PWR-310 · Lesson 8 of 12 · 29 min

Heat transfer calculations

▶ Video coming soon A video version of this lesson is on the way.

On the night of Sunday, September 6, 2026, Okonkwo Demarest's first night back on his usual rotation, Desmond Kirwan sent him on the midnight round with a thermal camera and a clipboard. The district hot water loop had started its autumn duty a week before, and Desmond wanted readings from both plate heat exchangers to compare with their design data: about 3,412,000 Btu/h each, the boiler loop cooling from 203 to 158 °F, the district loop heating from 122 to 176 °F, with 177 ft² of plate area. On the way back Okonkwo stopped at the deaerator, where the camera showed a bright patch on the steam supply line: the removable insulation jacket on a gate valve had been left off after a repack in the summer.

This lesson puts numbers on both observations. It covers the three ways heat moves, conduction, convection and radiation, and how to calculate each; heat flow through flat and cylindrical walls with several layers; the overall heat transfer coefficient and the effect of fouling; and the log mean temperature difference, which sizes and checks every heat exchanger in a plant, from plate exchangers to economizers.

Three modes of heat transfer

  • Conduction is heat passing through a material, or between materials in contact, from molecule to molecule, with no movement of the material itself. It is how heat crosses a boiler tube wall or an insulation layer.
  • Convection is heat carried by a moving fluid. In forced convection a fan or pump drives the fluid; in natural convection the fluid moves because the warmer part is lighter and rises. Convection carries heat from flue gas to tubes and from tubes to water.
  • Radiation is heat carried by electromagnetic waves, mainly infrared, from any surface to any other it can see. It needs no medium and is the dominant mode in a furnace, where flame and hot gas radiate to the waterwalls, and it is a large part of the loss from any hot, bare surface.

In most real equipment all three act together, in series and in parallel. The calculation method in every case is to find the rate of heat flow for a temperature difference, exactly as Ohm's law finds a current for a voltage, and the analogy goes further: each mode has a thermal resistance, and resistances in series add.

Conduction through flat walls

Fourier's law gives the conduction through a flat wall of thickness x and area A, with faces at temperatures T₁ and T₂:

\[Q = \frac{k A (T_1 - T_2)}{x}\]

where k is the thermal conductivity of the material. In US practice it is usually given in Btu·in/h·ft²·°F, with the thickness x in inches, so that Q comes out in Btu/h for an area in ft²; dividing by 12 gives Btu/h·ft·°F, which is needed when thickness is in feet. Metals conduct well; insulations badly, which is their purpose. Conductivity changes with temperature, and insulation manufacturers quote it at a stated mean temperature.

Typical thermal conductivities near room temperature or, for insulations, at moderate mean temperatures. Handbook and manufacturer values vary.
MaterialThermal conductivity, typical
Copper2,700 Btu·in/h·ft²·°F
Carbon steel350 Btu·in/h·ft²·°F
Stainless steel110 Btu·in/h·ft²·°F
Boiler scale (varies widely)7 to 20 Btu·in/h·ft²·°F
Firebrick7 Btu·in/h·ft²·°F
Water4 Btu·in/h·ft²·°F
Calcium silicate pipe insulation0.38 Btu·in/h·ft²·°F
Mineral wool board0.28 Btu·in/h·ft²·°F
Still air0.18 Btu·in/h·ft²·°F

For several layers in series, each layer has a resistance x ÷ kA, and the total resistance is their sum. The heat flow is the overall temperature difference divided by the total resistance, and the temperature at each interface follows from the drop across each layer, the largest drop always across the layer with the largest resistance.

Worked problem

Heat loss through the deaerator insulation

The deaerator storage tank has 2 in of mineral wool (k = 0.28 Btu·in/h·ft²·°F) over its shell, which is at 221 °F. The outside of the insulation, under its aluminum jacket, is at 86 °F. Find the heat loss per square foot and for the tank's 323 ft² of insulated surface. Treat the shell as a flat wall.

Show solution
  1. Per square foot:
  2. \[q = \frac{0.28 \times 135}{2} = 18.9 \text{ Btu/h·ft}^2\]
  3. For the whole tank:
  4. \[Q = 18.9 \times 323 = 6{,}100 \text{ Btu/h}\]

Answer: About 6,100 Btu/h, a small loss for a vessel holding many tons of water at 221 °F. The steel shell's own resistance is negligible: 3/8 in of steel has a resistance per square foot about 6,000 times smaller than the insulation's.

Conduction through cylinders

Pipe insulation is not a flat wall. Heat flowing outward meets a growing area at each larger radius, so the temperature falls quickly near the pipe and slowly near the outside. For a cylindrical layer from inner radius r₁ to outer radius r₂, the heat flow per unit length is:

\[\frac{Q}{L} = \frac{2\pi k (T_1 - T_2)}{\ln(r_2/r_1)}\]

The natural logarithm comes from adding up thin rings, each with its own area. Because of it, each extra layer of insulation saves less than the one before, which is why economic insulation thickness is a balance between the cost of the insulation and the value of the heat saved.

Worked problem

Heat loss from an insulated steam main

An NPS 8 steam main (outside diameter 8.625 in) at 366 °F carries 3 in of calcium silicate insulation (k = 0.38 Btu·in/h·ft²·°F). The insulation's outer surface is at 86 °F. Find the heat loss per foot of pipe.

Show solution
  1. Radii: r₁ = 4.3125 in, r₂ = 7.3125 in. Convert k to Btu/h·ft·°F: 0.38 ÷ 12 = 0.0318.
  2. \[\frac{Q}{L} = \frac{2\pi \times 0.0318 \times (366 - 86)}{\ln(7.3125/4.3125)} = \frac{55.9}{0.528} = 106 \text{ Btu/h·ft}\]

Answer: About 106 Btu/h per foot of pipe. The ratio of radii, not their difference, controls the loss.

Convection

Newton's law of cooling gives the heat carried away from a surface at T_s by a fluid at T_f:

\[Q = h A (T_s - T_f)\]

where h is the convective heat transfer coefficient. Unlike conductivity, h is not a property of a material. It depends on the fluid, its velocity, the shape of the surface and whether the fluid is boiling or condensing. Typical ranges show why boilers and condensers work as they do:

Typical convective coefficients. Actual values depend strongly on velocity, geometry and surface condition.
SituationTypical h
Natural convection in still air1 to 2 Btu/h·ft²·°F
Forced convection, flue gas over tubes5 to 18 Btu/h·ft²·°F
Forced convection, water in tubes180 to 1,800 Btu/h·ft²·°F
Boiling water900 to 9,000 Btu/h·ft²·°F
Condensing steam900 to 18,000 Btu/h·ft²·°F

The gas side of a boiler or economizer has coefficients a hundred times lower than the water side. The gas side therefore controls the heat transfer, which is why economizers and air heaters have fins on the gas side, and why soot on the gas side does so much harm.

Radiation

Every surface radiates energy in proportion to the fourth power of its absolute temperature. The Stefan-Boltzmann law gives the net exchange between a small surface at T_s and large surroundings at T_a:

\[q = \varepsilon \sigma (T_s^4 - T_a^4), \quad \sigma = 0.1714 \times 10^{-8} \text{ Btu/h·ft}^2\text{·°R}^4\]

The emissivity ε, between 0 and 1, says how well a surface radiates compared with a perfect radiator. Oxidized steel and most painted surfaces are around 0.8 to 0.95; bright aluminum jacketing is around 0.1, which is part of why jacketed insulation runs cool to the touch. Because of the fourth power, radiation becomes dominant at high temperatures: doubling a surface's absolute temperature multiplies its radiation sixteenfold.

Worked problem

The cost of a bare pipe

If the same NPS 8 main were bare, its surface would be close to the steam temperature, 366 °F. Estimate the loss per foot by radiation (ε = 0.8) and natural convection (h = 1.41 Btu/h·ft²·°F) to surroundings at 77 °F, and compare with the insulated pipe.

Show solution
  1. Surface area per foot:
  2. \[A = \pi \times 8.625/12 = 2.258 \text{ ft}^2\]
  3. Radiation, with 825.67 °R and 536.67 °R:
  4. \[q_r = 0.8 \times 0.1714 \times 10^{-8} (825.67^4 - 536.67^4) = 524 \text{ Btu/h·ft}^2 \;\Rightarrow\; 1{,}182 \text{ Btu/h·ft}\]
  5. Convection:
  6. \[1.41 \times 289 \times 2.258 = 920 \text{ Btu/h·ft}\]
  7. Total:
  8. \[1{,}182 + 920 = 2{,}100 \text{ Btu/h·ft}\]

Answer: About 2,100 Btu/h per foot, nearly twenty times the insulated pipe's 106 Btu/h. Running all year, each bare foot wastes about 17.5 million Btu of heat, roughly 21,000 ft³ of gas at the boiler's efficiency. A gate valve is equivalent to a few feet of bare pipe, which is why Okonkwo's missing jacket was worth a work order that night.

The overall heat transfer coefficient

In a heat exchanger, heat passes from the hot fluid by convection to the wall, by conduction through it, and by convection into the cold fluid. Each step is a resistance, and for a thin flat wall they combine into an overall heat transfer coefficient U:

\[\frac{1}{U} = \frac{1}{h_{hot}} + \frac{x}{k} + \frac{1}{h_{cold}} + R_f\]

R_f is the fouling resistance: scale on the water side, soot or ash on the gas side, oil films in a lubricating oil cooler. Fouling layers are thin but conduct poorly, and in an exchanger with high film coefficients, like a plate exchanger, even a thin layer can cut U by a quarter or more. The exchanger's duty is then:

\[Q = U A\, \Delta T_m\]

where ΔT_m is the mean temperature difference between the two fluids over the whole surface.

The log mean temperature difference

The temperature difference between two fluids changes along an exchanger as they heat and cool each other. The correct average for the duty equation is not the arithmetic mean but the log mean temperature difference, LMTD, found from the differences at the two ends, ΔT₁ and ΔT₂:

\[\Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1 / \Delta T_2)}\]

In a counterflow exchanger the fluids enter at opposite ends; in parallel flow they enter at the same end. Counterflow gives a larger LMTD for the same four temperatures and can heat the cold fluid to above the hot fluid's outlet temperature, which parallel flow never can. Most plant exchangers are counterflow or close to it; shell-and-tube exchangers with several passes use a correction factor applied to the counterflow LMTD.

Two temperature profiles along an exchanger. Counterflow: the hot fluid falls from left to right while the cold fluid rises from right to left, with a nearly constant gap. Parallel flow: both enter at the left with a large gap that narrows quickly. The end temperature differences delta T1 and delta T2 are marked on each.
Temperature profiles in counterflow and parallel flow. Counterflow keeps a more even temperature difference and allows the cold outlet to exceed the hot outlet.

Worked problem

Checking plate exchanger 1

Plate exchanger 1 is running at its design duty, 3,412,000 Btu/h, with the boiler loop cooling from 203 to 158 °F and the district loop heating from 122 to 176 °F in counterflow. Its plate area is 177 ft². Find the LMTD and the overall coefficient U.

Show solution
  1. End differences: at the hot inlet end, 203 − 176 = 27 °F; at the hot outlet end, 158 − 122 = 36 °F.
  2. \[\Delta T_{lm} = \frac{36 - 27}{\ln(36/27)} = \frac{9}{0.2877} = 31.3 \text{ °F}\]
  3. Overall coefficient:
  4. \[U = \frac{Q}{A\,\Delta T_{lm}} = \frac{3{,}412{,}000}{177 \times 31.3} = 616 \text{ Btu/h·ft}^2\text{·°F}\]

Answer: About 616 Btu/h·ft²·°F, typical of a clean plate exchanger with water on both sides. A fouling resistance of only 0.00057 h·ft²·°F/Btu, a scale layer a fraction of a millimeter thick, would cut U to about 456, three quarters of the clean value, and the exchanger would then run with its outlet temperatures short of design. That is how the scaling in plate exchanger 2 later showed itself.

Worked problem

Why economizers are counterflow

An economizer on a boiler like boiler 2 cools flue gas from 385 °F to 284 °F while heating feedwater from 221 °F to 266 °F, transferring 484,000 Btu/h. With a gas-side controlled U of about 7 Btu/h·ft²·°F (typical for bare tubes), compare the surface needed in counterflow and parallel flow.

Show solution
  1. Counterflow ends: 385 − 266 = 119 °F and 284 − 221 = 63 °F.
  2. \[\Delta T_{lm} = \frac{119 - 63}{\ln(119/63)} = 88.1 \text{ °F}, \quad A = \frac{484{,}000}{7 \times 88.1} = 785 \text{ ft}^2\]
  3. Parallel flow ends: 385 − 221 = 164 °F and 284 − 266 = 18 °F.
  4. \[\Delta T_{lm} = \frac{164 - 18}{\ln(164/18)} = 66.1 \text{ °F}, \quad A = \frac{484{,}000}{7 \times 66.1} = 1{,}046 \text{ ft}^2\]

Answer: Parallel flow would need about a third more surface for the same duty. Fins on the gas side raise the effective U several times and shrink the economizer further. The economizer's gas outlet must also stay safely above the flue gas dew point of lesson 10, which limits how much heat it can recover.

Back in the control room

Okonkwo's readings from exchanger 1 matched the design closely enough to give a U within a few in 100 of 616 Btu/h·ft²·°F; exchanger 2's, at a slightly different flow, came out about the same. He entered both in the log so that the next set of readings would have something to be compared with. For the valve, he wrote a work order to refit the insulation jacket, attached the thermal image, and added his estimate: about 7,000 Btu/h lost for as long as the jacket stayed off. Fenella Thorncroft's crew refitted it on the Tuesday.

Common mistakes

  • MistakeUsing the arithmetic mean temperature difference for an exchanger.

    InsteadUse the log mean temperature difference from the two end differences; the arithmetic mean overstates it.

  • MistakeTreating pipe insulation as a flat wall.

    InsteadUse the cylinder formula with ln(r₂ ÷ r₁); the growing area changes the result.

  • MistakeUsing degrees Celsius or Fahrenheit in the Stefan-Boltzmann law.

    InsteadRadiation uses the fourth power of absolute temperature, kelvin or degrees Rankine.

  • MistakeAdding conductances instead of resistances for layers in series.

    InsteadAdd the resistances, 1/h and x/k, then invert to find U.

  • MistakeThinking more water-side velocity will fix poor gas-side heat transfer.

    InsteadThe lowest coefficient controls U; improve the gas side, for example by keeping it clean or adding fins.

Summary and key terms

  • Heat moves by conduction, convection and radiation; each has a thermal resistance, and resistances in series add.
  • Fourier's law, Q = kAΔT ÷ x, gives conduction through a flat wall; cylinders use 2πkΔT ÷ ln(r₂ ÷ r₁) per unit length.
  • Newton's law, Q = hAΔT, gives convection; h depends on the fluid and flow, and is lowest for gases.
  • Radiation follows εσ(T_s⁴ − T_a⁴) and dominates at high temperature; bare hot surfaces lose heat fast.
  • The overall coefficient U combines the film, wall and fouling resistances; Q = UA ΔT_lm.
  • The LMTD uses the two end temperature differences; counterflow gives a larger LMTD than parallel flow.
Conduction
Heat transfer through a material by molecular contact, without movement of the material.
Convection
Heat transfer by a moving fluid, driven by a fan or pump or by natural buoyancy.
Radiation
Heat transfer by electromagnetic waves between surfaces that can see each other.
Thermal conductivity
The property of a material that sets the rate of conduction through it per unit area, thickness and temperature difference.
Emissivity
The ratio of the radiation from a surface to that from a perfect radiator at the same temperature.
Overall heat transfer coefficient
The heat transfer rate per unit area per degree of mean temperature difference between two fluids.
Fouling resistance
The added thermal resistance of scale, deposits or films on a heat transfer surface.
Log mean temperature difference
The effective mean temperature difference between two fluids in an exchanger, calculated from the end differences.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. A firebrick wall 9 in thick (k = 7 Btu·in/h·ft²·°F) has faces at 1,650 °F and 300 °F. Find the heat loss per square foot.

    Show answer

    q = 7 × 1,350 ÷ 9 = 1,050 Btu/h·ft².

  2. A surface of 20 ft² at 140 °F loses heat to air at 68 °F with h = 1.8 Btu/h·ft²·°F. Find the loss.

    Show answer

    Q = 1.8 × 20 × 72 = 2,590 Btu/h.

  3. An exchanger has end temperature differences of 72 °F and 18 °F. Find the LMTD.

    Show answer

    54 ÷ ln 4 = 39.0 °F.

  4. An exchanger with U = 210 Btu/h·ft²·°F and an LMTD of 45 °F must transfer 2,000,000 Btu/h. What area is needed?

    Show answer

    A = 2,000,000 ÷ (210 × 45) = 212 ft².