ARCH-330 · Lesson 4 of 12 · 21 min
Building area and height
Joon-ho asks the question everyone has been waiting to ask. 'How big can a building be?' Kostyshyn smiles. 'That depends on what it is used for, what it is built of, whether it has sprinklers, how many sides a fire truck can reach, and how you measure it. Which is why the measuring comes first.' She draws a section through a building on a slope, with a basement half out of the ground at one end and fully buried at the other, a mezzanine inside, and a rooftop mechanical penthouse. 'How many stories is this?' Each student gives a different answer. 'You are all thinking like architects. The code thinks like a lawyer. It has its own definitions, and they are what count.'
Why size is limited
Codes limit the size of buildings because size is a measure of how many people a fire can reach and how hard the fire will be to fight. A tall building takes longer to evacuate and puts firefighters further from the street. A building with a large area lets a fire grow larger before it meets a wall, and leaves firefighters with longer distances to cover inside. The code's limits are a trade between size and protection. The more a building does to keep a fire small and slow, by sprinklers, by noncombustible construction, by fire-rated floors and walls and by access for firefighters, the larger it may be. A one-story wood building without sprinklers may be quite small; a sprinklered concrete building may be unlimited.
The limits in the International Building Code are set in Chapter 5 by three tables. Table 504.3 gives the allowable height in feet above grade plane, Table 504.4 the allowable number of stories above grade plane, and Table 506.2 the allowable area per story. Each table is organized by occupancy group and by type of construction, and each gives different values for buildings without sprinklers, with an NFPA 13 sprinkler system, and for residential buildings with an NFPA 13R system. A designer finds the allowable size by reading across for the building's occupancy and down for its construction type, then adding the increase for frontage where it applies.
Measuring a building
The International Building Code defines its terms carefully. Building area is the area included within the surrounding exterior walls, or the exterior walls and fire walls, of each story; allowable area is checked story by story. Building height is measured in feet from grade plane to the average height of the highest roof surface, and in stories above grade plane. Grade plane is a reference plane at the average of the finished ground level adjoining the building at its exterior walls. A story above grade plane is any story whose floor is entirely above grade plane, or whose floor is more than 6 feet above grade plane, or more than 12 feet above the finished ground at any point. A basement may therefore count as a story on a sloping site. A mezzanine of not more than one third of the floor area of the room or space in which it is located is not counted as a story, provided it meets the code's other conditions.
Rooftop structures add another trap. A penthouse is not counted as a story if it is limited in area and height and encloses only mechanical equipment, stairs, elevators or similar services, as set out in the code's section on rooftop structures; a penthouse with any other use counts as a story. Callum's library monitors on the hub, which bring north light down into the reading room, are part of the roof, not stories. A rooftop terrace with a small glass pavilion for parties, which Ingrid drew on Greenway Homes, is a different matter and needs checking.
Sprinklers and streets
Two things make the biggest difference to how large a building may be. The first is sprinklers. Sprinklers keep most fires small, and both codes allow much larger, and often taller, buildings when they are installed throughout. The second is access for firefighters. A building that can be reached from several sides lets firefighters attack a fire from more than one direction and protect the buildings next to it.
The International Building Code adds a frontage increase to the allowable area when more than a quarter of the building's perimeter fronts on a public way or open space at least 20 feet wide, with access for the fire department. The increase factor is the share of the perimeter that has frontage, less one quarter, multiplied by the width of the open space divided by 30, using a width of no more than 30 feet. The allowable area per story is then the tabular area plus the non-sprinklered tabular area multiplied by the increase factor.
Table 506.2 gives four values for many occupancies: NS for buildings without sprinklers, S1 for one-story buildings with an NFPA 13 system, SM for buildings of more than one story with an NFPA 13 system, and S13R for residential buildings with an NFPA 13R system, which gets no area increase over NS. For a building of more than one story, the allowable area per story is checked for each story, and the total area of all stories is also limited, generally to the allowable area per story times the number of stories above grade plane, but not more than three, for sprinklered buildings.
| Group and type | Height (ft) NS / S / S13R | Stories NS / S / S13R | Area per story (ft²) NS / SM / S13R |
|---|---|---|---|
| R-2, Type V-A | 50 / 70 / 60 | 3 / 4 / 4 | 12,000 / 36,000 / 12,000 |
| R-2, Type III-A | 65 / 85 / 60 | 4 / 5 / 4 | 24,000 / 72,000 / 24,000 |
| A-3, Type V-A | 50 / 70 / – | 2 / 3 / – | 11,500 / 34,500 / – |
| E, Type V-A | 50 / 70 / – | 1 / 2 / – | 18,500 / 55,500 / – |
| B, Type V-A | 50 / 70 / – | 3 / 4 / – | 18,000 / 54,000 / – |
Checking Greenway Homes
The students check Greenway Homes first. Its four-story U-shaped block has a north bar and an east bar joined at the corner core, and a row of stacked townhouses on the west. Wren decides to separate the townhouses from the rest with a fire wall, so that each part is treated as a separate building for area. The script checks the main block.
# Greenway Homes main block: height, stories and area per story (R-2)
grade_plane = 97.0 # average finished ground at exterior walls (ft, site datum)
floors = [97.7, 108.0, 118.3, 128.6] # floor elevations (ft)
roof = 138.9
stories = sum(1 for f in floors if f >= grade_plane or f - grade_plane > 6)
height = roof - grade_plane
print(f"stories above grade plane {stories}, height {height:.1f} ft")
parts = {"north bar": (147, 36), "east bar": (92, 56)}
area = sum(w * d for w, d in parts.values())
P = 2 * (147 + 36) + 2 * (92 + 56) - 2 * 36 # joined at the corner
F, W = 0.62 * P, 30 # frontage on the greenway, streets and court
If = max(0.0, (F / P - 0.25) * W / 30)
for name, NS, At, smax, hmax in [("Type V-A, NFPA 13R", 12000, 12000, 4, 60),
("Type V-A, NFPA 13", 12000, 36000, 4, 70)]:
Aa = At + NS * If
ok = area <= Aa and stories <= smax and height <= hmax
print(f"{name}: allowable {Aa:,.0f} ft2 per story vs {area:,} ft2; stories {stories}/{smax}; "
f"height {height:.0f}/{hmax} ft -> {'OK' if ok else 'not OK'}")stories above grade plane 4, height 41.9 ft Type V-A, NFPA 13R: allowable 16,440 ft2 per story vs 10,444 ft2; stories 4/4; height 42/60 ft -> OK Type V-A, NFPA 13: allowable 40,440 ft2 per story vs 10,444 ft2; stories 4/4; height 42/70 ft -> OK
The main block passes both ways. With an NFPA 13R system, which costs less and is common in apartment buildings of up to four stories, the allowable area per story is about 16,400 square feet once the frontage increase is added, and the building uses about 64% of it. With a full NFPA 13 system the allowable area rises to about 40,400 square feet. Joon-ho notices how much hangs on the grade plane. If the site were lower along the south side, so that the ground floor sat more than 6 feet above grade plane, the bike room and parking level would count as a story and the building would be five stories, beyond what Type V-A allows.
Checking the community hub
The hub contains A-3 and E occupancies, two stories high and sprinklered with an NFPA 13 system, with a footprint of about 16,500 square feet. In Type V-A construction, Group A-3 is allowed 34,500 square feet per story and three stories, and Group E 55,500 square feet and two stories. Because Callum separates the daycare, each part is checked on its own and the ratios of actual to allowable area are added on each story; the sum on the ground floor is about 0.43, well under the limit of one. If the daycare had been on the second floor, the E occupancy would still be allowed two stories, but the daycare would have become Group I-4, with its own, much stricter, limits. Kostyshyn notes that the library monitors, which rise to about 36 feet, do not add a story, and the height is far below the 70 feet allowed.
Callum asks why it matters to leave spare capacity. Kostyshyn's answer is practical. Designs grow. A program that starts at 2,400 square meters often ends at 2,700 after the client adds rooms and the engineers add shafts. A building that is right at the limit of its article or table at schematic design will be over it by design development, and changing the construction type then is very expensive. Experienced architects check the limits early, choose a classification and construction with room to grow, and check again at every stage.
Firewalls and separate buildings
A fire wall is a fire-resistance-rated wall with structural stability that allows collapse of construction on either side without collapse of the wall, and that divides a building into parts treated as separate buildings for allowable height and area. It must have the rating required by the code, typically two, three or four hours depending on the occupancy, must extend continuously from the foundation to or through the roof, and must have rated protection at every opening, with openings limited to a share of the wall's length. Fire walls are expensive, but they allow a large development to be built as a series of smaller buildings, each within the limits for its group and type.
Worked problem
A sloping site
Ingrid's site for an arts building slopes so that the lowest floor is fully buried at the north and fully exposed at the south. The grade plane is 6.5 feet below the ground floor; the lowest floor is 11 feet below the ground floor. Does the lowest floor count?
Show solution
- Find the code's reference level: the grade plane, the average of the finished ground at the exterior walls.
- Find the height of the lowest floor relative to it: the lowest floor is 11 − 6.5 = 4.5 feet below grade plane.
- Apply the rule: the lowest floor is below grade plane, but the floor above it is more than 6 feet above grade plane, so the lowest level counts as a story above grade plane if more than 6 feet of it is above grade plane, or if any part of it is more than 12 feet above the finished ground.
- Check the second rule for the lowest level: at the south side the finished ground is at the lowest floor, so the floor above is 11 feet above the ground there, and the lowest level itself is fully exposed.
- Conclude: at the south the lowest level is exposed for its full height; the code counts it as a story if more than 6 feet of its height is above grade plane, which a check of the section confirms.
Answer: The lowest level counts as a story above grade plane, adding one story to the building height.
Exercise 4: building area and height
- For your Design Studio IV project, determine the building height and area as the code defines them, with a section showing the reference level for grade.
- Find the table values that apply to your building and record how much of the allowable area and height you use.
- Show how your result would change without sprinklers.
- Redraw your site so that the building faces one more street or open space, and calculate the effect on the allowable area.
Self-check
- Have I measured building area and height using the code's definitions, not everyday ones?
- Have I checked mezzanines, penthouses and sloping ground?
- Have I left room for the design to grow?
Common mistakes
MistakeUsing the total floor area of all stories as the building area.
InsteadUse the code's definition: the area of each story, checked story by story, with a cap on the total.
MistakeCounting stories from the street rather than from the code's reference level.
InsteadEstablish the reference level for grade from the finished ground along every wall.
MistakeForgetting that a rooftop amenity room is a story.
InsteadCount any penthouse with a use other than equipment, stairs or elevators.
MistakeAssuming every building faces a street because it has an address.
InsteadCheck the code's conditions for access by fire department vehicles.
MistakeDesigning right at the limit at schematic design.
InsteadLeave a margin for growth, and check again at each design stage.
Summary and key terms
- Codes limit building size because larger and taller buildings let fires grow and are harder to evacuate and fight.
- The IBC sets limits in Tables 504.3, 504.4 and 506.2 by occupancy and construction type, with a frontage increase for buildings with open space around them.
- Building area and height must be measured by the code's definitions, which depend on grade, stories, mezzanines and penthouses.
- Sprinklers and access for firefighters allow much larger buildings.
- Fire walls divide a development into separate buildings for area and height.
- Building area
- The area of a building as defined by the code for checking size limits.
- Building height
- The height of a building as defined by the code, in stories and, in some codes, in feet.
- Grade
- The code's reference level for the ground around a building.
- Mezzanine
- An intermediate floor within a room, which may or may not count as a story.
- Firewall
- A rated wall with structural stability that divides a building into separate buildings for size limits.
Practice problems
Work each problem on paper first, then reveal the answer to check.
An R-2 building of Type V-A has four stories and 13,000 square feet per story with an NFPA 13R system and no frontage increase. Does it comply?
Show answer
No: the S13R allowable area is 12,000 square feet per story; it needs frontage, a fire wall, an NFPA 13 system or a smaller floor plate.
A building has a perimeter of 600 feet, of which 300 feet fronts on open space 30 feet wide. What is the frontage increase factor?
Show answer
If = (300/600 − 0.25) × 30/30 = 0.25.
With that factor, what is the allowable area per story for an A-3 Type V-A building with an NFPA 13 system and more than one story?
Show answer
Aa = 34,500 + 11,500 × 0.25 = 37,375 square feet.
What does a fire wall allow?
Show answer
It lets each side be treated as a separate building for allowable height and area.
A mezzanine covers one quarter of the room below it. Is it a story?
Show answer
No, if it meets the code's other conditions; mezzanines of not more than one third of the room's area are not counted.