GAS-110 · Lesson 11 of 12 · 21 min

Gas permits, inspections and the safety authority

▶ Video coming soon A video version of this lesson is on the way.

Hank Morrow, Bayline's owner, likes to say that the paperwork is part of the gas line. In late October, he sat Jonah down at the shop with the file for a job they had just finished: a new gas line and an unvented garage heater replaced with a vented unit heater in a detached workshop. The file held the job order, Bayline's record of the pressure test with the gauge reading and test time, the appliance's installation manual, the combustion readings at start-up, a copy of the contractor's TSSA registration and Rosa's certificate number, and a note of the date the utility turned on gas to the new branch. "If something goes wrong in ten years," Hank said, "this file is how we show we did it right. And if we did it wrong, it's how the next person finds out what we did."

This lesson describes how gas work is approved and checked: who the safety authority is, what permits and approvals are needed, how inspections work, what happens when an unsafe condition is found, and what records a gasfitter keeps.

The safety authority

In Ontario, the Technical Standards and Safety Authority (TSSA) is the regulator for fuels. It is a not-for-profit organization that administers the Technical Standards and Safety Act, 2000 on behalf of the province. For gas work, its main roles are:

  • adopting the code: TSSA issues the code adoption documents that bring CSA B149.1 and B149.2 into force in Ontario, with any Ontario amendments;
  • certifying people: TSSA issues gas technician certificates (G.3, G.2, G.1) and other fuels certificates, and recognizes training providers;
  • registering contractors: every business that does fuels work must be registered with TSSA;
  • inspecting and auditing: TSSA inspectors inspect installations, investigate incidents and complaints, and audit contractors' work; and
  • enforcing: TSSA can issue orders, suspend or revoke certificates and registrations, and refer cases for prosecution.

Other provinces have their own authorities: Technical Safety BC, the Alberta Safety Codes Authority and municipal or agency inspectors in Alberta, the Technical Safety Authority of Saskatchewan, Manitoba's Office of the Fire Commissioner, the Régie du bâtiment du Québec, and provincial inspection branches in Atlantic Canada. Their rules on certificates, permits and inspections differ, so a gasfitter who moves must learn the new province's system before working.

Permits, approvals and authorization

The Ontario system is built mainly on certified people and registered contractors rather than on a permit for every job. For most residential and light commercial gas work, there is no separate municipal gas permit of the kind many US cities require. Instead, the law requires that the work be done by a registered contractor using certified technicians, to the adopted code, and that the contractor test the system and keep records. TSSA then inspects a share of installations and audits contractors. Some work needs more: TSSA approval is required before certain equipment can be used, such as appliances that are not certified to a recognized standard, which need a field approval, and large or special installations. Propane storage over certain sizes and propane facilities such as cylinder filling plants need TSSA licences or approvals under the propane regulation. A municipal building permit may also be needed when the work is part of a larger construction or alteration project, such as a new house or an addition, and the contractor checks with the local building department.

The gas utility has its own requirements. Before gas is turned on to a new service or a new piping system, the utility needs to know that the piping has been installed and tested. Utilities have forms and procedures for this, and they will not turn on gas to a system that has not passed its test or that shows a leak or hazard when they arrive.

Inspections

Inspections check that work meets the code before it is concealed or put into service. In Ontario, TSSA inspectors may visit any installation, and some installations, such as uncertified equipment and certain large appliances, must be inspected and approved before use. A TSSA inspector may also come during or after an incident investigation. The inspector looks at materials, sizing, support, protection, valves, test results, venting, clearances, combustion and ventilation air, and the installation against the manufacturer's instructions.

A five-step flowchart: registered contractor files permit; certified technician installs; pressure test and leak test; TSSA or utility inspection as required; gas turned on, start-up and records. A note says that if an inspection fails, the work is corrected and inspected again before gas is supplied.
The usual sequence for a new installation. Details vary with the type of work and the jurisdiction.

An inspection is not a substitute for doing the work right. Inspectors see the installation for minutes; the gasfitter is responsible for every joint, every clearance and every reading. Codes make the installer responsible for compliance whether or not the work is inspected.

If an inspection finds a deficiency, the inspector writes it up. The contractor corrects it and asks for a reinspection. Serious or repeated problems can lead to orders, certificate discipline or prosecution. Being courteous, having the documents ready, and leaving the test gauge on the line for the inspector to see all make inspections go smoothly.

Unsafe conditions

Gasfitters often find unsafe conditions in existing installations that someone else installed: a missing vent connector screw, a corroded flexible connector, a water heater backdrafting into a basement, an appliance with no shutoff valve, or a gas line run through a cold-air return. The codes and regulations require a gasfitter who finds such a condition to act, even if it is not part of the job they were called for.

In general terms, unsafe conditions fall into two groups. An immediately hazardous condition, such as a gas leak, CO spillage, a blocked vent or a failed safety control, is one that could cause injury or damage at once. The gasfitter shuts off the gas to the affected equipment, or to the whole building if needed, attaches a tag that warns against use, and informs the owner or occupant in writing. A non-immediately hazardous condition, such as a missing clearance label or an improperly supported pipe that is not yet leaking, must be corrected within a reasonable time; the gasfitter tags it, explains the problem and records it.

In Ontario, the regulations and TSSA's procedures set out how to handle these conditions, including the tag to use, the notice to give the owner and the distributor or supplier, and when the condition must be reported to TSSA. Utilities and propane suppliers follow the same system and may refuse to supply gas to equipment tagged as unsafe. Tampering with or removing a tag without correcting the condition is an offence.

The customer may object, especially in winter when shutting off a furnace means no heat. The gasfitter explains the hazard plainly, offers solutions, and documents the refusal if the customer will not allow repairs. Leaving an immediately hazardous appliance running is never an option. Lesson 12 shows what can happen when hazards are missed.

Records and documentation

Good records protect the customer, the next technician and the company. A complete file for a gas job usually includes:

What goes in a gas job file
RecordWhy it matters
Job order and scope of workShows what was asked for and agreed
Permit or approval numbers, where requiredLinks the job to the authority's records
Pressure test record: test medium, pressure, duration, gauge used, resultProves the piping was tight before gas was introduced
Appliance make, model, serial number and inputIdentifies the equipment for recalls and service
Start-up readings: inlet and manifold pressure, input, combustion analysis, draft or spillage testShows the appliance was set up to the manufacturer's specifications
Unsafe conditions found and actions taken, with the customer's signatureShows the hazard was reported and handled
Installer's name and certificate numberShows who did the work and that they were qualified

Many companies now record all of this in a service app on a tablet, with photographs of the installation, rating plates and test gauges. Photographs are especially valuable: they show what was there before and after the work, and they settle disputes.

Worked problem

Planning for the next certificate

Rosa tells Jonah that, once he holds his G.2, he will need at least 4,000 hours of field experience as a G.2, including at least 500 hours on appliances over 400,000 Btu per hour, before he can try for the G.1. If he works about 1,750 field hours a year, and about 10 in 100 of those hours are on large commercial appliances, which requirement will take longer, and about how many years will it take?

Show solution
  1. Years to reach 4,000 total hours:
  2. \[\frac{4{,}000}{1{,}750} \approx 2.3 \text{ years}\]
  3. Large-appliance hours per year:
  4. \[1{,}750 \times 0.10 = 175 \text{ hours}\]
  5. Years to reach 500 large-appliance hours:
  6. \[\frac{500}{175} \approx 2.9 \text{ years}\]

Answer: The large-appliance hours are the limit: about 2.9 years, compared with 2.3 years for the total. Jonah should ask to be scheduled on commercial jobs with a G.1 so that both requirements are met at about the same time, and log every hour carefully, because TSSA will ask for proof.

Certified appliances and manufacturers' instructions

The codes require that gas appliances and many components be certified by an accredited organization to a recognized standard, and bear the certification mark. In Canada, common marks include those of CSA Group, Intertek (ETL) and UL Solutions, showing certification to Canadian standards such as the CSA/ANSI Z21 series. Certification means a sample of the appliance was tested for safe ignition, combustion, controls and construction, and that the factory is audited. An appliance without a recognized mark cannot simply be installed; it needs a TSSA field approval before use.

Certification also gives the manufacturer's installation instructions special weight. The codes require appliances to be installed according to those instructions, so a clearance, vent length or gas pressure in the manual is as binding as a rule in the code. Where the code and the manual differ, the stricter requirement generally applies. Inspectors check installations against both, and keeping the manual with the appliance, as most manufacturers require, helps everyone who works on it later.

Staying current

Codes change on a regular cycle, and each change is debated by committees of manufacturers, utilities, regulators, contractors and other experts before it is published. Once a new edition is adopted, installations must follow it, and some changes apply to existing installations when they are altered. A professional gasfitter follows notices from TSSA, the utility and the major manufacturers, takes updating courses when a new edition arrives, and reads the actual text of the adopted code rather than relying on summaries or memory.

Findings inspectors see often
Common inspection findingHow to avoid it
Missing or wrong sediment trap or shutoff valveInstall one at each appliance as the code and manual require
Unsupported or unprotected pipingSupport at the intervals required and protect where exposed to damage
Clearance to combustibles not metCheck the manual and rating plate before setting the appliance
Vent connector joints not fastened or sloped wrongFasten every joint and keep the required rise toward the chimney
No pressure test record or gauge on the lineTest before concealing and leave the gauge for the inspector
Combustion air not providedSize and install the air supply before start-up

Liability is the final reason the paperwork matters. If an installation is involved in a fire, explosion or CO incident, investigators and insurers will ask who did the work, to what code, with what tests, and what was told to the customer. A contractor with complete records can answer; one without them may be held responsible for problems it did not cause.

Professional conduct

Gasfitters hold the public's trust. A certificate or license can be suspended or revoked for doing work outside its scope, lending a certificate number to an unqualified person, falsifying test records, or knowingly leaving a hazard. Technicians also have a duty to cooperate with inspectors and investigators and to report hazards they find, even when the report is unwelcome to a customer or an employer. Most jurisdictions protect workers who raise safety concerns in good faith. Behaving professionally is not only about avoiding penalties; it is what makes customers, inspectors and utilities trust the work.

Common mistakes

  • MistakeThinking an inspection makes the inspector responsible for the work.

    InsteadThe installer is responsible for code compliance whether or not the work is inspected.

  • MistakeLeaving an immediately hazardous condition in place because it was not part of the job.

    InsteadShut off, tag, inform the owner in writing and report as required, whatever the original call.

  • MistakeRemoving an unsafe-condition tag left by the utility once a customer says the problem is fixed.

    InsteadCorrect the hazard and follow the utility's and authority's procedure for restoring service.

  • MistakeKeeping test results only in your head.

    InsteadRecord the test medium, pressure, duration, gauge and result in the job file.

Summary and key terms

  • TSSA is Ontario's fuels safety authority: it adopts the gas codes, certifies technicians, registers contractors, inspects and enforces. Ontario relies mainly on certified technicians and registered contractors, with TSSA approvals for special cases and municipal permits for some construction. Inspections check work before it is concealed or used, but the installer remains responsible.
  • Immediately hazardous conditions are shut off, tagged and reported; others are tagged and corrected.
  • Complete records protect the customer, the next technician and the company.
Authority having jurisdiction
The body that enforces the code and approves installations in a place.
Permit
Written permission from the authority to carry out regulated work.
Inspection
An examination of work by the authority to check compliance with the code.
Immediately hazardous condition
A condition that could cause injury or damage at once, such as a leak or CO spillage.
Field approval
Approval of a specific piece of equipment on site when it is not certified to a recognized standard.
Job file
The records of a gas job: scope, permits, tests, readings, conditions found and installer.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What are TSSA's main roles in gas work?

    Show answer

    Adopting codes, certifying technicians, registering contractors, inspecting and enforcing.

  2. Why does the gas utility need to know a new system has been tested?

    Show answer

    It will not turn on gas to a system that has not passed its test or shows a hazard.

  3. What is the difference between an immediately hazardous and a non-immediately hazardous condition?

    Show answer

    An immediately hazardous condition could cause harm at once and is shut off; the other must be corrected within a reasonable time.

  4. Name four items in a complete gas job file.

    Show answer

    Scope of work, permit or approval numbers, pressure test record, appliance data, start-up readings, unsafe conditions and installer details.

  5. Who is responsible for code compliance if the work is never inspected?

    Show answer

    The installer.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz