GAS-120 · Lesson 8 of 12 · 20 min

Air supply for combustion and ventilation

▶ Video coming soon A video version of this lesson is on the way.

The service call came in from a landlord on Sanford Avenue: the tenants had finished the basement and now the water heater pilot kept going out. Rosa and Jonah found a natural draft furnace and a natural draft water heater in a small utility room, newly framed and drywalled, with a tight-fitting door. The water heater's draft hood spilled when Rosa held a smoke pencil to it with the door closed, and drew properly with the door open. "There's your answer," she said. "They built a nice room and took away the air." On the drive back, she had Jonah work out what the code required for the room, using the tape measurements and the two rating plates.

Air supply was introduced in earlier training as part of combustion and building pressure. This lesson concentrates on reading the code's air supply section: the kinds of air the code is concerned with, how it decides whether a space has enough air, the methods for bringing air in from other rooms or from outdoors, and the details of openings, louvres and ducts that inspectors check.

Three jobs for the air

The code calls the air an appliance needs by several names, depending on what it does. Combustion air supplies the oxygen the burner needs; without enough, combustion becomes incomplete and produces carbon monoxide. Dilution air enters a draft hood or barometric damper and mixes with the flue gases, steadying the draft. Ventilation air carries away the heat of the appliance and its casing from the room, keeping the space and the controls at a safe temperature. B149.1 groups these under the heading of air supply and sets separate requirements for combustion and ventilation air.

A direct-vent appliance takes all its combustion air from outdoors through its own sealed pipe and needs no combustion air from the room, although the room may still need ventilation as the instructions say. Most of the rules in this lesson apply to room-air appliances: natural draft and fan-assisted appliances that take their combustion air from the space around them. The more of these there are in a space, and the tighter the building, the more care the air supply needs.

How B149.1 approaches air supply

B149.1 sets out air supply requirements in its venting and air supply section, and they depend on several things at once: the total input of the appliances in the space, whether the appliances have draft control devices such as draft hoods or barometric dampers, whether the appliances are in an enclosure or an open area of the building, and how airtight the building is. Separate clauses cover smaller residential installations and larger installations, and the code provides tables that give the required free area of the openings for given inputs and appliance types. The current Ontario CAD amends some of these clauses, including an exception for direct-vent appliances and the separation of dryer exhaust from air supply openings. When sizing an air supply, identify which clause applies to the building and the appliance types, then use the table for that case.

Whatever the table says, three questions decide most jobs. Is the appliance in an enclosure, such as a furnace room or closet, or in a large open area? Does the building have normal air leakage, or is it built tight, as most new and renovated houses are? And are there exhaust appliances, such as range hoods, dryers, bath fans and fireplaces, that can pull air out of the building faster than the openings let it in? The code treats tight buildings and enclosures more strictly, and exhaust appliances may require make-up air, as Luis found at Marigold Kitchen.

A cross-section of a furnace room with two openings to an adjoining space. The upper opening is within 300 mm of the ceiling and the lower opening within 300 mm of the floor. Arrows show cooler air entering low and warm air leaving high. A second panel shows the same room with two ducts to outdoors, one ending near the top of the room and one near the bottom, with screens at the outdoor ends. Notes: louvres fixed open; motorized dampers interlocked with the appliance; free area from the louvre maker or an assumed value.
Two-opening air supply, from an adjoining space or from outdoors. Sizes come from the adopted code for the appliance types and input.

Bringing in outdoor air

Where indoor air is not enough, or the code requires it for the type of building, air supply comes from outdoors, through openings in an outside wall or through ducts. The code specifies how many openings are needed, where they go, and the free area they must have, which depends on the input, the appliance types and the route the air takes. A typical arrangement uses one opening or duct ending near the top of the room and one near the bottom, so that warm air leaves high and cool air enters low. Some arrangements allow a single opening near the top. The code also allows mechanical air supply, using a fan, provided the appliances are interlocked so they cannot run unless the fan is proving airflow.

Outdoor air openings must not draw from places where the air may be contaminated or hazardous, such as garages, refrigeration machinery rooms or spaces with flammable vapours. They must be located so that they will not be blocked by snow, landscaping or stored goods, and so that cold air entering them does not freeze water pipes or condensate lines nearby. Many installers place the lower duct so that it discharges into a trap or a bucket-shaped bend near the floor, which slows the cold air and keeps it from blowing directly at the appliance.

Free area, louvres and ducts

Every opening size in the code is a free area: the actual open area through which air can pass, not the outside dimensions of the grille. A louvre or grille blocks part of its opening with blades and frame, and a screen blocks more. The louvre manufacturer states the free area. If it does not, the code lets you assume a value: B149.1 and the louvre maker's data set this. Screens on outdoor openings must have a mesh no finer than the code allows, about 6 mm, because a fine screen clogs with lint and insects.

Louvres and grilles must be fixed in the open position, unless they are motorized and interlocked so that the appliances cannot operate unless the dampers are open. Ducts carrying combustion air must have at least the same free area as the openings they serve, must not be smaller at any point, and must not serve any other purpose. A combustion air duct must never be connected to a return air plenum, where the furnace blower would pull on it.

Worked problem

Air for the Sanford Avenue utility room

The utility room is 2.4 m by 3.0 m with a ceiling height of 2.3 m. The furnace is 26 kW and the water heater 12 kW, both natural draft. The finished basement outside the room is a large open area. Suppose the code clause that applies calls for two openings to the basement, each with a free area of 250 cm². Rosa plans to use metal grilles whose maker states a free area of 60 in 100. What gross grille size is needed, and does a 20 cm by 25 cm grille work?

Show solution
  1. Find the room volume and total input, the two numbers the code needs:
  2. \[2.4 \times 3.0 \times 2.3 \approx 16.6 \text{ m}^3 \qquad 26 + 12 = 38 \text{ kW}\]
  3. Convert the required free area to a gross grille area:
  4. \[\frac{250}{0.60} \approx 417 \text{ cm}^2\]
  5. Check the proposed grille:
  6. \[20 \times 25 = 500 \text{ cm}^2 \ge 417 \text{ cm}^2\]
  7. Place the openings:
  8. One grille within 300 mm of the ceiling and one within 300 mm of the floor, or in the door at those heights.

Answer: Two 20 by 25 cm grilles, one high and one low, give the room the free area this clause requires. Rosa also checks that the basement itself has enough air under the code, and that no exhaust fan in the basement can depressurize it. The landlord has the grilles installed in the door, and the water heater draws properly with the door closed.

Exhaust fans and tight buildings

An air supply that meets the code on paper can still fail if exhaust equipment pulls air out of the building. Range hoods, clothes dryers, bathroom fans, central vacuum systems, fireplaces and some ventilation systems all remove air. When they run, the building's pressure drops below outdoor pressure, and a natural draft appliance's vent may reverse. The code requires that the operation of exhaust fans, ventilation systems and other air-handling equipment not interfere with the proper operation of appliances, and the Ontario Building Code's ventilation rules address make-up air for exhaust devices in houses. A spillage test with all exhaust equipment running, as you practised in an earlier course, is the practical check.

Air supply is also a maintenance item. Openings get blocked by boxes, sealed by renovators, filled with lint or covered by snow. When you service a room-air appliance, check that its air openings are still there, still open and still clear. Report blocked or missing openings to the owner in writing and, if the appliance is spilling or producing carbon monoxide, follow the unsafe-condition procedure.

Air supply details inspectors check
DetailWhat to check
Opening locationWithin the specified distance of the top and bottom of the space; not from a garage or hazardous area
Free areaNet open area after blades and screens; from the maker or the code's assumed value
ScreensMesh no finer than the code allows; clean
Louvres and dampersFixed open, or motorized and interlocked with the appliances
DuctsSame free area as the opening, no reductions, not connected to return air, serving no other purpose
Exhaust equipmentCannot depressurize the space enough to cause spillage; make-up air where required

Mechanical air supply and interlocks

Where openings would be impractical, such as in a large boiler room deep inside a building, the code allows air to be supplied by a fan. A mechanical air supply must deliver at least the airflow the code requires for the total input, and the appliances must be interlocked so that they cannot fire unless the fan is running and proving airflow, usually through a pressure or airflow switch. If the fan fails, the burners shut down. The interlock must be tested at start-up and at each service, by stopping the fan and confirming that the appliances will not fire.

Similar interlocks apply to motorized dampers in combustion air openings and to some exhaust systems. In commercial kitchens, the gas supply to the cooking line is often interlocked with the hood exhaust and make-up air fans, so that the appliances cannot be used unless the ventilation is running, as Luis found when he traced the carbon monoxide problem at Marigold Kitchen to a make-up air unit that had been switched off.

Common field problems

Most air supply problems in the field are not design errors but later changes. Renovators drywall over a grille, finish a basement and close the furnace room door, or replace old leaky windows and doors, making the house tighter. Owners stack boxes against a louvre, cover an outdoor opening because it lets in cold air, or install a large range hood or a second dryer. Each of these can turn a code-compliant air supply into one that fails.

When you service a room-air appliance, compare what you see with what the code requires, not with what was there before. If the appliance is spilling, producing carbon monoxide or showing scorch marks at the draft hood, treat it as an unsafe condition. If it is working but the air supply no longer meets the code, record it, explain it to the owner in plain language, and recommend the fix. Replacing natural draft appliances with direct-vent models often solves the problem permanently.

Write down what you found and what you told the owner. If the same house calls again next winter, the next technician will know where to look first, and the record shows that the hazard was reported.

Common mistakes

  • MistakeMeasuring a grille by its outside size.

    InsteadUse the free area, from the maker's data or the code's assumed value.

  • MistakeTaking combustion air from a garage.

    InsteadDraw air only from spaces the code permits, never from hazardous locations.

  • MistakeInstalling a manual damper in a combustion air duct.

    InsteadLouvres and dampers must be fixed open, or motorized and interlocked.

  • MistakeCounting a closed bedroom's volume toward the indoor air.

    InsteadCount only spaces connected by openings that meet the code.

  • MistakeIgnoring the range hood.

    InsteadCheck for depressurization with all exhaust equipment running.

Summary and key terms

  • Appliances need combustion, dilution and ventilation air.
  • Direct-vent appliances take combustion air from outdoors through a sealed system.
  • B149.1 sizes air supply by total input, appliance type, enclosure and building airtightness, using its clauses and tables, with Ontario amendments. Rooms may be combined, or air brought from outdoors, through openings near the top and bottom of the space.
  • Outdoor openings and ducts are sized from the code for the input and appliance type. Opening sizes are free areas.
  • Louvres must be fixed open or interlocked, ducts must not shrink, and air must not come from hazardous spaces.
  • Exhaust equipment must not depressurize the space.
Combustion air
Air that supplies oxygen to the burner.
Dilution air
Air that enters a draft hood or barometric damper and mixes with flue gases.
Ventilation air
Air that carries heat away from the appliance and the space.
Free area
The net open area of an opening after louvres, bars and screens.
Make-up air
Outdoor air supplied to replace air removed by exhaust equipment.
Room-air appliance
An appliance that takes its combustion air from the space around it.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What are the three kinds of air an appliance with a draft hood needs?

    Show answer

    Combustion air, dilution air and ventilation air.

  2. Why are air openings placed near the top and bottom of a room?

    Show answer

    Warm air leaves high and cool air enters low, creating circulation.

  3. What is free area?

    Show answer

    The net open area of an opening after the louvre blades and screens.

  4. May a combustion air duct connect to a return air plenum?

    Show answer

    No. The blower would pull on it and could depressurize the space.

  5. What practical test checks that exhaust fans do not upset a natural draft appliance?

    Show answer

    A spillage test with all exhaust equipment running and doors set to the worst case.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz