GAS-240 · Lesson 2 of 12 · 23 min

Cylinders: types, markings and requalification

▶ Video coming soon A video version of this lesson is on the way.

On Friday afternoon, September 25, Priya Nair handed Luis a clipboard and a can of marking paint and sent him and Jonah to the cylinder cage behind Bayline's shop. Every fall, before the construction heating season, the propane crew checks every cylinder the company owns: the 20 lb cylinders for the torches and the barbecue demonstration, the 33 lb forklift cylinder for the shop's lift truck, and a row of 100 lb cylinders that supply the temporary heaters on new-house sites. Beside them stood four older 100 lb cylinders the farm customer outside Grove City had retired when her new tank went in, which the supplier had asked Bayline to hold for pickup. "Every cylinder tells you its life story on its collar," Luis said, handing Jonah a wire brush. "Read it before you fill it, carry it or connect it. If you can't read it, it doesn't get used."

This lesson explains the kinds of propane cylinders, the markings stamped on them, the valves they carry, how long they may be used before they must be requalified, and how they are stored, carried and connected. Filling them is covered in lesson 7.

Cylinders and tanks: the difference

NFPA 58 and the federal rules divide propane containers into two families. A cylinder is a portable container built to a U.S. Department of Transportation specification, sold by the weight of propane it holds and filled at a dispensing station, by weight or by volume, or exchanged for a full one. A tank is a stationary container built to the ASME pressure vessel code and filled on site from a delivery truck. Cylinders are designed to be moved full; tanks are not. The distinction matters because the rules for building, marking, requalifying, filling, storing and locating the two are different.

The common cylinder types

Cylinders come in a handful of standard sizes, each named by the propane it holds when properly filled. The 20 lb barbecue cylinder is a vertical vapor-withdrawal cylinder with a collar to protect the valve and a foot ring to stand on. Smaller sizes, from about 4 lb to 30 lb, serve camping stoves, patio heaters and torches. The 100 lb cylinder, about 4 ft tall, is common on farms, at cottages and on construction sites, and two or more are often connected through a manifold with an automatic changeover regulator. Forklift cylinders, usually 33 lb, are horizontal and draw liquid from the bottom, because a forklift engine vaporizes the fuel itself, as lesson 10 explains. A locating pin or slot on the collar ensures the cylinder is mounted so that its withdrawal tube points down into the liquid and its relief valve discharges into the vapor space.

Most propane cylinders are steel, made in two pieces welded together or drawn from one piece. Aluminum cylinders are lighter and common for forklifts. Composite cylinders, made of a plastic liner wrapped in fiber, are translucent so the liquid level can be seen, and they have a shorter, fixed service life set by their specification. Single-use 1 lb cylinders for camping and plumbing torches are not refillable and must never be refilled.

Common propane cylinders.
CylinderTypical useWithdrawalNotes
4 to 30 lbCamping, patio heaters, torchesVaporMust have an overfilling prevention device
20 lbBarbecues, torches, small heatersVaporMost common exchange cylinder
33 lbForklifts and floor machinesLiquidHorizontal, with locating pin; mounted as marked
100 lbFarms, cottages, construction heatVaporOften manifolded in pairs with a changeover regulator
1 lbCamping, hand torchesVaporSingle use; never refilled
Four cylinder outlines drawn side by side. A small barbecue cylinder with a protective collar, a foot ring and a valve with a triangular handwheel; a liquid line inside is absent and a short tube ends in the vapor space. A tall 100 pound cylinder with a collar and a vapor valve. A horizontal forklift cylinder lying on its side, with a liquid withdrawal tube reaching down into the liquid, a locating pin on the collar and a relief valve on top in the vapor space. A small disposable cylinder marked do not refill.
Vapor-withdrawal and liquid-withdrawal cylinders. The forklift cylinder must be mounted so that its relief valve stays in the vapor space.

Reading the collar

Every cylinder has permanent markings stamped into its collar or a plate, and they must stay legible. The specification shows the standard it was built to, such as DOT-4BA240 or DOT-4BW240, in which 240 is the service pressure in psig. The manufacturer's mark and serial number identify it. The water capacity (WC) is how much water it would hold, in pounds, and the tare weight (TW) is the weight of the empty cylinder with its valve, in pounds. The date of manufacture, month and year, starts the clock for requalification. Each requalification adds a mark showing the month, the requalifier's identification number (RIN) issued by the Pipeline and Hazardous Materials Safety Administration, the year and, for an external visual inspection, the letter E. A cylinder that has been requalified several times carries several marks; the latest one counts.

A drawing of a cylinder collar unrolled into a strip, with its stamped markings labeled. From left: the specification DOT-4BW240, the manufacturer's symbol and serial number, the water capacity WC 47.6 pounds, the tare weight TW 17.0 pounds, the manufacture date 04 14 for April 2014, and a requalification mark reading 05 A123 26 E. Callouts explain each one and note that an external visual requalification is good for five years, so the cylinder is next due in May 2031.
Reading a cylinder collar. The newest requalification mark sets when the cylinder is next due.

How long a cylinder may be used

A cylinder must not be filled unless it is within its requalification period. Under the DOT rules in 49 CFR Part 180, a propane cylinder of the common types must be requalified 12 years after its date of manufacture, by a requalifier holding a RIN. After that the period depends on the method used, and the mark shows which method it was: an external visual inspection to the CGA procedure, the most common method for propane cylinders and marked with an E, is good for 5 years; a proof pressure test is good for 10 years; and a volumetric expansion test in a water jacket is good for 12 years. Requalification includes an inspection of the outside of the cylinder for dents, gouges, corrosion, fire damage, bulges and damage to the collar and foot ring. A cylinder that fails is condemned and must be made unusable and recycled; it is never patched or repainted to hide damage. A cylinder past its date may still be used to burn the propane already in it, but it may not be refilled or offered for transport full.

Worked problem

Is this cylinder in date?

A 100 lb cylinder from the farm is marked with a manufacture date of 08 09 and a requalification mark of 09 A123 21 E. Another is marked 03 14 with no requalification mark. On Friday, September 25, 2026, which may be refilled?

Show solution
  1. First cylinder: last requalified September 2021 by external visual inspection; next due:
  2. \[2021 + 5 = 2026 \;\to\; \text{September 2026: due this month}\]
  3. Second cylinder: made March 2014, never requalified; first requalification due:
  4. \[2014 + 12 = 2026 \;\to\; \text{March 2026: out of date}\]

Answer: The first cylinder reaches the end of its five-year period this month, so the supplier will requalify it before the next fill. The second ran out of date in March 2026 and must be requalified or retired before it is filled again. Jonah tagged both with Bayline's yellow "requalification due, do not fill" tag for the supplier.

Cylinder valves and the overfilling prevention device

The valve is the most important part of a cylinder after the steel itself. A vapor-service cylinder valve has a handwheel that opens and closes the main seat, an outlet for the regulator or hose, a pressure relief valve built into the valve body that discharges into the vapor space, and a short dip tube for the fixed liquid level gauge, a small bleeder valve whose tube ends at the level the cylinder should be filled to. Modern barbecue-size cylinders have a Type 1 outlet with a large external thread that accepts a hand-tightened connector with a built-in excess flow check and a thermal shutoff, and that will not let gas flow unless it is properly connected. Older cylinders used a POL connection, a left-hand thread tightened with a wrench.

Cylinders from 4 lb to 40 lb propane capacity used in vapor service must also have an overfilling prevention device (OPD) under NFPA 58: a float inside the cylinder that closes the filling path when the liquid reaches the safe level. OPD valves are identified by a triangular handwheel and the letters OPD on the valve. The OPD is a backup, not a filling method; cylinders must still be filled by weight or by volume using the fixed liquid level gauge. A cylinder of that size without an OPD may not be refilled.

Storing cylinders

Cylinders are stored outdoors wherever possible, upright with the relief valve in the vapor space, valves closed and capped or plugged when not connected, away from building openings, air intakes, heat and ignition sources, and protected from vehicles and tampering. NFPA 58 limits the propane that may be stored inside buildings to small quantities in specific circumstances, and the Ohio Fire Code is strict: in residential buildings, including basements and attached garages, it allows only small cylinders of about 2.7 lb each and 5.4 lb in total per living unit. At public locations, cylinders awaiting sale or exchange must be in a lockable, ventilated metal locker or rack and protected from vehicles. Bayline's cage is outdoors, fenced, locked, ventilated at the base, well away from the shop's doors and the neighboring property, and signed with the propane and no smoking signs the code requires.

Worked problem

How much propane is in the cage?

The cage holds six 20 lb cylinders, one 33 lb forklift cylinder and five 100 lb cylinders, all full. The four retired farm cylinders are empty. What is the total weight of propane, and if propane releases about 21,600 Btu per pound, how much energy is stored?

Show solution
  1. Propane:
  2. \[6 \times 20 + 33 + 5 \times 100 = 120 + 33 + 500 = 653 \text{ lb}\]
  3. Energy:
  4. \[653 \times 21{,}600 = 14{,}104{,}800 \text{ Btu} \approx 14.1 \text{ million Btu}\]

Answer: About 650 lb of propane, about the energy a house furnace uses in two weeks of cold weather, sits in a cage the size of a garden shed. That is why it is outdoors, locked, separated and signed.

Carrying cylinders

Cylinders travel in Bayline's vans and trucks under the federal hazardous materials regulations in 49 CFR, which treat propane as a Division 2.1 flammable gas, UN1075. The materials of trade exception covers what a service contractor carries in support of its work, with limits on the size of each cylinder and the total weight on the vehicle, and conditions on securing and marking; larger loads need placards, shipping papers and training. Whatever the quantity, Bayline's rules are the same: cylinders upright and secured so they cannot fall, roll or shift, valves closed and plugged or capped, never in the cab or a closed car trunk, the cargo area ventilated, and never left in a closed vehicle in the sun. A cylinder lying on its side can put its relief valve in the liquid, so a relief valve that opens on a hot day discharges liquid instead of vapor.

Connecting a cylinder

Before connecting any cylinder, Bayline technicians check the collar for the requalification date, look at the cylinder for damage and the valve for a damaged thread or seat, make sure the connector and its washer or O-ring are in good condition and fit the outlet, and confirm the regulator suits the appliance: a high-pressure torch or heater regulator is never put on an appliance meant for 11 in. w.c.. They connect with the valve closed, open the valve slowly, and leak test every connection they made with leak detection solution or an electronic detector before lighting anything. Hoses must be certified for propane, of the right pressure rating, protected from damage and kept as short as practical; they are never run through doorways or windows where they can be pinched. When a cylinder is disconnected, its valve is closed first, the line is allowed to burn out or is bled safely outdoors, and the outlet is capped.

Manifolded cylinders and automatic changeover

Where a customer uses more propane than one cylinder can supply between deliveries, but a tank is not practical, two or more 100 lb cylinders are connected through a manifold to an automatic changeover regulator. The regulator draws from the cylinders on the service side until they run low, then switches by itself to the reserve side, and a small indicator on top turns from green to red to show that the service side is empty. The supplier, or the customer, then replaces or refills the empty cylinders and turns the lever to make the full ones the new reserve. A two-cylinder installation of this kind is what the farm outside Grove City used before its tank was set, and it is common at cottages, small shops and construction sites. The cylinders stand on a firm, level, non-combustible base, are chained or strapped so they cannot be knocked over, and are connected with pigtails rated for full cylinder pressure. Because the changeover regulator is usually also the first stage of a two-stage system, a second-stage regulator is still needed at the building, as lesson 6 explains. Manifolding does not increase the vaporizing ability of a cylinder: a changeover set draws from one side at a time, so on a cold day a two-cylinder set supplies only what the cylinder in service can boil, which lesson 5 shows is often less than a furnace needs.

Common mistakes

  • MistakeFilling or using a cylinder without reading its collar.

    InsteadCheck the manufacture and latest requalification marks first; out-of-date cylinders are not filled.

  • MistakeLaying a vapor-service cylinder on its side in a van.

    InsteadCarry cylinders upright and secured so that the relief valve stays in the vapor space.

  • MistakeRelying on the OPD to stop the fill.

    InsteadThe OPD is a backup; cylinders are filled by weight or by volume.

  • MistakeMounting a forklift cylinder any way it fits.

    InsteadMount it as the locating pin and markings require so the relief valve is in the vapor space.

  • MistakeStoring a spare barbecue cylinder in a basement or attached garage.

    InsteadCylinders are stored outdoors, away from openings and ignition sources, as the code limits indoor storage.

Summary and key terms

  • Cylinders are portable containers built to DOT specifications, sold by the propane they hold and filled at a refill station or exchanged; tanks are stationary ASME containers filled on site.
  • Common sizes run from 4 lb camping cylinders to 100 lb farm and construction cylinders, with horizontal liquid-withdrawal cylinders for forklifts.
  • The collar shows the specification, water capacity, tare weight, manufacture date and every requalification.
  • DOT cylinders are first requalified 12 years after manufacture, then every 5 years by external visual inspection, 10 by proof pressure or 12 by volumetric expansion. Small vapor cylinders must have an OPD, recognized by its triangular handwheel, but are still filled by weight or volume.
  • Cylinders are stored outdoors, carried upright and secured, and connected with the right regulator and a leak test.
Cylinder
A portable propane container built to a transport specification and filled at a refill station.
Water capacity
The amount of water a container would hold, the basis for its fill limit.
Tare weight
The weight of an empty cylinder with its valve.
Requalification
The periodic inspection or test that allows a cylinder to continue in service.
Overfilling prevention device
A float-operated device in a small cylinder valve that stops the fill at the safe level.
Fixed liquid level gauge
A small bleeder valve with a dip tube ending at the maximum fill level.
Type 1 connection
The hand-tightened barbecue cylinder connection that flows gas only when properly connected.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What two collar markings decide whether a cylinder may be refilled?

    Show answer

    The date of manufacture and the latest requalification mark.

  2. What does the letter E in a requalification mark mean?

    Show answer

    The cylinder was requalified by external visual inspection.

  3. How do you recognize an OPD valve?

    Show answer

    By its triangular handwheel and the letters OPD on the valve.

  4. Why must a forklift cylinder be mounted as its locating pin requires?

    Show answer

    So that the withdrawal tube is in the liquid and the relief valve is in the vapor space.

  5. Why are cylinders carried upright?

    Show answer

    So the relief valve stays in the vapor space and would release vapor, not liquid.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz