Electrical hazards and temporary power

Every trade on a construction site works with electricity, even the trades that never touch a panel. Maya plugs her press tool and threading machine into temporary power on every floor, drills and cores through slabs and walls that may contain live conduit, cuts metal pipe that may be part of the building's grounding system, and works near the electricians as they energize new circuits. Electrical contact is one of the leading causes of traumatic deaths in construction, and many of the people killed are not electricians. They are workers who contacted an overhead line with a ladder or a boom, drilled into a live cable, or used a damaged cord in a wet area.

This lesson covers what every non-electrical worker needs to know. Electrical work itself, opening panels, working on circuits and testing, is for licensed electricians and electrical apprentices under supervision, and is covered in the electrician courses in the Skilled Trades stream.

How electricity hurts people

Electricity injures in four main ways. A shock happens when current passes through the body, which can stop the heart, stop breathing or cause internal burns along the current's path. Burns happen where current enters and leaves the body, and from the intense heat of an arc. An arc flash is an explosive release of energy when current jumps through the air between conductors, which can cause severe burns and blast injuries several feet away. And a shock that is not itself serious can make a worker jerk back and fall from a ladder or platform.

The danger of a shock depends mainly on the amount of current, its path through the body and how long it flows. Remarkably small currents are dangerous. The figures below are approximate, widely used guides for household-frequency alternating current; individual responses vary.

Approximate effects of household-frequency current on the body.
Current through the bodyTypical effect
About 1 milliampereA faint tingle; the threshold of feeling
About 5 milliamperesA noticeable, painful shock; most people can let go
About 10 to 20 milliamperesMuscles contract; a person may be unable to let go of the conductor
About 50 to 100 milliamperes and aboveVentricular fibrillation of the heart is possible; often fatal without immediate CPR and defibrillation
Several amperesCardiac arrest, severe internal and external burns

A typical household circuit can deliver thousands of times more current than it takes to kill. What limits the current through a person is mostly the resistance of their skin and body, and that resistance drops sharply when skin is wet, sweaty or broken, or when the person is standing in water or on a damp concrete floor.

# Ohm's law: current = voltage / resistance (rough illustration only)
voltage = 120   # volts, a standard receptacle
for condition, resistance in [("Dry skin, dry floor", 100_000),
                              ("Sweaty hands", 5_000),
                              ("Wet skin, standing in water", 1_000)]:
    current_ma = voltage / resistance * 1000
    print(f"{condition:30s} about {current_ma:6.1f} mA")
Output
Dry skin, dry floor            about    1.2 mA
Sweaty hands                   about   24.0 mA
Wet skin, standing in water    about  120.0 mA

The numbers are a rough illustration, not a prediction for any real shock, but the point is clear. The same 120-volt receptacle that gives a tingle through dry skin can drive a current in the fibrillation range through wet skin. That is why water and electricity are such a dangerous combination on construction sites, where cords run through puddles, workers sweat in summer, and new concrete floors stay damp for weeks.

Temporary power on site

Kingsway Tower is powered by temporary panels fed from a construction service at the street. Each floor has a temporary distribution panel with receptacles, and trades plug in extension cords to reach their work. Temporary power is a common source of electrical incidents because cords get run over, pinched in doors, dragged through water and repaired with tape.

OSHA requires employers to protect workers on construction sites from ground faults on temporary power. Under 1926.404(b)(1), the employer must use ground fault circuit interrupters (GFCIs) on 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring, or run an assured equipment grounding conductor program, a written program of regular testing and inspection of cords and equipment. Most contractors use GFCIs, and many use both. A GFCI constantly compares the current going out on the hot conductor with the current returning on the neutral. If some current is leaking to ground, perhaps through a person, it trips in a fraction of a second. GFCIs for personnel protection trip at about 5 milliamperes, below the level that causes ventricular fibrillation.

Schematic of a GFCI receptacle supplying a drill: the hot and neutral conductors pass through a sensing coil, and when a fault sends current through a worker to ground, the imbalance trips the contacts open
How a GFCI protects a worker.

A GFCI is only useful if it works. Maya presses the test button on the GFCI or portable GFCI cord before plugging in at the start of each shift; the device should trip, and the reset button should restore power. If it does not trip, she does not use it and reports it. A GFCI that trips repeatedly is telling her something is wrong with her cord or tool; it should never be bypassed.

Cords and tools

Rules for cords and portable tools.
Check or ruleWhy
Inspect cords and tools before each use: jacket intact, no exposed wires, plug and connector undamaged, ground pin presentDamaged insulation and missing ground pins are the most common electrical defects on sites
Use cords rated for hard or extra-hard usage and for outdoor use, of a size suited to the length and loadLight cords overheat and are easily damaged
Never remove the ground pin or use an adapter that defeats groundingThe ground path is what trips the breaker or GFCI in a fault
Do not repair cords with tape; remove damaged cords from serviceTaped jackets hide damage and fail again
Run cords overhead or along walls, away from doors, sharp edges, vehicles and waterPrevents damage and trip hazards
Do not daisy-chain extension cords or overload themLong chains drop voltage, overheat and multiply connection points
Unplug by pulling the plug, not the cordPulling the cord damages the connection
Keep tools and cords dry; do not use corded tools while standing in waterWater lowers body resistance and creates current paths
Use double-insulated or grounded tools; prefer battery tools in wet areasBattery tools remove the cord hazard altogether

Battery tools have changed this picture on many sites. Northbridge now issues battery press tools, drills, saws and work lights to most of its crews, and corded tools are used mainly for heavy equipment such as core drills and threading machines. Fewer cords means fewer trip hazards, fewer damaged cords and fewer chances for a shock in a wet area. Batteries bring their own, smaller hazards: a damaged or overheated lithium-ion battery can catch fire, so Maya charges batteries only on the chargers supplied, away from combustible material, and takes any swollen or damaged battery out of service.

Contractors running an assured equipment grounding conductor program must test cords and tools at set intervals and mark them, often with colored tape that changes every quarter; Kingsway Tower uses the color code even though it relies on GFCIs, and a cord without the current color is not allowed on site.

Drilling, coring and cutting

Plumbers make many holes: sleeves through slabs, holes through studs and blocks, openings in existing walls. In a new building most cables and conduits are installed after the plumbing rough-in, but not all of them, and in renovations walls and slabs can hide live cables anywhere. A core drill or saw that hits a live cable can energize the tool and the worker, and can start a fire.

Precautions before drilling, coring or cutting.
Before drilling or cuttingWhy
Check the drawings and ask the electricians what is in the slab or wallConduits embedded in slabs and walls are shown on drawings and known to the electrical crew
Scan concrete with a ground-penetrating radar or similar scanner before coringLocates conduit, rebar and post-tensioning tendons; cutting a tendon is a serious hazard of its own
In existing buildings, have the circuits in the area isolated and locked out where possibleRemoves the energy instead of relying on finding the cable
Use tools with insulated grips and a GFCI; use a wet core drill only with GFCI protectionLimits the current if contact occurs
Stop immediately if the tool hits metal unexpectedly, and get the area checkedContinuing can cut deeper into a cable

Kingsway Tower's floors are post-tensioned concrete, with high-strength steel tendons under very high tension running through the slab. Cutting one can release it violently and weaken the structure. Every core hole on the site is laid out from the drawings and scanned before drilling, and the scan is checked by Stonebridge. Maya's job, as a new worker, is never to core without a scan and a sign-off.

Metal pipe and bonding

One electrical hazard belongs especially to plumbers. Metal water piping in a building is bonded to the electrical grounding system, and in some buildings current can flow through the piping because of wiring faults or an open neutral in the electrical service. If a plumber cuts a metal water pipe that is carrying current, the plumber's body can complete the circuit between the two cut ends.

The precaution is simple and is part of Northbridge's procedure for cutting existing metal piping: before cutting, attach a bonding jumper cable with clamps on each side of the cut, so the current has a path that bypasses the gap. Remove the jumper only after the new section is installed and the pipe is continuous again. If Maya feels a tingle when she touches a pipe, she stops and calls an electrician.

Overhead and buried lines

Contact with overhead power lines by cranes, boom trucks, ladders, scaffolds and long pipe is one of the most common causes of electrical deaths in construction. OSHA's general rule for unqualified workers and their equipment is to keep at least 10 ft away from overhead lines up to 50,000 volts, with greater distances for higher voltages, and the crane standard sets a 20-ft distance for lines up to 350,000 volts unless the voltage is confirmed and smaller distances are planned. Buried cables are just as dangerous for anyone digging; before any excavation, the locations of underground utilities must be marked, through the national 811 call-before-you-dig number.

Side view of an overhead power line next to the site with a boom lift and a worker carrying a long pipe, showing the minimum approach distance as a dashed zone around the line that no person, tool or material may enter
Keep out of the minimum approach zone around overhead lines.

At Kingsway Tower, the overhead lines along the street were covered with insulating sleeves by the utility before work began, and the crane's operation is planned to keep loads well away. Maya's part is simple: never carry long pipe or ladders upright near the street, look up before raising anything, and never assume a line is dead or insulated.

If someone is shocked

If a co-worker is being shocked, the first instinct is to grab them, and that can make two casualties. Do not touch the person while they are in contact with the source. Shut off the power at the switch, breaker or plug if you can do it quickly and safely. If you cannot, and the voltage is low, push them clear with a dry non-conductive object such as a wooden broom handle. Never approach anyone in contact with an overhead line or a downed line; keep everyone back and call the utility and emergency services. Once the person is clear of the source, call for help, start CPR if they are not breathing normally and use an AED if one is available. Anyone who has had an electrical shock needs medical assessment, even if they feel fine, because heart rhythm problems can appear later. Lesson 12 covers first aid and emergency response.

Common mistakes

  • MistakeUsing a cord with a damaged jacket because it still works.

    InsteadRemove it from service; damaged insulation is a shock hazard.

  • MistakeBypassing a GFCI that keeps tripping.

    InsteadFind and remove the faulty cord or tool; the GFCI is doing its job.

  • MistakeCoring a slab without a scan because the drawings show nothing there.

    InsteadScan first and get a sign-off; drawings are not always complete.

  • MistakeCutting existing metal water pipe without a bonding jumper.

    InsteadClamp a jumper across the cut first, and stop if you feel a tingle.

Summary and key terms

  • Electricity injures through shock, burns, arc flash and falls caused by shock.
  • Currents of tens of milliamperes can stop the heart; wet skin lets far more current flow.
  • OSHA requires GFCIs or an assured equipment grounding conductor program for temporary 120-volt receptacles.
  • Test GFCIs before use, inspect cords and tools, and remove damaged equipment from service.
  • Scan concrete and check drawings before drilling or coring, especially in post-tensioned slabs.
  • Use a bonding jumper before cutting existing metal water pipe.
  • Keep at least 10 ft from overhead lines up to 50,000 volts, and call 811 before you dig.
Shock
The effect of electric current passing through the body.
Arc flash
An explosive release of energy when current flows through the air between conductors.
GFCI
A ground fault circuit interrupter, which trips when it detects current leaking to ground, at about 5 milliamperes for personnel protection.
Ground pin
The round or U-shaped prong on a plug that connects equipment to the ground path.
Double-insulated tool
A tool with two layers of insulation that does not rely on a ground pin for protection.
Bonding jumper
A cable clamped across a pipe cut to keep the electrical path continuous.
Minimum approach distance
The closest a person, tool or material may come to an energized overhead line.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. Why are wet conditions more dangerous for electric shock?

    Show answer

    Wet skin and wet floors lower resistance, so the same voltage drives much more current through the body.

  2. What should Maya do before plugging into a GFCI-protected receptacle each shift?

    Show answer

    Press the test button to confirm it trips, then reset it.

  3. Name three checks on an extension cord.

    Show answer

    Jacket intact with no exposed wires, plug and connector undamaged, ground pin present, current inspection color.

  4. Why is scanning required before coring a post-tensioned slab?

    Show answer

    To avoid cutting a tendon under high tension, or a live conduit.

  5. What is the first thing to do if a co-worker is being shocked by a tool?

    Show answer

    Do not touch them; shut off the power or unplug the tool, then call for help and give first aid.