ELEC-220 · Lesson 11 of 12 · 30 min

Commercial lighting, controls and energy codes

Lighting is the most visible part of a commercial electrical installation and, together with its controls, one of the largest. In two decades it has changed almost completely: fluorescent and high-intensity discharge lamps with magnetic ballasts have given way to LED luminaires with electronic drivers, and simple wall switches to occupancy sensors, daylight controls and networked lighting systems mandated by energy codes. This lesson covers lighting branch circuits and voltages, LED drivers and their electrical behaviour, dimming and control protocols, the energy code requirements for lighting power and controls, outdoor and sign lighting, and the practical work of installing, commissioning and troubleshooting modern lighting systems. Emergency lighting was covered in Lesson 9.

Lighting circuits and voltages

In Canadian commercial buildings, general lighting is usually supplied at 347 V, line to neutral from a 600Y/347 V system, which reduces current and voltage drop compared with 120 V and allows long branch circuits. Section 30 covers the installation of lighting equipment, including the voltages permitted for luminaires in different locations, wiring in and through luminaires, recessed luminaires near combustible materials and insulation, and luminaires in damp, wet and hazardous locations. Lighting at 347 V must not be installed in dwelling units, and luminaires within reach in some locations are restricted to lower voltages.

Lighting loads in offices, stores and warehouses are continuous (Lesson 1), so branch circuits are loaded to no more than 80% of the overcurrent device rating. Multiwire branch circuits sharing a neutral are common for lighting and need a means to disconnect all ungrounded conductors simultaneously (handle-tied or multipole breakers), and the shared neutral must be sized for harmonic currents from electronic drivers (Lesson 1 discussed neutral sizing).

LED luminaires and drivers

An LED luminaire contains LED arrays, which need a regulated DC current, and a driver, an electronic power supply that converts the AC supply to that current. The driver, not the LEDs, determines most of the luminaire's electrical behaviour:

  • Inrush current: when switched on, the driver's input capacitors charge, drawing a very brief current spike that can be tens of amperes per driver for a fraction of a millisecond. Many drivers switched together on one circuit can trip breakers or weld relay and switch contacts, so manufacturers specify the maximum number of drivers per breaker and controls are rated for LED inrush.
  • Power factor and harmonics: good drivers have a power factor above 0.9 and total harmonic distortion of input current below about 20%; cheap drivers can be much worse, increasing neutral current and transformer heating.
  • Operating voltage range: many commercial drivers accept 120 to 277 V; others are designed for 347 V or 480 V, and the voltage on the label must match the circuit.
  • Lifetime: LED luminaires are rated by L70 (hours until light output falls to 70% of initial), often 50,000 to 100,000 hours; drivers, especially their electrolytic capacitors, often fail first, particularly in hot locations.

Worked problem

Drivers per breaker

A driver manufacturer states that a 20 A breaker of type C curve can support 16 drivers switched simultaneously because of inrush, while each driver draws 0.35 A at 277 V in steady state. A warehouse row has 40 luminaires on 277 V. How many circuits are needed, considering both continuous load and inrush?

Show solution
  1. Continuous load limit: 80% of 20 A is 16 A; \(16/0.35 = 45\) drivers per circuit.
  2. Inrush limit: 16 drivers per circuit.
  3. Circuits: \(\lceil 40/16 \rceil = 3\).

Answer: Three circuits, set by inrush rather than steady-state current. Using breakers with a higher magnetic trip curve, staggered switching through the lighting control system, or drivers with inrush limiting could reduce this.

Dimming and control protocols

Most commercial LED drivers are dimmable, controlled by one of several methods:

Dimming and lighting control methods.
MethodHow it worksNotes
0-10 Va separate pair of low-voltage control wires carries a DC signal from 0 to 10 V that sets the light levelmost common in commercial work; control wiring is Class 2 or Class 1 depending on the installation; polarity matters
Phase dimming (forward or reverse)the dimmer chops part of the AC waveformcommon in residential and small retrofit work; compatibility between dimmer and driver is a frequent problem
DALIa digital two-wire bus addresses each driver individuallytwo-way communication, scenes, fault reporting; DALI-2 standardizes devices
Wireless and networked (Bluetooth mesh, Zigbee, proprietary)each luminaire has a radio and sensor nodereduces control wiring; supports luminaire-level sensing and data
Power over Ethernet lightingluminaires powered and controlled over Ethernet cabling (Lesson 10)integrates lighting with IT networks

Control wiring must be installed according to its classification. Class 2 0-10 V wiring may need separation from line-voltage conductors in the same luminaire or box unless the cable and devices are suitably rated, which manufacturers address with barriers or Class 1 rated control conductors. The polarity of 0-10 V wiring (violet and grey wires by common convention) must be correct, and long control runs may need shielded cable to avoid flicker from induced noise.

Lighting controls required by energy codes

Energy codes require controls that turn lights off or down when they are not needed. Typical requirements in current codes include:

  • Automatic shutoff: occupancy or vacancy sensors in offices, classrooms, conference rooms, washrooms and storage rooms, or time scheduling elsewhere, so that lights turn off when spaces are empty.
  • Partial-off or reduced levels: in warehouses, corridors, stairwells and parking garages, sensors reduce light output by at least about 50% when unoccupied.
  • Daylight responsive controls: in areas near windows and skylights (daylight zones), photosensors dim the lights in response to available daylight.
  • Local control and multilevel dimming in most spaces, so occupants can reduce light when full output is not needed.
  • Exterior lighting controls: automatic shutoff during daylight and reduction late at night.
  • Receptacle control in some codes: a portion of receptacles in offices automatically switched off when spaces are unoccupied, with marking.

In Canada, the National Energy Code of Canada for Buildings (NECB) and provincial energy codes (or ASHRAE 90.1 where permitted as an alternative) set lighting power limits and control requirements; some provinces, such as British Columbia and Ontario, adopt specific editions and step codes. The electrical inspector checks the electrical installation, while energy code compliance may be checked by the building official or through design documentation.

Lighting power density

Energy codes also limit the installed lighting power, expressed as lighting power density (LPD) in W/m² (or W/ft²) for the building type or for each space type. Modern LED designs typically achieve 4 to 8 W/m² in offices, well below the code limits.

Worked problem

Checking lighting power density

An open office of 600 m² has 96 LED troffers of 30 W each and 12 downlights of 12 W. If the energy code allows 8.5 W/m² for open offices, does the design comply, and what is the installed LPD?

Show solution
  1. Installed power: \(96 \times 30 + 12 \times 12 = 2{,}880 + 144 = 3{,}024\) W.
  2. LPD: \(3{,}024/600 = 5.0\) W/m².

Answer: About 5.0 W/m², well within 8.5 W/m². With occupancy and daylight controls, actual energy use is typically 30 to 60% below what the installed power running full time would use.

Worked problem

Savings from controls

A 3 kW office lighting system operates 3,000 hours a year without controls. Occupancy sensors reduce operating hours by 30%, and daylight dimming reduces the remaining energy by 20% in the daylight zone, which contains 40% of the luminaires. Estimate annual savings.

Show solution
  1. Baseline: \(3 \times 3{,}000 = 9{,}000\) kWh.
  2. After occupancy control: \(9{,}000 \times 0.7 = 6{,}300\) kWh.
  3. Daylight savings: \(6{,}300 \times 0.4 \times 0.2 = 504\) kWh; result 5,796 kWh.

Answer: About 3,200 kWh saved, 36% of the baseline. At $0.12/kWh that is about $385 a year for this space, and controls also extend luminaire life. The value depends heavily on correct sensor placement, time-out settings and commissioning.

Installing and commissioning lighting controls

Many lighting complaints come from controls that were installed but not commissioned: sensors with default settings that turn lights off on people sitting quietly at desks, daylight sensors that dim too much or flicker, and schedules that do not match the building's hours. Good practice:

  • Choose the right sensor technology: passive infrared (PIR) needs line of sight and detects movement; ultrasonic and microwave sensors detect smaller movements and see around obstacles but can be triggered by air movement; dual-technology sensors combine them.
  • Place sensors according to manufacturer coverage patterns, away from HVAC diffusers and doorways where people walk past.
  • Set time delays appropriately, often 15 to 20 minutes in offices, shorter in washrooms and storage, within the maximum allowed by the energy code.
  • Calibrate daylight sensors with the space furnished and at representative times, setting the target light level and dimming limits.
  • Program schedules, overrides and integration with the building automation system, and train the owner's staff.
  • Document settings and provide control drawings, because networked systems with hundreds of devices are difficult to troubleshoot without records.

Outdoor and site lighting

Parking lot and site lighting brings its own issues: long circuits with significant voltage drop, poles that must be bonded and installed on engineered bases, hand holes and junction boxes exposed to water, and luminaires exposed to lightning and surges (surge protective devices in the driver or at the pole are common). Pole wiring needs fusing at each pole in many designs, and pole hand holes must be bonded and covered. Lighting near property lines and sky must comply with local bylaws on light trespass and glare, often using full-cutoff luminaires and lower colour temperatures (3,000 K or less) to reduce sky glow and effects on wildlife, as dark-sky guidelines recommend.

Worked problem

Voltage drop on a parking lot circuit

Eight 150 W LED pole luminaires at 347 V are spaced 40 m apart along a single circuit starting 30 m from the panel, in 8 AWG copper (about 2.1 Ω/km). Estimate the voltage drop to the last pole using the lumped-load method (all load at the end).

Show solution
  1. Current: \(8 \times 150/347 = 3.46\) A (assuming power factor near 1).
  2. Length to last pole: \(30 + 7 \times 40 = 310\) m; loop resistance \(2 \times 0.310 \times 2.1 = 1.30\) Ω.
  3. Drop: \(3.46 \times 1.30 = 4.5\) V, 1.3% of 347 V.

Answer: About 1.3% even with the conservative lumped-load method, comfortably within the usual 3% branch circuit guideline; the real drop, with loads distributed, is about half. The higher voltage is what makes long site lighting circuits practical.

Signs and outline lighting

Electric signs and outline lighting have specific rules: each sign must have a disconnecting means within sight of the sign or lockable, signs and their power supplies must be certified, branch circuits supplying signs in commercial buildings with entrances accessible to pedestrians are often required by the code to be provided at each entrance, and LED sign power supplies and their secondary wiring have their own installation rules.

CEC Section 34 covers electric signs and outline lighting, including disconnecting means, enclosures, wiring of neon and LED sign systems and bonding.

Common mistakes

  • MistakeLoading lighting circuits by steady-state current only.

    InsteadCheck driver inrush limits per breaker and the rating of switches and relays.

  • MistakeReversing or mixing 0-10 V control wiring with line voltage.

    InsteadObserve polarity and classification and separate as required.

  • MistakeLeaving occupancy and daylight sensors at factory settings.

    InsteadCommission sensors, time delays and daylight setpoints in the finished space.

  • MistakeInstalling a 120-277 V driver on a 347 V circuit.

    InsteadMatch the driver voltage rating to the circuit.

  • MistakeIgnoring light trespass and colour temperature in site lighting.

    InsteadUse full-cutoff luminaires and warm colour temperatures to meet bylaws and dark-sky goals.

Summary and key terms

  • Commercial lighting usually runs at 347 V in Canada, as continuous load, under Section 30 rules.
  • LED drivers determine inrush, power factor, harmonics, voltage range and often lifetime.
  • Dimming uses 0-10 V, phase control, DALI, wireless or PoE; control wiring must be classified and separated properly.
  • Energy codes require automatic shutoff, partial-off, daylight, multilevel and exterior controls, and limit lighting power density.
  • Controls save 30 to 60% of lighting energy only when correctly placed and commissioned.
  • Site lighting needs voltage drop checks, bonding, surge protection and dark-sky design.
  • Signs need certified equipment, disconnects and the outlets required by the code.
Driver
The electronic power supply that powers LED arrays.
Inrush current
A brief high current when a driver is switched on.
L70
Hours until an LED luminaire's output falls to 70% of initial.
0-10 V dimming
Analog dimming control using a 0 to 10 V DC signal.
DALI
Digital Addressable Lighting Interface, a digital lighting control bus.
Occupancy sensor
A sensor that turns lights on and off automatically by detecting people.
Vacancy sensor
A sensor that turns lights off automatically but requires manual on.
Daylight harvesting
Dimming electric light in response to available daylight.
Lighting power density
Installed lighting power per unit floor area.
Full-cutoff luminaire
A luminaire emitting no light above the horizontal.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. Why is commercial lighting run at 347 V or 277 V?

    Show answer

    Lower current and voltage drop than 120 V.

  2. Maximum continuous load on a 20 A lighting circuit?

    Show answer

    16 A.

  3. What causes LED driver inrush current?

    Show answer

    Charging of the driver's input capacitors.

  4. Circuits for 50 drivers with a limit of 12 per breaker?

    Show answer

    5.

  5. How does 0-10 V dimming work?

    Show answer

    A low-voltage DC control signal sets the light level.

  6. What does DALI add over 0-10 V?

    Show answer

    Individual addressing and two-way communication.

  7. LPD of 2,400 W in 400 m²?

    Show answer

    6 W/m².

  8. Typical office occupancy sensor time delay?

    Show answer

    15 to 20 minutes.

  9. Name two features of dark-sky friendly site lighting.

    Show answer

    Full-cutoff luminaires and warm colour temperatures.

  10. What must every sign have nearby?

    Show answer

    A disconnecting means within sight or a lockable disconnect.

Lesson quiz · 5 questions