ELEC-130 · Lesson 5 of 12 · 33 min

Branch circuits and receptacles

Branch circuits are the final circuits from the panel to the lights, receptacles and appliances of the house. They are where most of an electrician's residential work happens, and where the code is most detailed, because they are what occupants touch every day. This lesson covers the kinds of branch circuit and their ratings, cable and wire sizes, the number and placement of receptacles, dedicated circuits for appliances, lighting outlets and switching, and receptacle types.

Kinds of branch circuit

Residential branch circuits fall into a few groups:

  • General-purpose 120 V circuits, rated 15 A (14 AWG copper) or 20 A (12 AWG copper), supplying lighting and general receptacles.
  • Small-appliance and kitchen counter circuits, which carry the heavy, intermittent loads of kettles, toasters and microwaves.
  • Dedicated (individual) circuits supplying one appliance: refrigerator, dishwasher, washing machine, microwave, furnace, sump pump and so on.
  • 240 V circuits for large appliances: range (commonly 40 A), dryer (30 A), water heater, baseboard heaters, heat pumps and air conditioners, EV chargers.
  • Multiwire branch circuits: two ungrounded conductors from opposite buses sharing one neutral, for example to supply a split kitchen receptacle. The neutral carries only the difference of the two currents, saving a conductor, but the two hots must be on a two-pole breaker or handle-tied breakers so both are disconnected together.

The circuit rating is set by the overcurrent device, and the conductors must be protected by it. The small-conductor rule from ELEC-120 applies: 14 AWG copper on no more than 15 A, 12 AWG on 20 A and 10 AWG on 30 A, regardless of the higher ampacity of 90 °C insulation.

Typical residential branch circuits. Always check the appliance instructions, the ampacity rules and voltage drop.
LoadTypical circuitCopper conductor (non-metallic cable)
Lighting, general receptacles15 A, 120 V14 AWG
Kitchen counter, bathroom, laundry20 A, 120 V (or split 15 A)12 AWG (14 AWG for 15 A)
Dryer30 A, 240 V10 AWG
Range40 A, 240 V8 AWG
EV charger (7.7 kW at 32 A continuous)40 A, 240 V8 AWG
Baseboard heaters 3 kW15 A or 20 A, 240 V14 or 12 AWG

Worked problem

Sizing an EV charger circuit

An EV charger draws 32 A continuously at 240 V. What breaker and copper conductor are needed?

Show solution
  1. Continuous load: the overcurrent device must be at least 125% of the load: \(1.25 \times 32 = 40\) A.
  2. A 40 A breaker with conductors rated at least 40 A at the termination temperature: 8 AWG copper (non-metallic cable is limited to the 60 °C column, where 8 AWG is rated 40 A).

Answer: A 40 A two-pole breaker and 8 AWG copper. The charger counts at its full rating in the load calculation (Lesson 1), and in both countries it must be on its own circuit.

Cable and wiring practice

Most US houses are wired with non-metallic sheathed cable, type NM-B, which has insulated copper conductors and a bare equipment grounding conductor in a PVC jacket; type MC or AC cable or raceway is used where required for protection or by local amendments (some cities, such as Chicago, require conduit). NM cable must be secured within 12 in of each box and at intervals of not more than 4½ ft (334.30), and protected by steel plates where it passes through framing within 1¼ in of the edge (300.4).

Wiring is planned so that circuits are logical and well labeled: lights and receptacles of a room are often on different circuits, so a tripped breaker does not leave a room dark; high-load receptacles are spread across circuits; and 120 V circuits are balanced between the two buses (Lesson 3). The panel directory must identify every circuit clearly.

Receptacle spacing

Receptacles must be placed so that a lamp or appliance with a normal cord can reach one from anywhere along a wall, which discourages extension cords.

NEC 210.52(A) requires receptacles in habitable rooms of a dwelling so that no point along the floor line of any wall space is more than 6 ft from a receptacle, measured along the wall; in other words, receptacles at most 12 ft apart and within 6 ft of each doorway. Any wall space 2 ft or more wide counts, including space occupied by fixed panels of sliding glass doors. Hallways 10 ft or longer need at least one receptacle.

Floor plan of a bedroom with a door and a window. Receptacles are placed around the walls so that no point along the floor line is more than 6 feet from a receptacle, shown by colored bands extending 6 feet either way from each receptacle along the wall line, overlapping around the room, with the doorway breaking the wall line.
Receptacle spacing along the walls of a room.

Worked problem

Receptacles for a room

A living room wall runs 26 ft from a doorway to the corner without openings. What is the minimum number of receptacles along it?

Show solution
  1. Each receptacle covers 6 ft on each side, a 12 ft stretch.
  2. Positions at 6 ft and 18 ft cover 0 to 24 ft; the last 2 ft need a third receptacle, or shift them (6 ft and 20 ft leave a gap from 12 to 14 ft).

Answer: Three receptacles: n = ⌈L / 12 ft⌉ for a wall that starts at an opening. Corners continue onto the next wall, so planning the whole room together often saves a receptacle.

Kitchens

Kitchens have the most demanding requirements, because counters host many high-current appliances.

In the US, at least two 20 A small-appliance branch circuits must serve the kitchen, pantry, breakfast and dining room receptacles (210.11(C)(1)), and they may not serve other outlets. Countertop receptacles must be placed so that no point along the wall line is more than 24 in from a receptacle (210.52(C)), with every countertop space 12 in or wider served; island and peninsula requirements were revised in the 2023 NEC. Refrigerators may be on a small-appliance circuit or an individual 15 A or larger circuit; dishwashers and disposers are commonly on their own circuits, and all kitchen receptacles need GFCI protection (Lesson 7).

Worked problem

Counter receptacles

A straight countertop is 10 ft long, from the end of the counter to a range. How many receptacles are needed, at minimum?

Show solution
  1. Each receptacle covers 24 in on each side, 4 ft in all.
  2. \(10/4 = 2.5\), so at least 3, placed at about 2 ft, 6 ft and 10 ft (within 24 in of the range end).

Answer: Three receptacles on the 20 A small-appliance circuits, GFCI protected.

Bathrooms, laundry, outdoors and garages

  • Bathrooms: at least one 20 A receptacle within 3 ft of each basin (210.52(D)), on a 20 A bathroom circuit that serves only bathroom receptacles (or one bathroom's entire load), GFCI protected.
  • Laundry: a 20 A laundry circuit (210.11(C)(2)) with a receptacle for the washer, plus the dryer circuit.
  • Outdoors: at least one receptacle at the front and one at the back of a one-family dwelling, accessible from grade and not more than 6½ ft above it (210.52(E)), GFCI protected, weather-resistant, with an in-use cover.
  • Garages: at least one receptacle for each vehicle bay in the 2023 NEC, on a circuit serving only the garage receptacles, GFCI protected.

Number of outlets per circuit

The NEC does not limit the number of outlets on a dwelling general-purpose circuit. Instead, enough circuits must be provided for the calculated general lighting load: at 3 VA/ft², a 2400 ft² house has 7200 VA, which needs at least 7200/(120 × 15) = 4 circuits of 15 A, or 3 of 20 A (210.11(A)). Many designers limit circuits to 8 to 10 outlets as good practice.

Worked problem

Planning general-purpose circuits

A 3000 ft² house is wired with 15 A general-purpose circuits. What is the minimum number required for the general lighting load?

Show solution
  1. General lighting load: \(3 \times 3000 = 9000\) VA.
  2. Each 15 A circuit carries 1800 VA: \(9000/1800 = 5\) circuits.

Answer: At least 5 circuits of 15 A, in addition to the small-appliance, laundry, bathroom and dedicated circuits; in practice more, for convenience and balance.

Lighting outlets and switching

Every habitable room, bathroom, hallway, stairway, attached garage and outdoor entrance needs a lighting outlet controlled by a wall switch near the entrance (in living rooms, a switched receptacle may be accepted in place of a ceiling outlet). Stairways with six or more risers, and rooms with more than one entrance, commonly need switches at each end or entrance:

  • A single-pole switch controls a light from one place.
  • Two three-way switches control a light from two places: the supply goes to the common terminal of the first switch, two travelers connect the switches, and the common of the second switch feeds the light.
  • Four-way switches inserted between the two three-ways add each further control location.

Smart switches, occupancy sensors and dimmers usually need a neutral at the switch box. Bringing a neutral to every switch location is therefore good practice, and the NEC has required it at most switch locations since 2011 (404.2(C)). Dimmers must be compatible with the lamps, especially LED lamps, and rated for the load.

Wiring diagram of a light controlled by two three-way switches. The supply hot conductor connects to the common terminal of the first switch. Two traveler conductors connect the traveler terminals of the two switches. The common terminal of the second switch connects to the light. The neutral runs from the supply directly to the light. Bonding conductors connect to each box and device.
Three-way switching: the light is on when both switches connect the same traveler.

Worked problem

Voltage drop on a long branch circuit

A 15 A, 120 V circuit of 14 AWG copper (8.28 Ω/km, or 2.53 Ω/1000 ft) runs 30 m (98 ft) to a garage receptacle that will supply a 12 A tool. What is the voltage drop? Is 12 AWG (5.21 Ω/km) better?

Show solution
  1. 14 AWG: the circuit loop is 60 m, \(R = 0.060 \times 8.28 = 0.497\) Ω; drop \(= 12 \times 0.497 = 5.96\) V, or 5.0%.
  2. 12 AWG: \(R = 0.060 \times 5.21 = 0.313\) Ω; drop \(= 3.75\) V, or 3.1%.

Answer: About 6 V (5%) with 14 AWG, above the usual 3% branch-circuit target, and 3.75 V (3.1%) with 12 AWG on a 15 A or 20 A breaker. Long runs to garages and outbuildings are routinely upsized for voltage drop.

Receptacle types

Receptacle configurations are standardized by NEMA (and in Canada by CSA, which uses the same configurations) so that a plug fits only a matching voltage and current rating:

  • 5-15R: 15 A, 125 V, the ordinary duplex receptacle. 5-20R: 20 A, 125 V, with a T-shaped slot that accepts both 15 A and 20 A plugs.
  • 14-30R: 30 A, 125/250 V, four-wire, for dryers. 14-50R: 50 A, 125/250 V, four-wire, for ranges and plug-in EV chargers.
  • 6-20R, 6-30R and 6-50R: 250 V receptacles without neutral.

Older three-wire 10-30 and 10-50 receptacles, which use the neutral as the equipment ground, are no longer permitted for new installations; new dryer and range circuits use four-wire receptacles with a separate equipment grounding conductor.

Receptacles in dwellings must be listed tamper-resistant (406.12), with internal shutters, and receptacles in damp and wet locations must be listed weather-resistant (406.9), with in-use covers where exposed to rain.

Lesson 6 continues with the circuits for ranges, dryers, water heaters, pumps and other major appliances, and Lesson 4 covers how the cable and boxes for these circuits are installed.

Common mistakes

  • MistakePutting 14 AWG on a 20 A breaker because 90 °C insulation is rated higher.

    InsteadThe small-conductor rule limits 14 AWG copper to 15 A and 12 AWG to 20 A.

  • MistakeWiring a multiwire circuit with two single-pole breakers.

    InsteadUse a two-pole breaker or identified handle tie so both hots disconnect together, and land the hots on opposite buses.

  • MistakeMeasuring receptacle spacing as a straight line across the room.

    InsteadMeasure along the floor line of the wall, with doorways and openings breaking the wall.

  • MistakeSizing a continuous load like an EV charger at its running current.

    InsteadSize the breaker at 125% of continuous load and the conductors to match.

  • MistakeInstalling three-wire dryer or range receptacles in new work.

    InsteadNew dryer and range circuits use four-wire receptacles with a separate equipment grounding conductor.

  • MistakeOmitting the neutral at switch boxes.

    InsteadBring a neutral to switch locations for smart switches and sensors (required by 404.2(C) in most cases).

Summary and key terms

  • Branch circuits: general-purpose 15/20 A, small-appliance and counter, dedicated appliance, 240 V appliance, and multiwire circuits.
  • Small-conductor rule: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A; continuous loads at 125%.
  • NM-B cable: secure within 12 in of boxes and every 4½ ft; protect within 1¼ in of framing edges.
  • Receptacle spacing: no point along a wall more than 6 ft from a receptacle (12 ft apart).
  • Kitchens: two or more 20 A small-appliance circuits; counter receptacles within 24 in of any point.
  • Bathroom receptacle within 3 ft of each basin on a 20 A circuit; front and back outdoor receptacles; general circuits from 3 VA/ft².
  • Lighting outlets with wall switches in every room; three-way and four-way switches for multiple locations; neutrals at switch boxes.
  • Receptacle configurations: 5-15, 5-20, 14-30, 14-50; tamper-resistant in dwellings; weather-resistant with in-use covers outdoors.
Branch circuit
The circuit conductors between the final overcurrent device and the outlets.
General-purpose circuit
A branch circuit supplying lighting and general receptacles.
Dedicated circuit
A branch circuit supplying a single appliance or outlet.
Multiwire branch circuit
Two or more ungrounded conductors sharing a neutral.
Small-appliance circuit
A 20 A circuit for kitchen and dining receptacles.
Split receptacle
A duplex receptacle whose two halves are fed from different circuits.
Outlet
A point on the wiring where current is taken to supply equipment.
Three-way switch
A switch with a common and two traveler terminals, used in pairs.
Traveler
A conductor between three-way or four-way switches.
Tamper-resistant receptacle
A receptacle with shutters that block single-slot insertion.
In-use cover
A weatherproof cover that protects a receptacle while a plug is inserted.
Voltage drop
The reduction in voltage along conductors due to their resistance.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What breaker and copper conductor size suit a 24 A continuous load at 240 V?

    Show answer

    1.25 × 24 = 30 A breaker; 10 AWG copper.

  2. A multiwire circuit carries 12 A on one hot and 9 A on the other. What is the neutral current?

    Show answer

    3 A, if the hots are on opposite buses.

  3. What happens to the neutral of a multiwire circuit if both hots are mistakenly on the same bus?

    Show answer

    The currents add instead of canceling: 21 A on a conductor rated for 15 or 20 A, overheating the neutral without tripping either breaker.

  4. A wall runs 14 ft between two doorways. How many receptacles at minimum?

    Show answer

    One covers 12 ft; 14 ft needs 2.

  5. How many 20 A general-purpose circuits does a 2000 ft² house need, at minimum?

    Show answer

    6000 VA / 2400 VA = 2.5, so 3.

  6. What is the voltage drop on a 25 m run of 12 AWG copper (5.21 Ω/km) carrying 16 A at 120 V?

    Show answer

    R = 0.050 × 5.21 = 0.26 Ω; 16 × 0.26 = 4.2 V, 3.5%.

  7. Describe how two three-way switches control one light.

    Show answer

    The supply goes to one switch's common, two travelers join the switches, and the other common feeds the light; the light is on when both switches select the same traveler.

  8. Which receptacle configuration suits a new electric dryer circuit?

    Show answer

    NEMA 14-30R (30 A, 125/250 V, four-wire with separate ground).

  9. Why must new range and dryer circuits be four-wire?

    Show answer

    So that the equipment frame is bonded through a separate grounding conductor rather than the neutral, which carries current and could energize the frame if it opened.

  10. Why are lights and receptacles of a room often put on different circuits?

    Show answer

    So a tripped receptacle circuit does not leave the room dark, and to spread load.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz