoxide reading. He shut the water heater off, let it cool, removed and cleaned the screen as its instructions describe, cleared lint from the combustion chamber area, and restarted it. The flame came back blue and steady, and the CO fell to a normal level.
Worked problem
Air-free carbon monoxide
GAS-110 introduced air-free CO, which corrects a measured CO reading for the dilution air in the sample. Before cleaning, Jonah's analyzer read 140 ppm CO with an oxygen reading of 9.5 parts in 100 by volume in the water heater's flue sample above the flue tube. After cleaning, it read 30 ppm CO with an oxygen reading of 9.0 parts in 100. What were the air-free CO values?
Show solution
- Air-free CO is the measured CO multiplied by 20.9 divided by 20.9 minus the oxygen reading:
- \[\text{CO}_{af} = 140 \times \frac{20.9}{20.9 - 9.5} = 140 \times \frac{20.9}{11.4} \approx 257 \text{ ppm}\]
- After cleaning:
- \[\text{CO}_{af} = 30 \times \frac{20.9}{20.9 - 9.0} = 30 \times \frac{20.9}{11.9} \approx 53 \text{ ppm}\]
Answer: Air-free CO fell from about 257 ppm to about 53 ppm. Bayline compares air-free readings with the manufacturer's limit and its own action levels; the before reading was well above them and the after reading within them. GAS-230 covers combustion analysis in full.
Servicing tankless heaters and combination systems
A tankless water heater's service centres on scale. Using the isolation valves fitted at installation, the technician pumps the descaling solution the maker specifies through the heat exchanger for the time the instructions give, then flushes it with fresh water. They clean the inlet water filter screen, check the condensate trap and neutralizer, inspect the vent and intake, read the unit's error history, which often reveals intermittent problems the customer never noticed, and check the gas pressures and combustion. On a combination system, the water side gets the extra checks lesson 6 described: the mixing valve, the anti-stagnation cycle, the loop pressure and relief valve on a boiler, and the air handler's filter.
Servicing a fireplace
A fireplace service starts with the glass, which is removed as the instructions describe and cleaned with the maker's cleaner, never an abrasive or ammonia product, and with the gasket inspected before the glass is refitted. The barrier screen must be present and secure; if an older unit has none, the customer is offered one. The logs and media are checked against the diagram, since owners and cleaners often move them, and soot is cleaned off. The pilot assembly is cleaned, the pilot flame's envelope on the thermocouple or flame sensor checked, and on a millivolt system the thermopile's output measured as GAS-130 described. The vent termination outdoors is checked for clearances and blockage, and the remote, wall switch and blower tested.
At the Sherman Avenue fireplace, two logs had been moved. The owner's teenager had rearranged them to make the flame "look more like a campfire", and the glass had a grey film of soot. Jonah put the logs back where the diagram showed, cleaned the glass and the soot off the logs, and ran the fireplace for fifteen minutes. The flame no longer touched the front log, and the glass stayed clear. He explained to the owner why the logs had to stay where they were.
| Appliance | Common annual finding | Why it matters |
|---|---|---|
| Furnace | Dirty filter, high static pressure | Overheated heat exchanger, limit trips, cracking |
| Condensing furnace | Sludge in the condensate trap | Pressure switch trips, water damage |
| Storage water heater | Lint-clogged flame arrestor | Poor combustion, CO, thermal cutoff trips |
| Atmospheric appliances | Spillage after house changes | CO entering the living space |
| Tankless heater | Scale in the heat exchanger | Reduced flow, overheating, error codes |
| Fireplace | Logs moved, sooty glass | Flame impingement, CO, glass damage |
| Any vented appliance | Blocked or buried terminal | Lockouts, flue gas re-entering the house |
Records and recommendations
Every service visit ends with a service report that records the as-found and as-left conditions and readings: CO on arrival, gas pressures, temperature rise, static pressure, combustion readings, flame sensor signal, capacitor value, motor current, water temperature, and every part replaced or cleaned. A report that says only "cleaned and checked" is useless the following year. A report with numbers lets the next technician see a trend: a flame signal falling year by year, a static pressure creeping up, a CO reading rising.
The report also records any unsafe condition and what was done about it, following the procedures GAS-110 described, and any recommendations, stated plainly with their reasons: replace the water heater within a year because the tank is weeping at a fitting, add a CO alarm near the bedrooms, move the laundry products away from a single-pipe furnace. Rosa's rule is that recommendations are made for safety and the customer's benefit, never to sell, and that the customer should be able to read the report and understand what was found.
Jonah's report for the Sherman Avenue visit listed the filter and static pressure readings, the condensate trap cleaned and refilled, the water heater's flame arrestor cleaned with the before and after CO readings, the fireplace logs repositioned, the CO alarms tested, and one recommendation: replace the CO alarm in the basement, whose date showed it was past the age its maker recommends. Rosa read it twice, changed one word, and signed it. "Next year," she said, "whoever comes here will know exactly what to look at first."
Common mistakes
MistakeOpening doors and running appliances before taking a CO reading on arrival.
InsteadRead CO at the door and near the appliances before changing anything.
MistakeCleaning first and recording afterwards.
InsteadRecord the as-found condition, then service, then record the as-left condition.
MistakeSkipping the spillage test because the water heater has worked for years.
InsteadTest draft every visit; house changes can cause spillage at any time.
MistakeWriting "cleaned and checked" on the report.
InsteadRecord every reading and part, as found and as left.
MistakeCleaning fireplace glass with household glass cleaner.
InsteadUse the maker's cleaner and check the gasket before refitting.
Summary and key terms
- Annual service catches slow changes before they become failures, keeps appliances efficient and keeps warranties valid.
- Start with CO on arrival, customer questions and CO alarms, and record the as-found condition.
- On furnaces, check the filter, vent and intake, burners, igniter and flame sensor, inducer and hoses, condensate trap and drain, heat exchanger, blower and capacitor, then measure pressures, temperature rise, static pressure and combustion and test the safety controls.
- On storage water heaters, test draft, clean the flame arrestor, check the T&P valve, flush sediment and inspect the anode.
- Descale tankless heaters.
- On fireplaces, clean the glass, check the gasket, barrier, logs, pilot and termination.
- Write a report with every reading as found and as left, unsafe conditions and plain recommendations.
- As-found condition
- The state and readings of an appliance before any service work is done.
- As-left condition
- The state and readings of an appliance when the technician leaves.
- Air-free CO
- A CO reading corrected for the dilution air in a flue gas sample.
- Sediment
- Mineral deposits that settle at the bottom of a storage water heater tank.
- Descaling
- Pumping a mild acid solution through a heat exchanger to dissolve mineral scale.
- Service report
- The written record of a service visit, its readings, work and recommendations.
- Trend
- A change in a reading over successive visits that points to developing wear or a fault.
Practice problems
Work each problem on paper first, then reveal the answer to check.
Why is CO measured on arrival before anything is changed?
Show answer
To capture the house's condition before doors are opened and appliances run differently.
Name two signs of a breached heat exchanger.
Show answer
Flames that move, lift or change colour when the blower starts, and visible cracks, holes or soot.
What clogs an FVIR water heater's air inlet in a laundry room?
Show answer
Lint and dust.
Measured CO is 60 ppm at an oxygen reading of 8.5 parts in 100. What is the air-free CO?
Show answer
60 × 20.9 ÷ 12.4 ≈ 101 ppm.
Why record readings rather than writing "checked"?
Show answer
Numbers show trends from year to year; a tick does not.
Lesson quiz · 5 questions
Score 60% or more to complete this lesson.