ELEC-130 · Lesson 6 of 12 · 31 min
Major appliance circuits
The largest individual loads in most houses are fixed and cord-connected appliances: ranges, cooktops and ovens, clothes dryers, water heaters, dishwashers, microwaves, and pumps. Each has its own requirements for circuit rating, conductor size, connection method and disconnecting means, and many are continuous loads or have demand factors that change how they are counted. Lesson 5 covered the receptacle circuits of kitchens, bathrooms and laundries; this lesson covers the appliances themselves, reading their nameplates, sizing their circuits, connecting them correctly, and the special case of appliances supplied at 208 V in apartment buildings.
Reading the nameplate
Every appliance has a nameplate or rating label giving its voltage, power or current, and often the minimum circuit ampacity and maximum overcurrent protection. The installation instructions, which are part of the appliance's certification or listing, may add requirements such as a specific breaker size or receptacle type. Codes require installation according to the listing, so the instructions are as binding as the code itself.
Worked problem
From nameplate to current
A cooktop is rated 9.6 kW at 240 V and 7.2 kW at 208 V. What current does it draw at each voltage?
Show solution
- At 240 V: \(9{,}600/240 = 40\) A.
- At 208 V: \(7{,}200/208 = 34.6\) A.
Answer: 40 A and 34.6 A. Resistive heating elements draw less power at lower voltage (power varies with the square of voltage: \((208/240)^2 = 0.75\)), so the cooktop heats about 25% more slowly at 208 V.
Ranges, cooktops and ovens
Cooking appliances are large but rarely run at full power for long, so the codes apply demand factors in the load calculation (Lesson 1) and allow circuits smaller than the full nameplate rating would suggest.
In the US, the NEC (Table 220.55) permits a demand of 8 kW for a single household range rated not over 12 kW, and the range branch circuit must be at least 40 A for ranges of 8¾ kW or more (210.19(A)(3)). A counter-mounted cooktop and up to two wall ovens in the same room may be added together and treated as one range. Ranges connect through a 14-50R receptacle (four-wire) or are hard-wired.
Induction cooktops are increasingly common. Their electronics draw nearly sinusoidal current at a high power factor, and some can share power between zones, limiting their maximum draw. They may specify a 40 A or 50 A circuit; the instructions decide.
Worked problem
A cooktop and wall oven on one circuit
A kitchen has a 7.2 kW induction cooktop and a 4.8 kW wall oven, both 240 V. What is their combined rating, and what circuit is reasonable if the instructions permit a shared circuit?
Show solution
- Combined: \(7.2 + 4.8 = 12.0\) kW, treated as one range of 12 kW.
- Demand in the load calculation: 6 kW (Canada) or 8 kW (US) for a 12 kW range.
- A 40 A circuit can supply both if both appliances' instructions allow it and each tap is sized for its appliance.
Answer: A single 40 A circuit, often with a junction box splitting to each appliance, or separate circuits (for example 40 A and 30 A) if either appliance's instructions require it. Separate circuits cost more but are simpler to service.
Clothes dryers
Electric dryers are 240 V appliances of about 5 kW, with motors and controls at 120 V, so they need both legs and a neutral.
- Circuit: 30 A, 240 V with 10 AWG copper.
- Connection: a four-wire receptacle (NEMA 14-30R) with two ungrounded conductors, a neutral and a separate bonding (grounding) conductor. Older installations used three-wire receptacles (10-30R) in which the frame was connected to the neutral; new installations use four wires so that a broken neutral cannot leave the frame energized.
- Venting: dryers produce lint and heat; their ducts are separate from electrical concerns but affect where the receptacle is placed.
In the NEC load calculation, a dryer is counted at the larger of 5,000 W or its nameplate rating (220.54), with demand factors for multiple dryers.
Heat-pump dryers use far less energy and some run on 120 V, 15 A or 20 A circuits; combination washer-dryers vary. Again, the instructions decide.
Water heaters
Electric storage water heaters typically have two 3.8 kW or 4.5 kW elements, wired so that only one heats at a time, at 240 V. They can run for hours after a large hot-water draw, so they are treated as continuous loads.
Worked problem
Sizing a water heater circuit
A 180 L water heater has two 4,500 W elements that cannot operate together. Size the circuit, treating the heater as a continuous load.
Show solution
- Maximum load: 4,500 W at 240 V: \(4{,}500/240 = 18.75\) A.
- Continuous: \(1.25 \times 18.75 = 23.4\) A.
- Next standard breaker: 25 A; with 60 °C cable ampacity, 10 AWG copper on a 30 A breaker is the common choice, or 12 AWG on 25 A where the instructions and ampacity tables allow.
Answer: Usually a 30 A, 240 V circuit with 10 AWG copper, which also allows future higher-power elements. The water heater needs a disconnecting means within sight, or a breaker that can be locked off (ELEC-120).
Heat-pump water heaters use roughly a third of the energy of resistance heaters, often with a backup element; some models run on 120 V. Tankless electric water heaters, by contrast, draw very large currents (often 100 A to 150 A at 240 V) for short periods, and can be impractical on a typical 100 A or 200 A service without load management (Lesson 10).
The NEC (422.13) treats fixed storage water heaters of 450 L (120 gal) or less as continuous loads, requiring branch-circuit ratings of at least 125% of the nameplate.
Dishwashers, disposals and other kitchen appliances
- Dishwashers: usually a 15 A or 20 A, 120 V individual circuit, either hard-wired through a junction box at the appliance or cord-and-plug connected to a receptacle in an adjacent cabinet. Their heating elements and pumps make them significant loads.
- Food waste disposers: a 15 A or 20 A, 120 V circuit, often switched from a wall switch near the sink, and sometimes sharing a split circuit with the dishwasher.
- Built-in microwaves and microwave-range hoods: typically a 15 A or 20 A individual circuit, since a microwave alone can draw 12 A to 15 A.
- Refrigerators and freezers: commonly an individual 15 A circuit, so that a fault elsewhere does not spoil food; ground-fault and arc-fault requirements for these receptacles vary by code and edition.
The NEC (210.8(D)) requires GFCI protection for dishwasher outlets in dwellings, and recent editions extend GFCI protection to all 125 V to 250 V kitchen receptacles serving countertops and to many appliance outlets; AFCI protection applies to kitchen circuits as well.
Laundry, pumps and other appliances
- Washing machines: a 20 A, 120 V circuit (often required to serve only laundry outlets), with GFCI protection required in laundry areas in many editions.
The NEC (210.11(C)(2)) requires at least one 20 A branch circuit for laundry receptacle outlets, serving no other outlets.
- Sump pumps: an individual circuit, so that other loads tripping a breaker do not stop the pump during a storm. GFCI protection may be required in basements and unfinished areas, which raises the risk of a nuisance trip disabling the pump; a high-water alarm on a separate circuit or battery is a good addition.
- Well pumps: 240 V circuits sized from the pump's motor data, with a pressure switch and often a controller; voltage drop over long runs to the well can be significant (Lesson 5).
- Hot tubs and spas: large 240 V loads with ground-fault protection, an emergency shutoff within sight but at a minimum distance from the tub, and bonding requirements (ELEC-120).
Worked problem
Voltage drop to a well pump
A well pump draws 9.8 A at 240 V and is 85 m from the panel. With 12 AWG copper (about 5.2 Ω/km per conductor), what is the voltage drop, and is it acceptable at 3%?
Show solution
- Loop resistance: \(2 \times 0.085 \times 5.2 = 0.884\) Ω.
- Drop: \(9.8 \times 0.884 = 8.7\) V, or 3.6% of 240 V.
- With 10 AWG (about 3.3 Ω/km): \(9.8 \times 2 \times 0.085 \times 3.3 = 5.5\) V, 2.3%.
Answer: 12 AWG gives 3.6%, above the 3% guideline, and the motor's starting current would cause an even larger dip; 10 AWG gives 2.3%. Long runs to pumps, garages and outbuildings often need conductors larger than ampacity alone requires.
Disconnects and cord connections
Every fixed appliance needs a way to disconnect it for service:
- A plug and receptacle serves as the disconnect for cord-connected appliances if it is accessible.
- For hard-wired appliances, the branch-circuit breaker serves if it is within sight of the appliance or can be locked in the open position; otherwise a separate disconnect switch is installed at the appliance.
- Some appliances, such as furnaces and air conditioners, have their own specific disconnect rules (Lesson 8).
Cords supplied with appliances must not be replaced with longer or lighter cords, and appliance cords must not be run through walls or ceilings; if the receptacle is too far away, a new receptacle is installed.
Appliances at 208 V
Many apartment and condominium buildings are supplied from a three-phase 120/208 V system, so each unit gets two phases of a wye, with 208 V between them rather than 240 V. Appliances rated for 240 V run at 208 V with reduced output for resistive elements (75% of rated power) and possibly incorrect operation of motors and controls. Most ranges, dryers and water heaters are dual-rated (240/208 V); others must be ordered for 208 V. EV chargers, heat pumps and induction cooktops must be checked for their 208 V performance.
Worked problem
A water heater at 208 V
A 4,500 W, 240 V water heater element is connected at 208 V. What power does it produce, and how much longer does recovery take?
Show solution
- Power scales with voltage squared: \(4{,}500 \times (208/240)^2 = 3{,}380\) W.
- Recovery time scales inversely with power: \(4{,}500/3{,}380 = 1.33\) times longer.
Answer: About 3.4 kW, and a third longer to reheat a tank. Buildings at 208 V should use appliances rated for 208 V or accept the slower performance knowingly.
Common mistakes
MistakeSizing appliance circuits from habit instead of the nameplate and instructions.
InsteadRead the nameplate and instructions; they are part of the appliance's certification.
MistakeInstalling a three-wire dryer receptacle on a new circuit.
InsteadUse a four-wire (14-30R) receptacle with a separate bonding conductor.
MistakeForgetting that water heaters are continuous loads.
InsteadSize the circuit at 125% of the heater's load.
MistakeIgnoring voltage drop on long runs to pumps and outbuildings.
InsteadCalculate drop and upsize conductors where needed.
MistakeAssuming 240 V appliances perform normally at 208 V.
InsteadUse dual-rated or 208 V appliances and expect 25% less heating power.
Summary and key terms
- Nameplates and installation instructions set appliance circuit requirements.
- Ranges, cooktops and ovens use demand factors; a single 40 A circuit often serves a range.
- Dryers need 30 A, 240 V four-wire circuits; water heaters are continuous loads, usually 30 A.
- Dishwashers, disposals, microwaves, refrigerators, washers and sump pumps usually get individual circuits.
- Long runs need voltage-drop checks; every appliance needs an accessible disconnect.
- At 208 V, resistive appliances produce about 75% of their 240 V rating.
- Nameplate
- The appliance's label of voltage, power and current ratings.
- Listing or certification
- Recognition by a testing body that a product meets a standard, including its instructions.
- Demand factor
- The fraction of a load counted in a calculation.
- Four-wire receptacle
- A receptacle with two hots, a neutral and a bonding contact.
- Continuous load
- A load expected to run at maximum for three hours or more.
- Individual branch circuit
- A circuit that supplies only one appliance.
- Disconnecting means
- A device that disconnects an appliance from its supply.
- Dual-rated appliance
- An appliance rated for both 240 V and 208 V.
- Heat-pump water heater
- A water heater that moves heat from the air using a heat pump.
- Recovery time
- The time for a water heater to reheat its tank.
Practice problems
Work each problem on paper first, then reveal the answer to check.
Current of a 5,600 W dryer at 240 V?
Show answer
23.3 A.
Typical dryer circuit?
Show answer
30 A, 240 V, 10 AWG copper, 14-30R receptacle.
Why are four-wire dryer connections required in new work?
Show answer
A broken neutral cannot then energize the frame.
Circuit rating for a 3,800 W continuous water heater at 240 V?
Show answer
15.8 A × 1.25 = 19.8 A: a 20 A circuit minimum.
Power of a 6,000 W, 240 V element at 208 V?
Show answer
4,507 W.
Why give a sump pump its own circuit?
Show answer
So other loads tripping a breaker do not stop it.
Voltage drop for 12 A over 60 m of 12 AWG (5.2 Ω/km)?
Show answer
12 × 2 × 0.06 × 5.2 = 7.5 V (3.1% at 240 V).
What serves as the disconnect for a cord-connected dishwasher?
Show answer
An accessible plug and receptacle.
Why can tankless electric water heaters be impractical?
Show answer
They draw 100–150 A, straining typical services.
Combined rating of a 6.6 kW cooktop and 3.4 kW oven?
Show answer
10 kW, treated as one range.
Lesson quiz · 5 questions
Score 60% or more to complete this lesson.
Create a free account to save your progress, take quizzes and earn a certificate.