GAS-350 · Lesson 4 of 12 · 23 min

Review: the gas code

▶ Video coming soon A video version of this lesson is on the way.

Rosa kept the second half of the October 27 evening for the code. She brought her own copy of the IFGC, twenty years of editions on a shelf at home reduced to the current one, tabbed in four colors. "On the exam," she said, "the code questions split two ways. Half of them you should know cold, because you use them every week: test pressures, clearances to a garage floor, what a sediment trap is for. The other half you're not meant to remember. You're meant to know where to look and what the words mean when you get there. So tonight is partly facts and partly how to read."

This lesson reviews GAS-120, with the codes and regulations that the later courses added. It covers who writes and adopts the codes, how a code is organized, how to read its language, the general requirements that apply to every installation, the rules on unsafe conditions, and a method for finding an answer in the book quickly. It does not reproduce the code: every rule here is described in the program's own words, and on the exam the book itself is the authority.

Who writes the codes and who adopts them

Ohio's commercial gas code is the International Fuel Gas Code, written by the International Code Council and adopted by the Ohio Board of Building Standards as part of the Ohio Mechanical Code. The 2024 Ohio Mechanical Code, with the 2021 IFGC, applies to commercial buildings from March 1, 2024. One-, two- and three-family houses come under the Residential Code of Ohio, which has its own fuel gas chapter based on the International Residential Code. NFPA 54, the National Fuel Gas Code, written by the National Fire Protection Association, covers the same ground and is the basis of much of the IFGC; it is used as a reference and is adopted directly in some other states. NFPA 58 covers propane storage and handling and is adopted through the Ohio Fire Code. Columbus enforces the codes through the Department of Building and Zoning Services, and Columbia Gas of Ohio controls turn-on at the meter.

Two ideas from GAS-120 matter most for the exam. First, a code has force only where a law adopts it, and the law may change it: an exam question about what "the code" requires means the edition and amendments in force where you are licensed. Second, the code sets a minimum. An appliance maker's installation instructions often ask for more, and where they do, the instructions must be followed too; the code itself requires installation according to the certified or listed instructions.

How a code is organized

The IFGC opens with its scope and administration and then a long chapter of definitions. Chapter 3 holds the general regulations, including combustion air, appliance location and clearances; chapter 4 is gas piping installations, with the sizing tables and the testing rules; chapter 5 is chimneys and vents, with the vent sizing tables; chapter 6 covers specific appliances; chapter 7 covers gaseous hydrogen systems; and chapter 8 lists the referenced standards. The Residential Code of Ohio's fuel gas chapter follows the same order. Knowing that structure is the fastest way to find anything.

A flowchart of finding an answer in the code. Step one: identify the subject in the question, such as piping, venting or air supply. Step two: go to that part of the code by its tab, or use the index. Step three: read the requirement and any exceptions that follow it. Step four: check the definitions of the key words in the requirement. Step five: check whether the appliance instructions or the local amendments change it. Step six: answer. A side note says: under one minute with practice.
A six-step routine for code questions. Most wrong code answers skip step three or four.

Reading the language

Code language is precise, and exam questions test the precision:

  • Shall is mandatory. Should is advice, usually found in notes or informative annexes. May gives permission. A question that asks what the code requires is asking about the shall statements.
  • Defined words mean what the definition says, not what they mean in conversation. Appliance, accessible, readily accessible, concealed, vent connector, chimney, approved, certified or listed: each has a definition, and many exam questions turn on one.
  • Exceptions follow the rule they change. A clearance rule followed by "except where the appliance is certified for..." means the general rule is not the final answer.
  • Units and limits. "Not less than" is a minimum, "not more than" a maximum, and "within" a distance or time inside which something must happen.

General requirements every installation meets

Most of the general requirements reviewed in GAS-120 apply to every job, which is why they are favorite exam topics. In summary:

  • Certified or listed appliances, installed according to the maker's instructions, with the rating plate visible. An appliance that is not certified needs a field evaluation and the approval of the authority having jurisdiction before it may be used, as Luis found when the Marigold Kitchen's owner bought an imported wok range.
  • Location. Appliances are kept out of places the code prohibits for them, such as sleeping rooms and bathrooms for many types, and appliances in garages have their ignition sources raised at least 18 in. above the floor unless they are certified as resistant to flammable vapor ignition.
  • Access and clearance. Appliances and their controls must be accessible for service, with clearances to combustibles as the certification and the code set out; reduced clearances need the shields or methods the code allows.
  • Piping materials and joints: only approved materials, with joints of the kinds allowed; no concealed unions or other fittings the code prohibits in concealed spaces; supports at the spacing the code requires; a shut-off valve and a sediment trap, called a drip in some books, ahead of each appliance where required.
  • Corrugated stainless steel tubing installed by trained installers to the maker's instructions, with bonding with at least a 6 AWG copper conductor, as the code requires.
  • Testing and purging. New and altered piping is pressure tested before use, then purged safely, to outdoors where the code requires, as GAS-120 and GAS-330 taught. The IFGC requires a test at not less than one and a half times the working pressure and never less than 3 psig, held for the time the code sets.
  • Putting into service. Gas is turned on only after the test, the purge and the leak check at each appliance, and each appliance is started and checked to the maker's instructions, including combustion and venting checks.

Worked problem

Test pressure check

New commercial piping will operate at 2 psig. Another section will operate at 7 in. w.c. What minimum test pressure does the IFGC rule require for each?

Show solution
  1. 2 psig section: one and a half times the working pressure:
  2. \[1.5 \times 2 = 3 \text{ psig}\]
  3. The minimum of 3 psig also applies, so 3 psig.
  4. 7 in. w.c. section: working pressure in psi:
  5. \[\frac{7}{27.7} \approx 0.25 \text{ psi}; \quad 1.5 \times 0.25 \approx 0.38 \text{ psig}\]
  6. The 3 psig minimum governs, so 3 psig.

Answer: Both sections are tested at no less than 3 psig, held for the time the code sets. A common wrong answer applies one and a half times the low working pressure and forgets the minimum.

Unsafe conditions and the duties they bring

In Ohio, the codes make an installation that does not comply a violation, and the authority having jurisdiction can order it corrected or disconnected. The utility, Columbia Gas of Ohio, may refuse or disconnect service to a hazardous installation under its tariff and the state's utility rules. Bayline's procedure, set out in GAS-340, puts the duty on the technician who finds a hazard: shut off the gas, red-tag the appliance, give the customer a written notice that explains the hazard, and call Columbia Gas when its equipment is involved, the leak cannot be isolated or the customer refuses. On the exam, answer from the code and the authority's powers; on the job, follow the procedure as well.

On every unsafe condition, the record matters as much as the shut-off: what was found, the readings, what was done, what the customer was told and when, and who was notified. An exam question that asks what a technician must do about a hazard has an answer built from the duties above, and the distractors usually leave one step out.

Code questions that catch people

Rosa's list of the code questions her apprentices get wrong most often:

  • The test pressure question that offers one and a half times a low working pressure and forgets the minimum.
  • The clearance question that asks about a certified appliance with a reduced clearance on its label: the label governs, within the code's rules.
  • The concealed-fitting question: unions, bushings and running threads are not allowed where they will be concealed.
  • The definition question: accessible is not the same as readily accessible.
  • The authority question: who approves an uncertified appliance, who issues a certificate, who turns on the meter.
  • The two-answer question: both the code and the maker's instructions apply, and the stricter of the two is the answer.

Words the exam turns on

Some definitions come up so often that they are worth learning by heart. The wording here is the program's paraphrase; on the exam, check the definition in the book you are allowed.

Definitions that decide many code questions, in the program's own words.
TermWhat it means in the codeWhy it matters
AccessibleCan be reached for service, though panels or doors may have to be removedMost appliances and valves must be at least accessible
Readily accessibleCan be reached quickly without removing panels, climbing over obstacles or using portable laddersSome shut-off valves must be readily accessible, which is stricter
ApplianceA device that uses gas as a fuel or raw materialThe word decides which rules apply to a piece of equipment
Vent connectorThe pipe joining an appliance to a vent or chimneyConnectors have their own rules for slope, length and material
ConcealedHidden by the building, not reachable without damaging itMany fittings are prohibited where concealed
ListedIncluded in a list published by a recognized testing organization as meeting a standardOnly certified or listed appliances may be installed without a field approval or evaluation
Authority having jurisdictionThe body that enforces the code: in Columbus, Building and Zoning ServicesApprovals, inspections and orders come from it

The difference between accessible and readily accessible catches more candidates than any other pair. A valve behind a removable access panel is accessible. A valve that needs a stepladder, or is behind a stack of stored boxes, is not readily accessible. Where the code asks for readily accessible, only the stricter meaning satisfies it.

A lookup, step by step

Worked problem

Finding an answer you do not remember

A practice question asks for the IFGC requirement on the minimum free area of a combustion air opening from outdoors through a horizontal duct. Luis does not remember it. Show the lookup routine he used.

Show solution
  1. Subject: combustion air, which is in chapter 3, general regulations.
  2. Go to the chapter 3 tab and the combustion air section, or look up 'combustion air' in the index.
  3. Read the requirement for outdoor air through horizontal ducts: 1 square inch per 2,000 Btu/h of total input.
  4. Read on for exceptions and for the rules on louvers and duct size.
  5. Check the Ohio amendments for any change.
  6. Answer, and note the section number in his error log for next time.

Answer: The routine took Luis about 45 seconds by the end of his drills. The note in the error log meant that the second time a similar question came up, he went straight to the page.

Who does what

Many code questions are really questions about authority: who may do a thing, approve it or turn it on. A simple map helps:

  • OCILB licenses contractors; the Ohio Board of Building Standards adopts the state codes; Building and Zoning Services issues permits and inspects in Columbus; the fire code official covers propane storage under the Ohio Fire Code.
  • Columbia Gas of Ohio owns the meter and service regulator, sets the service pressure, turns on gas to new services after the city's inspection, and may refuse or disconnect service to a hazardous installation.
  • The certificate or license holder installs, tests and puts into service, within scope, and is responsible for what they sign.
  • The appliance maker writes the installation instructions, which the code makes part of the requirement.

Common mistakes

  • MistakeAnswering from an old edition or another jurisdiction's rules.

    InsteadAnswer from the edition and amendments in force where you are licensed.

  • MistakeReading a should as a shall.

    InsteadOnly shall statements are requirements.

  • MistakeMissing the exception after a rule.

    InsteadRead on past every rule to see whether an exception follows.

  • MistakeUsing the everyday meaning of a defined word.

    InsteadCheck the definition: words like accessible and appliance have code meanings.

  • MistakeForgetting the minimum test pressure.

    InsteadCheck both the multiple of working pressure and the minimum.

  • MistakeLeaving a step out of the unsafe-condition duties.

    InsteadShut off where required, notify, tag, record, and follow up as the rules set out.

Summary and key terms

  • Ohio uses the 2024 Ohio Mechanical Code with the 2021 IFGC for commercial work from March 1, 2024, and the Residential Code of Ohio for houses; NFPA 54 is the parallel national code and NFPA 58 covers propane through the Ohio Fire Code.
  • The code sets a minimum, and the listed instructions must also be followed.
  • Shall is mandatory, should is advice, may is permission; defined words have code meanings; exceptions follow rules.
  • General requirements cover listing, location (garage ignition sources at least 18 in. up), access and clearances, materials and joints, CSST bonding with at least 6 AWG copper, testing at 1.5 times working pressure and never less than 3 psig, purging and putting into service.
  • Hazards are handled under the codes, the utility's rules and the company procedure.
  • Find answers by subject, tab, requirement, exceptions, definitions and amendments.
Code adoption
The legal act by which a government makes a code edition enforceable, often with local amendments.
Shall
The code word for a mandatory requirement.
Exception
A statement following a rule that changes how the rule applies in stated cases.
Field approval
Approval of an uncertified appliance or equipment at its site by the authority or its delegate, after inspection against a standard.
Immediate hazard
An unsafe condition that presents an immediate danger to people or property and requires the gas to be shut off.
Sediment trap
A capped tee and nipple ahead of an appliance that collects debris before it reaches the controls; also called a drip.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What does the word should mean in a code?

    Show answer

    It is advice, not a requirement.

  2. Why must you read past a rule before answering?

    Show answer

    An exception may follow that changes the rule.

  3. What is the minimum test pressure for new piping under the IFGC?

    Show answer

    1.5 times working pressure, and never less than 3 psig.

  4. Which applies when the code and the maker's instructions differ?

    Show answer

    Both apply, so the stricter requirement is followed.

  5. How high must ignition sources be above a garage floor for an ordinary appliance?

    Show answer

    At least 18 in..

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz