PWR-120 · Lesson 1 of 12 · 27 min

Heat, steam and hot water basics

▶ Video coming soon A video version of this lesson is on the way.

On Thursday, September 17, 2026, the day after the inspector signed off boiler 3, Lorne Fitzwilliam stood with Tamar Ellingsen in front of the control room's steam header gauge. It read 150 psi. "Tell me the temperature of the steam in that header," he said. Tamar looked for a thermometer and found none. "You don't need one," Lorne said. "If the steam is saturated, the pressure tells you the temperature. That's the first thing a boiler operator learns, and everything else in this course builds on it."

This course covers the boilers and plant equipment that a new stationary engineer learns first, the material behind Ohio's low and high pressure boiler operator exams and the first stage of most graded licenses. This first lesson explains heat and temperature, sensible and latent heat, how water turns to steam, how pressure sets the boiling point, and how to read a steam table.

Heat and temperature are not the same

Temperature tells you how hot something is: it measures the average energy of motion of the molecules in a substance. Heat is energy moving from a hotter body to a colder one because of the temperature difference. A bathtub of warm water and a cup of boiling water have very different temperatures, but the bathtub holds far more heat because it holds far more water. A boiler operator cares about both: temperature decides whether a pipe can burn you or a metal can be damaged, and heat decides how much fuel the plant burns.

In US customary units, temperature is measured in degrees Fahrenheit (°F) and heat in British thermal units (Btu). One Btu is the heat that raises one pound of water by 1 °F. A rate of heat flow is measured in Btu per hour (Btu/h), so a boiler rated about 27,300,000 Btu/h delivers that much heat to its water each hour at full load. Plants also use boiler horsepower (about 33,475 Btu/h) and, for comparison with Canadian and European equipment, kilowatts (1 kW is about 3,412 Btu/h).

Heat always flows from hot to cold, by three routes. Conduction carries heat through solid material, as through a boiler tube wall. Convection carries heat by the movement of a fluid, as hot flue gas sweeps past tubes or boiler water circulates. Radiation carries heat as infrared energy, as the burner flame radiates to the furnace walls. In a boiler all three work together: the flame radiates to the furnace tubes, hot gases convect heat to the rest of the tubes, and the heat conducts through the steel into the water.

Sensible heat and specific heat

Heat that changes the temperature of a substance, without changing its state, is called sensible heat, because you can sense the change with a thermometer. The amount of heat needed depends on the mass, the temperature change and the material's specific heat capacity, the heat needed to raise one unit of mass by one degree. Water's specific heat is high compared with most materials, which is why water is such a good way to carry heat around a building.

Typical specific heats near room temperature. Values vary slightly with temperature.
QuantitySIUS customary
Specific heat of water (typical)about 4.19 kJ/(kg·K)1 Btu/(lb·°F)
Specific heat of steel (typical)about 0.49 kJ/(kg·K)about 0.12 Btu/(lb·°F)
Specific heat of air at constant pressure (typical)about 1.0 kJ/(kg·K)about 0.24 Btu/(lb·°F)

The formula for sensible heat is the same in any unit system: heat equals mass times specific heat times temperature change.

\[Q = m \, c \, \Delta T\]

Worked problem

Heating feedwater

The deaerator heats 32,200 lb of feedwater each hour from 140 °F to 239 °F. Using a specific heat of 1 Btu/(lb·°F), how much heat does that take each hour?

Show solution
  1. Temperature rise:
  2. \[239 - 140 = 99 \text{ °F}\]
  3. Heat per hour:
  4. \[32{,}200 \times 1 \times 99 = 3{,}187{,}800 \text{ Btu/h}\]
  5. In kW, for comparison:
  6. \[3{,}187{,}800 \div 3{,}412 \approx 934 \text{ kW}\]

Answer: About 3,187,800 Btu/h, or about 934 kW. That heat comes from low pressure steam that would otherwise be wasted, which is one reason a deaerator saves fuel.

Latent heat: changing state

Heat that changes the state of a substance, without changing its temperature, is called latent heat, from the Latin for hidden. When water at its boiling point takes in heat, its temperature does not rise; instead the heat breaks the bonds between molecules and turns liquid into vapor. The heat needed to turn a unit mass of water at its boiling point into steam at the same temperature is the latent heat of vaporization (or of evaporation). When steam condenses, it gives exactly that heat back. That is why steam is such a powerful way to deliver heat: a kilogram of steam condensing in a customer's heat exchanger gives up far more heat than a kilogram of hot water cooling by a few degrees.

At atmospheric pressure, water boils at 212 °F, and its latent heat of vaporization is about 970 Btu/lb. Raising a kilogram of water from 32 °F to 212 °F takes only about 180 Btu, so boiling it takes more than five times as much heat as heating it to the boiling point.

A graph of water temperature against heat added. A sloped line rises from cold water to the boiling point, a long flat section shows boiling at constant temperature, and a short steep line shows the steam being superheated. The flat section is labeled latent heat and the sloped sections sensible heat.
Heating water at atmospheric pressure: sensible heat raises the temperature, latent heat changes the state.

There is also a latent heat of fusion, the heat needed to melt ice at 32 °F, about 144 Btu/lb. It matters to a boiler operator mainly in winter, when an idle pipe, a steam trap or a sensing line freezes, and in refrigeration plants.

Boiling point depends on pressure

Water does not always boil at 212 °F. The boiling point, called the saturation temperature, rises with pressure. In a closed boiler the steam pressure builds up above the water and pushes the boiling point higher. At Cantwell's operating pressure of 150 psi gauge, water boils at about 366 °F. As long as liquid and vapor are both present, the pressure and the temperature are locked together: if you know one, a steam table gives the other. Steam and water in this state are called saturated.

This link explains several things an operator sees every day. When the steam pressure drops, some of the hot water in the boiler instantly flashes to steam because it is now above its new boiling point. When condensate at 366 °F is released to an atmospheric tank, part of it flashes to steam, which is the cloud above a vent. And when a boiler is shut down and cools, the pressure falls with the temperature, until steam condensing inside it can pull a vacuum unless the vent is opened.

Saturation temperatures from a standard steam table, rounded. Always use the full table for real calculations.
Gauge pressureAbsolute pressure (approx.)Saturation temperature (approx.)
0 psig14.7 psia212 °F
15 psig29.7 psia250 °F
50 psig64.7 psia298 °F
150 psig164.7 psia366 °F
200 psig214.7 psia388 °F

Remember from PWR-110 that steam tables are written in absolute pressure (psia), so an operator adds atmospheric pressure, about 14.7 psi, to the gauge reading (psig) before looking up a value. Forgetting that step is one of the most common mistakes on licensing exams.

Reading a steam table

A saturated steam table lists, for each pressure (or temperature), the saturation temperature, the specific volume of the water and the steam, and three enthalpies. Enthalpy is the heat content of a unit mass of water or steam, measured from a reference point (water at 32 °F). The three columns are:

  • h_f (water): the enthalpy of saturated water, which is the sensible heat needed to bring water from the reference point to its boiling point at that pressure.
  • h_fg (evaporation): the latent heat needed to turn that saturated water into saturated steam.
  • h_g (steam): the enthalpy of dry saturated steam, which is h_f plus h_fg.

As pressure rises, h_f rises (the water must be hotter before it boils) and h_fg falls (less latent heat is needed). The total h_g changes only a little. This is why low pressure steam carries more latent heat per kilogram than high pressure steam, and why plants often reduce steam pressure before sending it to heating coils.

Rounded saturated steam values at atmospheric pressure and at Cantwell's operating pressure.
PressureTemperatureh_f, waterh_fg, evaporationh_g, steam
14.7 psia212 °F180 Btu/lb970 Btu/lb1,150 Btu/lb
164.7 psia366 °F338 Btu/lb857 Btu/lb1,195 Btu/lb

Worked problem

Heat to make the plant's steam

Boiler 3 makes 25,400 lb/h of saturated steam at 150 psig from feedwater at 239 °F. Water at 239 °F has an enthalpy of about 207 Btu/lb. Using the table, how much heat goes into each pound, and what is the boiler output in Btu/h?

Show solution
  1. Heat per pound:
  2. \[1{,}195 - 207 = 988 \text{ Btu/lb}\]
  3. Output:
  4. \[25{,}400 \times 988 = 25{,}095{,}200 \text{ Btu/h}\]
  5. In kW, for comparison:
  6. \[25{,}095{,}200 \div 3{,}412 \approx 7{,}355 \text{ kW}\]

Answer: About 988 Btu per pound, or about 25,100,000 Btu/h (about 7,355 kW), which is within boiler 3's rating. The example shows how a steam table turns a flow and two temperatures into a heat load.

Wet, dry and superheated steam

Steam leaving a boiler drum is rarely perfectly dry. Tiny droplets of water are carried along with it, and the fraction of the mixture that is actually vapor is called the dryness fraction or steam quality. Steam with a quality of 0.97 is 97 parts vapor and 3 parts water by mass, and it carries only 97 in 100 of the latent heat that dry steam would. Wet steam erodes valves and turbine blades and causes water hammer, so drums have separators and dryers to remove the water.

If dry steam is heated further, away from contact with water, its temperature rises above the saturation temperature and it becomes superheated steam. Superheated steam behaves more like a gas: its pressure and temperature are no longer locked together, so an operator needs both to describe it. Superheaters are fitted to power boilers that drive turbines, because superheated steam does not condense in the turbine's first stages. Cantwell's boilers make saturated steam for heating customers, so the plant has no superheaters; PWR-220 covers them.

Worked problem

Wet steam carries less heat

Steam at 150 psig has a quality of 0.97. Using h_f = 338 Btu/lb and h_fg = 857 Btu/lb, what is its enthalpy, and how much less heat does each pound carry than dry steam?

Show solution
  1. Enthalpy of wet steam:
  2. \[h = h_f + x \, h_{fg} = 338 + 0.97 \times 857 \approx 1{,}169 \text{ Btu/lb}\]
  3. Shortfall:
  4. \[1{,}195 - 1{,}169 = 26 \text{ Btu/lb}\]

Answer: About 1,169 Btu/lb, which is 26 Btu/lb (3 in 100 of the latent heat) less than dry steam. The water also has to be drained by traps before it causes trouble.

Hot water as a heat carrier

Not every plant makes steam. Cantwell's two hot water boilers heat water that is pumped around a closed loop to customer buildings and back, giving up sensible heat in their heat exchangers. A hot water system's capacity depends on the flow and on the temperature drop between supply and return. The same formula, Q = m c ΔT, applies, with the flow rate in place of the mass.

Hot water systems are classed by temperature. Low temperature systems run at or below 250 °F at no more than 160 psi, and US codes treat those boilers as heating boilers; high temperature hot water systems run above that and are built and operated like power boilers. Cantwell's loop supplies about 203 °F water and returns at about 158 °F (typical).

Worked problem

Heat carried by the hot water loop

The hot water loop circulates 454 US gallons per minute with a supply of 203 °F and a return of 158 °F. Using the rule of thumb that 1 gpm with a 1 °F drop carries about 500 Btu/h, how much heat is the loop delivering?

Show solution
  1. Temperature drop:
  2. \[203 - 158 = 45 \text{ °F}\]
  3. Heat rate:
  4. \[500 \times 454 \times 45 = 10{,}215{,}000 \text{ Btu/h}\]

Answer: About 10,215,000 Btu/h, which is one hot water boiler at full rating. The 500 factor comes from 8.33 lb per gallon times 60 minutes per hour, and is close enough for plant checks.

Why this matters on the floor

Lorne ended the lesson back at the gauge. A pressure reading tells an operator the temperature of every surface in contact with the steam, so a steam line at 150 psi is at about 366 °F even where its insulation is missing. Pressure falling while the burners are firing hard means the steam is being used faster than the boiler can make it. Condensate flashing at a vent shows that heat is being lost. And a pressure gauge that reads higher than the temperature allows means a gauge, a thermometer or the steam itself is not what it seems. "You read the plant through its pressures and temperatures," Lorne said. "Learn to check one against the other."

Common mistakes

  • MistakeLooking up a steam table with the gauge pressure.

    InsteadAdd atmospheric pressure to get absolute pressure first.

  • MistakeTreating heat and temperature as the same thing.

    InsteadTemperature says how hot; heat is the energy that flows. Mass matters.

  • MistakeExpecting water to boil at the same temperature at any pressure.

    InsteadThe saturation temperature rises with pressure.

  • MistakeIgnoring the water in wet steam.

    InsteadWet steam carries less latent heat and must be drained by traps.

  • MistakeAssuming an insulated steam line is cool where the insulation is missing.

    InsteadEvery surface touching saturated steam is at the saturation temperature.

Summary and key terms

  • Temperature measures how hot something is; heat is energy flowing because of a temperature difference.
  • Sensible heat changes temperature (Q = m c ΔT); latent heat changes state at constant temperature.
  • Water boils at 212 °F at atmospheric pressure; the saturation temperature rises with pressure.
  • Steam tables use absolute pressure and give h_f, h_fg and h_g; h_g = h_f + h_fg.
  • Wet steam has a quality below 1 and carries less heat; superheated steam is heated above its saturation temperature.
  • Hot water systems carry sensible heat; their output depends on flow and temperature drop.
Saturation temperature
The boiling point of water at a given pressure.
Sensible heat
Heat that changes a substance's temperature.
Latent heat
Heat that changes a substance's state at constant temperature.
Enthalpy
The heat content of a unit mass of water or steam, from a reference point.
Steam quality
The fraction of a steam and water mixture that is vapor.
Superheated steam
Steam heated above its saturation temperature.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What does a saturated steam table need you to do with a gauge pressure reading?

    Show answer

    Add atmospheric pressure to get absolute pressure.

  2. What is the saturation temperature at 150 psi gauge?

    Show answer

    About 366 °F.

  3. Which column of a steam table gives the latent heat?

    Show answer

    h_fg, the heat of evaporation.

  4. Steam has a quality of 0.95. What does that mean?

    Show answer

    95 parts vapor and 5 parts water by mass.

  5. How does the latent heat change as pressure rises?

    Show answer

    It falls.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz