HSE-222 · Lesson 8 of 12 · 27 min

Evacuation time, flow and stair capacity

How long will it take to get everyone out? Wardens are asked this by managers, by fire departments after drills and sometimes by worried occupants. Fire protection engineers answer it with detailed calculations and computer models, but wardens can understand the main ideas with simple arithmetic. Knowing where the time goes tells a warden where effort pays off: in many buildings, the minutes lost before people start moving, and the minutes spent queuing at doors and stairs, matter far more than walking speed. This lesson introduces the basic model, shows how door and stair widths limit flow, and explains how to use drill timings to improve a plan. It is awareness-level material: it does not replace an engineer's egress analysis.

The three parts of evacuation time

A useful simple model splits the time to evacuate into three parts. Pre-movement time runs from the alarm until people start moving to an exit; it includes recognizing the alarm, deciding to act, finishing tasks and gathering things. Travel time is the time to walk from the starting point to the exit, and depends on distance and walking speed. Flow time is the time it takes the whole group to pass through the narrowest point, usually a door or stair, and depends on the number of people and the effective width.

The simplest estimate adds the three: total time ≈ pre-movement + travel + flow. This overstates the time a little, because people walk and queue at the same time, but it is easy to calculate, it is conservative, and it shows clearly which part dominates. Engineers refine it with the time at which queues form and with separate calculations for each floor and stair, but wardens rarely need that level of detail.

A horizontal bar split into three segments: pre-movement about 2 minutes, travel about 0.6 minutes and flow through the door about 4.3 minutes, totalling about 7 minutes. A second bar shows the same floor with two doors and a 1-minute pre-movement, totalling about 3.7 minutes.
Where the time goes. Pre-movement and queuing usually matter more than walking.

Pre-movement: the part wardens control most

Pre-movement times vary enormously. In a well-drilled office where wardens act at once, most people may be moving within a minute. In a hotel at night, a hospital, a shopping centre or an office with frequent false alarms, pre-movement can run to many minutes, and in some fires people have waited ten minutes or more before leaving. Pre-movement also has a spread: a few people start almost immediately and a long tail follows. The last people to start often decide the total evacuation time.

Lesson 6 described how wardens cut pre-movement: visible presence, specific instructions, voice messages, and a culture in which every alarm is treated as real. Every minute saved in pre-movement is a minute saved for everyone, and unlike stair widths, it costs nothing to change.

Travel: walking speed and distance

Building codes limit the travel distance to an exit, typically to a few tens of metres, depending on occupancy and sprinkler protection. Unimpeded walking speeds for adults on the flat are around 1.2 m/s, falling sharply in dense crowds, in smoke, on stairs and for people with mobility impairments. Some people using walkers or canes move at 0.5 m/s or less. Going down stairs, an able-bodied adult in a light crowd typically takes 15 to 20 seconds per storey, including the landings.

Flow: why widths matter

When many people try to pass through a door or down a stair, they form a queue, and the rate at which they get through depends on the effective width. The effective width is the clear width minus a boundary layer on each side, because people do not walk right up against walls, door frames and handrails. The SFPE Handbook of Fire Protection Engineering gives typical boundary layers, for example about 15 cm for walls and door frames and about 9 cm measured from the centre of a handrail. For doors and corridors, a maximum specific flow of about 1.3 persons per second per metre of effective width is widely used. Stairs carry fewer people per metre, around 1.0 to 1.1 persons per second per metre for common stair geometries, because people slow down and space out on steps.

These are typical values for healthy adults moving in an orderly way. Real flows can be lower when people carry bags, when some need help, when doors swing against the flow or are heavy to open, or when two streams of people merge at a landing. Treat the figures as a guide, not a guarantee.

Worked problem

Estimating the evacuation time for one floor

An office floor holds 200 people. Drills show a typical pre-movement time of 2 minutes. The longest travel distance to the single exit door is 45 m, and people walk at about 1.2 m/s on the flat. The exit door has a clear width of 0.90 m. Using a specific flow of about 1.3 persons per second per metre of effective width, and subtracting a boundary layer of 0.15 m on each side of the door, estimate the time for everyone to pass through the door. Then see what a second door of the same width would do.

Show solution
  1. Effective width of the door: 0.90 − (2 × 0.15) = 0.60 m.
  2. Flow through the door: 1.3 × 0.60 ≈ 0.78 persons per second, or about 47 persons per minute.
  3. Flow time for 200 people: 200 ÷ 0.78 ≈ 256 s, about 4.3 minutes.
  4. Travel time for the furthest person: 45 ÷ 1.2 ≈ 38 s, about 0.6 minutes.
  5. Simple conservative sum: 2.0 + 0.6 + 4.3 ≈ 6.9 minutes. In reality the first people reach the door while others are still walking, so the true time is somewhat less, but the door queue dominates.
  6. With two doors, the flow time halves to about 2.1 minutes, and the total falls to about 4.7 minutes. Cutting the pre-movement time to 1 minute would save another minute.

Answer: About 7 minutes with one door, dominated by the queue; about 4.7 minutes with two doors, and less again if pre-movement is cut.

Approximate flows using typical SFPE-based values. For awareness only; engineers use the full method.
OpeningClear widthEffective widthApproximate flow
Single door0.85 m0.55 mAbout 43 persons per minute
Single door0.90 m0.60 mAbout 47 persons per minute
Pair of doors1.80 m1.50 mAbout 117 persons per minute
Corridor1.50 m1.20 mAbout 94 persons per minute
Stair with two handrails1.10 m0.92 mAbout 56 persons per minute
Stair with two handrails1.50 m1.32 mAbout 80 persons per minute

Stairs in multi-storey buildings

In a multi-storey building, the stairs are almost always the bottleneck. A stair can hold only so many people at once, and people from lower floors entering the stair must merge with people coming down from above. Studies of merging at stair landings show that the flow from the floor and the flow down the stair share the space, sometimes with priority to one or the other depending on the door position and on who is more assertive. Upper floors can take much longer to empty than lower floors, because their occupants have to wait for space in a stair that is already full.

Worked problem

How many people can a stair carry?

An eight-storey office building has two exit stairs, each 1.10 m wide between walls, with a handrail on each side. Each upper floor has 60 occupants, so 420 people on floors 2 to 8 need the stairs in a full evacuation. Use a stair specific flow of about 1.01 persons per second per metre of effective width (a typical value for common stair geometry), and subtract 0.09 m for each handrail. Estimate how long the stairs take to discharge everyone if both are available, and if one is lost to smoke.

Show solution
  1. Effective width of each stair: 1.10 − (2 × 0.09) = 0.92 m.
  2. Flow per stair: 1.01 × 0.92 ≈ 0.93 persons per second, about 56 persons per minute.
  3. Both stairs: 2 × 56 = 112 persons per minute. Time for 420 people: 420 ÷ 112 ≈ 3.8 minutes of flow at the stair exits, once the stairs are fully loaded.
  4. One stair only: 420 ÷ 56 = 7.5 minutes, roughly double.
  5. Add pre-movement and the time to walk down eight storeys, about 15 to 20 s per storey for able-bodied adults, or 2 to 3 minutes for the top floor. Losing a stair therefore turns a 6- or 7-minute evacuation into one of 10 minutes or more.

Answer: About 3.8 minutes of stair flow with both stairs and about 7.5 minutes with one, before adding pre-movement and travel; plans should assume a stair may be lost.

A cross-section of a stair with walls on both sides and a handrail on each side. Arrows show the boundary layers subtracted from the clear width to give the effective width, and people standing on the steps at typical spacing.
Effective width is the clear width minus the boundary layers next to walls and handrails.

Using the model to improve a plan

The value of the model for wardens is in showing which change helps most. If pre-movement dominates, work on alarm recognition, warden response and culture. If a single door or stair dominates, look at whether people can be spread across other exits; drills often show that most people use the exit they know best while another stair stands nearly empty. If one floor is slow because many people need help, that is a planning issue for assisted evacuation, not for the stairs. If losing one stair would double the time, make sure the plan, the wardens and the voice messages can redirect people quickly.

Wardens should never change the building, such as by removing doors, propping them open or blocking a stair, to improve flow. Exit widths and door arrangements are set by building codes and fire engineers for fire safety as well as flow. Suggestions go through the person in charge of the plan.

Measuring flow in a drill

Simple measurements in drills give real numbers to replace typical values. A warden with a stopwatch at a stair door can record when the alarm sounded, when the first person entered the stair, and when the last person entered. Another observer at the exit can record when the first and last people left the building. The difference between the alarm and the first movement is a direct measure of pre-movement. Dividing the number of people by the time between first and last through a door gives the actual flow. Comparing drills over time shows whether training and changes are working.

Simple drill measurements wardens can collect.
MeasurementHow to take itWhat it shows
Alarm to first movementNote the alarm time and when the first person leaves the areaFastest pre-movement
Alarm to last person leaving the floorWarden notes the time the floor is clearPre-movement tail and sweep time
First to last person through the exitObserver at the door with a counter and stopwatchActual flow rate for that door
Exit use by routeObservers count people at each exitWhether exits are used evenly
Alarm to all accounted forChief warden records when headcount is completeOverall effectiveness of the plan

Canadian building codes size exits using occupant loads and minimum widths per person rather than flow times, and some provinces allow alternative solutions supported by engineering egress analysis. The fire safety plan does not usually include evacuation time calculations, but drill records under the fire code should show how long evacuation took.

Common mistakes

  • MistakeAssuming walking speed is the main factor in evacuation time.

    InsteadLook first at pre-movement and queuing at doors and stairs.

  • MistakeUsing the full clear width of a door or stair to estimate flow.

    InsteadSubtract the boundary layers to get the effective width.

  • MistakePlanning as if both stairs will always be available.

    InsteadCheck how long evacuation takes if one stair is lost to smoke.

  • MistakePropping doors open or removing them to speed up flow.

    InsteadNever alter fire doors or exits; suggest changes through the plan owner.

  • MistakeTreating typical flow values as exact.

    InsteadUse them as a guide and replace them with drill measurements where possible.

Summary and key terms

  • Total evacuation time is roughly pre-movement plus travel plus flow.
  • Pre-movement is often the largest and most variable part, and wardens can reduce it most.
  • Adults walk about 1.2 m/s on the flat, much slower in crowds, in smoke and on stairs.
  • Effective width is the clear width minus boundary layers at walls, frames and handrails.
  • Doors carry about 1.3 persons per second per metre of effective width; stairs carry less.
  • Stairs are usually the bottleneck in multi-storey buildings, and losing one can double the time.
  • Drill measurements give real numbers and show whether changes are working.
Pre-movement time
Time from the alarm until people start moving to an exit.
Travel time
Time to walk from the starting point to the exit.
Flow time
Time for a group to pass through the narrowest point of the route.
Clear width
The measured open width of a door, corridor or stair.
Effective width
Clear width minus boundary layers at the edges.
Boundary layer
The edge strip of a route that people do not use, next to walls and handrails.
Specific flow
People passing per unit time per unit of effective width.
Bottleneck
The narrowest point that limits the flow of people.
Merging
People from a floor joining people already moving down a stair.
Egress analysis
An engineering calculation or model of how long evacuation takes.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. Name the three parts of the simple evacuation time model.

    Show answer

    Pre-movement, travel and flow.

  2. Why is the simple sum conservative?

    Show answer

    People walk and queue at the same time, so the parts overlap.

  3. A door has a clear width of 1.00 m. What is its effective width with 0.15 m boundary layers?

    Show answer

    0.70 m.

  4. How many people per minute pass a door with 0.70 m effective width at 1.3 p/s/m?

    Show answer

    1.3 × 0.70 × 60 ≈ 55 persons per minute.

  5. How long would 165 people take through that door?

    Show answer

    About 3 minutes.

  6. Why do stairs carry fewer people per unit width than doors?

    Show answer

    People slow down and space out on steps.

  7. Why do upper floors often take longer to empty?

    Show answer

    Their occupants must wait for space in stairs already loaded by others.

  8. A drill shows one stair nearly empty and the other queued. What might wardens do?

    Show answer

    Direct some people to the less used stair, and ask the plan owner to review routes and signs.

  9. How can a warden measure flow at a door in a drill?

    Show answer

    Count the people and time the first and last through; divide people by time.

  10. Why must wardens not prop doors open to improve flow?

    Show answer

    Exit doors are fire protection features; propping them lets smoke spread.