LVT-130 · Lesson 10 of 12 · 20 min

Certification testing of permanent links and channels

Certification is the test that turns an installation into a deliverable. Every one of the sixth floor's 348 links must be tested with a certification tester against the Category 6A permanent link limits of TIA-568.2, and every result must be saved, reviewed and submitted to the manufacturer for the 25-year system warranty and to Brightwater as part of the records. A link that has not been certified, as far as the owner and the manufacturer are concerned, has not been installed. This lesson covers the tester, its setup, the test configurations, the parameters it measures and how to read its verdicts.

The certification tester

A certification tester is a pair of handheld units, a main unit and a smart remote, each with interchangeable adapters. The two units take turns sending and measuring, so that every parameter is measured from both ends of the link. The tester sweeps a range of frequencies, up to 500 MHz for Category 6A, and compares each measured value at each frequency with the limit line in the selected standard. A complete Category 6A autotest takes well under a minute per link with current testers.

Testers are themselves tested. TIA-1152-A sets accuracy levels for field testers: Level IIe for Category 5e, Level III for Category 6, Level IIIe for Category 6A and Level 2G for Category 8. A tester used for Category 6A certification must meet at least Level IIIe, and most current testers, such as the Fluke Networks DSX series or the Viavi Certifier series, meet the highest level and test to 2,000 MHz. Every tester must also be within its calibration period, usually one year, with a calibration certificate that the submittals include. Results from an out-of-calibration tester are not accepted.

Setting up the tester

Most failed test campaigns go wrong in the first five minutes of each day, at setup. Before the first test on the sixth floor, Maya's routine is the same every morning.

  • Check the battery and that the main and remote units have the same firmware and limit database versions.
  • Fit the permanent link adapters to both units, and check the adapters' plug ends and cords for damage.
  • Set the reference: connect the two units together as the manufacturer describes and run the set-reference routine, which removes the adapters' own effects from later results. Repeat it whenever the adapters are changed, and at least daily.
  • Select the test limit: TIA Category 6A Permanent Link, or the specific configuration for links that differ, such as an MPTL.
  • Select the cable type, so the tester uses the correct NVP for length.
  • Set the project, the operator name and the identifier sequence, so that each saved result gets the right identifier automatically.

The identifier sequence matters as much as the limit. Testers can step through a list of identifiers, 6A-A01, 6A-A02 and so on, saving each result under the next one. If the list is loaded and the crew tests in order, each saved result carries the right identifier without anyone typing. If the crew tests out of order or skips a link, the results and the identifiers drift apart. Lesson 12 shows how Maya cross-checks them before submitting.

The permanent link test measures the installed cable and its two end connections, the panel jack and the outlet jack, and excludes the cords that will later be added. To do that, the tester uses permanent link adapters: short, high-quality test cords with plugs designed and characterized so that the tester can remove their effect, leaving the measurement of the link alone. The plug at the end of each adapter mates with the link's jack, and the connection between them is included in the measurement, as it should be, because the jack is part of the link.

The channel test measures everything between the two pieces of network equipment: the equipment cord, the panel, the horizontal cable, any consolidation point, the outlet and the work area cord. The tester uses channel adapters, which accept the plugs of the actual cords; the final connections at the equipment are not part of the channel, so the adapter's jack is excluded. Channel limits are slightly looser than permanent link limits, because the channel includes more cable and more connections.

Permanent link testing is the norm for new installations, because cords change and the permanent link does not. Certifying a channel certifies particular cords, and when those cords are replaced, the result no longer describes the system. Brightwater's specification calls for permanent link testing of every link and a sample of 5 percent of channels with the project's cords in place, which is common in specifications that include the cords in the warranty.

Two diagrams one above the other. The upper, marked permanent link test, shows a tester main unit at the left with a permanent link adapter cord plugged into a patch panel jack, horizontal cable through a consolidation point to an outlet jack, and a remote unit at the right with its own permanent link adapter plugged into the outlet. A bracket labeled measured runs from the plug-jack connection at the panel to the plug-jack connection at the outlet. The lower, marked channel test, shows the same link with an equipment cord and a work area cord in place, and channel adapters on the tester and remote that accept the cords' plugs. Its bracket covers both cords and everything between them, but not the adapter jacks.
Permanent link and channel tests. Permanent link adapters measure jack to jack; channel adapters include the cords.

Links through a consolidation point, like the desk links through the sixth floor's zone boxes, are tested as permanent links that include the consolidation point: the tester's main unit at the panel, the remote at the desk outlet, and the zone box connectors in between. The MPTLs for the cameras use a different setup: a permanent link adapter at the panel, and at the camera end an adapter that accepts the link's plug, often a channel adapter or a dedicated MPTL adapter, as the tester maker's MPTL procedure describes. Dev's review in LVT-120 asked for that adapter to be named in the test plan, and it is.

What the tester measures

A Category 6A autotest measures the parameters that TIA-568.2 sets limits for, at each end of the link, and summarizes each as a margin: how far the worst measured value is from its limit.

The main parameters of a Category 6A autotest.
ParameterWhat it measuresTypical cause of a failure
WiremapEach conductor reaches the right far-end contactTermination errors, damage
LengthElectrical length of each pairRoute longer than planned, wrong NVP
Insertion lossSignal lost along the linkToo long, warm ceiling, damaged cable
NEXT and PSNEXTCrosstalk from one pair into others at the same endUntwist, poor termination, wrong components
ACRF and PSACRFFar-end crosstalk relative to the received signalMismatched components, damaged cable
Return lossSignal reflected back by impedance changesKinks, tight ties, bad terminations, mixed cables
Propagation delayTime for a signal to travel the linkExcess length
Delay skewSpread in delay between the four pairsMixed cable types, damaged pairs
DC resistance and unbalanceResistance of each conductor and difference within a pairPoor contact, important for PoE

Insertion loss and NEXT are the two that installers think about most. Insertion loss rises with length and frequency, so a long link has less margin than a short one. NEXT, which is measured close to the tester, depends mostly on the terminations near each end. That gives a useful pattern: long links tend to fail insertion loss, short links tend to fail NEXT, because on a short link the far-end termination is close enough to add its crosstalk to the near-end measurement. Return loss can fail at any length, and its graph usually shows where along the link the problem is, which lesson 11 uses.

For each parameter the tester reports a margin in decibels. A positive margin means the link performs better than the limit by that amount; a negative margin means it fails. The tester also reports the frequency where the margin is smallest, the worst case, and for NEXT, which end it occurred at.

PASS, FAIL and the asterisk

Every measurement has some uncertainty, set by the tester's accuracy level. When a result is closer to the limit than the tester's accuracy, the tester marks it with an asterisk: PASS* means the measured value passed, but by less than the tester can be sure of; FAIL* means it failed, by less than the tester can be sure of. The overall result for the link is the worst of its parameters. Most specifications and warranty programs treat PASS* as a pass and FAIL* as a fail, but some project specifications reject PASS* results or require them to be reported separately, so the specification has to be checked. Brightwater's accepts PASS* but requires a list of them, which Maya prepares.

The code below shows the logic on three links from panel B and panel F, using illustrative limit lines with the general shape of the real ones and an illustrative accuracy band. The tester holds the real limits; the point here is how the margin and the verdict are worked out.

import math
FREQS = [1, 10, 100, 250, 400, 500]                                   # MHz
def il_limit(f):   return 1.65 * math.sqrt(f) + 0.01 * f               # illustrative limit line, dB
def next_limit(f): return min(65.0, 42.0 - 20 * math.log10(f / 100))   # illustrative limit line, dB
ACCURACY = 0.6     # a result closer to the limit than this is marked with an asterisk

def verdict(margin):
    if margin >= ACCURACY:
        return "PASS"
    if margin >= 0:
        return "PASS*"
    return "FAIL*" if margin > -ACCURACY else "FAIL"

# measured insertion loss as a fraction of the limit, and NEXT above the limit at each frequency
links = {
    "6A-B37": (0.62, [8.0, 7.0, 6.5, 5.2, 5.8, 4.9]),
    "6A-B48": (0.70, [3.0, 2.1, 1.5, 0.9, 0.4, 0.7]),
    "6A-F12": (0.27, [5.0, 3.0, 1.2, -0.3, -1.4, -0.9]),
}
for link, (frac, headroom) in links.items():
    il_margin = il_limit(500) * (1 - frac)      # margin at the top frequency
    k = min(range(len(FREQS)), key=lambda i: headroom[i])
    next_margin = headroom[k]
    worst = min(il_margin, next_margin)
    print(f"{link}: IL margin {il_margin:4.1f} dB at 500 MHz, worst NEXT margin {next_margin:4.1f} dB "
          f"at {FREQS[k]} MHz -> {verdict(worst)}")
Output
6A-B37: IL margin 15.9 dB at 500 MHz, worst NEXT margin  4.9 dB at 500 MHz -> PASS
6A-B48: IL margin 12.6 dB at 500 MHz, worst NEXT margin  0.4 dB at 400 MHz -> PASS*
6A-F12: IL margin 30.6 dB at 500 MHz, worst NEXT margin -1.4 dB at 400 MHz -> FAIL

Link 6A-B37, a long desk link in zone Z4, passes comfortably. Link 6A-B48, the longest on the floor at 220 ft, has plenty of insertion loss margin but only 0.4 dB of NEXT margin at 400 MHz, within the accuracy band, so it is a PASS*. Link 6A-F12, a short meeting room link of about 79 ft, fails NEXT around 250 to 500 MHz even though its insertion loss is excellent: the classic short-link pattern, and a sign of a termination problem at one end. Lesson 11 follows Maya as she finds it.

A graph with frequency from 1 to 500 MHz on the horizontal axis and decibels on the vertical axis. A red limit line for NEXT falls from upper left to lower right. Above it, a blue measured NEXT curve with small ripples stays above the limit across the range; the smallest gap between the curves is marked at about 400 MHz as the worst-case margin. A shaded band just above and below the limit line is marked as the tester's accuracy band, with a note that a result falling inside the band is marked with an asterisk.
Reading a NEXT result. Margin is the gap between the measured curve and the limit at its smallest point; a result inside the accuracy band is marked with an asterisk.

Saving and reviewing results

Every test is saved, pass or fail, under its identifier. Failed links are fixed and retested, and the passing result is saved under the same identifier, replacing or superseding the failure according to the tester software's rules. At the end of each day, Maya downloads the tester into the manufacturer's management software, where Dev reviews the day's results: any failures not yet fixed, any PASS* results, any links with suspicious lengths, and any identifiers missing or duplicated.

The final submission is the native test file from the tester's software, not a spreadsheet or a printed summary, because the manufacturer's warranty team checks the raw data: the limit used, the adapter type, the tester's calibration date and the full graphs. A submission with the wrong limit selected, for example Category 6 instead of Category 6A, or channel instead of permanent link, is rejected and the links must be retested.

Worked problem

Choosing the right limit for an MPTL

The six camera links end in field-terminated plugs. Renée starts testing them with the standard permanent link setup, with a permanent link adapter on the remote, and finds that the remote's adapter has a plug, not a jack. What should the setup be?

Show solution
  1. An MPTL ends in a plug, so the remote needs an adapter that accepts a plug: a channel adapter or the tester maker's MPTL adapter.
  2. The main unit at the panel keeps its permanent link adapter, because the panel end is a jack.
  3. The limit is the TIA Category 6A MPTL limit, so that the plug connection at the camera end is included in the measured link.
  4. The test plan names the adapters and the limit, so Renée sets up the tester as listed and retests the six links.

Answer: Use a permanent link adapter at the panel, a plug-accepting adapter at the device end and the MPTL limit.

Common mistakes

  • MistakeStarting tests without setting the reference.

    InsteadSet the reference daily and whenever adapters change.

  • MistakeTesting with a tester whose calibration has expired.

    InsteadCheck the calibration date before the job; results are rejected otherwise.

  • MistakeSelecting the channel limit with permanent link adapters.

    InsteadMatch the limit to the configuration and adapters.

  • MistakeTreating PASS* as a pass on every project.

    InsteadCheck how the specification and warranty treat marginal results.

  • MistakeSubmitting a spreadsheet of results.

    InsteadSubmit the native test files from the tester software.

Summary and key terms

  • Certification measures every TIA-568.2 parameter across the category's frequency range from both ends.
  • Category 6A requires a tester of at least TIA-1152-A Level IIIe, within its calibration period.
  • Daily setup includes adapters, reference, limit, cable type and the identifier sequence.
  • Permanent link tests measure jack to jack; channel tests include the cords; MPTLs use a plug-accepting adapter at the device end.
  • Long links tend to fail insertion loss, short links NEXT; return loss can fail anywhere.
  • Margin is the distance from the limit; asterisks mark results within the tester's accuracy.
  • Every result is saved under its identifier and submitted in the tester's native format.
Certification tester
A field tester that measures link performance against standard limits across the full frequency range.
Permanent link adapter
A characterized test cord whose effect the tester removes, so that only the link is measured.
Channel adapter
An adapter that accepts the plug of the channel's own cord.
Set reference
A routine that removes the adapters' effect before testing.
Margin
The difference between a measured value and its limit, positive when passing.
PASS* / FAIL*
Results within the tester's accuracy band of the limit.
Insertion loss
The loss of signal strength along a link.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What accuracy level must a tester meet for Category 6A certification?

    Show answer

    At least TIA-1152-A Level IIIe.

  2. A link shows NEXT margin of −0.3 dB with an accuracy band of 0.6 dB. What is the result?

    Show answer

    FAIL*.

  3. Why are new installations normally tested as permanent links?

    Show answer

    Cords change over time; the permanent link does not.

  4. A short link fails NEXT but has large insertion loss margin. Where should the search start?

    Show answer

    At the terminations at each end.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz