GAS-240 · Lesson 1 of 12 · 25 min
Propane properties and why storage is different
▶ Video coming soon A video version of this lesson is on the way.
On Monday morning, September 28, before the vans left the yard, Luis Ferreira set a 20 lb barbecue cylinder on the shop bench beside a pressure gauge, a roofing torch and a thermometer. He screwed the gauge onto the valve and opened it. The needle jumped to about 113 psig. "It's 72 °F in here," he told Jonah. "Now watch." He carried a second cylinder, the same size, out of the walk-in cooler where the shop kept its sealant in summer, and fitted the gauge. About 54 psig." Same gas, same cylinder, same amount left in it. Only the temperature changed." Then he connected the torch to the warm cylinder and ran it hard for ten minutes against a brick. By the end, a band of frost had formed on the outside of the cylinder, level with the liquid inside, and the gauge had dropped by a third. "Everything you will learn about propane storage," Luis said, "is in these three minutes. It is stored as a liquid, it is used as a vapor, and the pressure depends on temperature."
GAS-110 introduced propane's specific gravity, heating value and flammable range, and GAS-120 showed where the storage code fits beside the installation code. This lesson explains the properties that make propane storage different from natural gas service: why propane is a liquid in the container, what sets the pressure, how much it expands, how a leak behaves and how propane is made to smell. Every later lesson in this course builds on them.
A gas that liquefies under modest pressure
Natural gas arrives at a building through a utility main at a pressure the utility controls, and the building never stores any. Propane is different because it is easy to liquefy. At atmospheric pressure it boils at about −44 °F, so on any day warmer than that, propane left in an open pan would boil away. Put it in a closed container, though, and the liquid boils only until the vapor above it reaches a certain pressure. At that pressure, boiling stops: molecules leave the liquid as fast as others return to it. That balance pressure is the vapor pressure, and it depends only on the temperature of the liquid. It does not depend on how much liquid is left, which is why a nearly empty cylinder on a warm day reads the same pressure as a full one.
Because propane is stored as a liquid, a small container holds a great deal of fuel. One volume of liquid propane boils to about 270 volumes of vapor at atmospheric pressure and normal room temperature. A 20 lb cylinder holds enough fuel to run a 50,000 Btu/h barbecue burner for about eight hours; the same energy as natural gas at atmospheric pressure would fill a room. That is the great advantage of propane where there are no gas mains: farms, cottages, construction sites, forklifts, food trucks and vehicles. It is also what makes propane storage demanding. A container holds a liquid at a pressure that rises and falls with the weather, and if that liquid escapes it turns into a large, heavy, flammable cloud.
Worked problem
How much vapor does a leak of liquid make?
A fitting on a liquid line leaks half a gallon of liquid propane before it is shut off. Using an expansion ratio of 270, how much vapor does that make, and how many cubic feet of flammable mixture could it form at the lower flammable limit of about 2.1 parts in 100? (1 gal = 0.1337 ft³.)
Show solution
- Liquid in cubic feet:
- \[0.5 \times 0.1337 = 0.0669 \text{ ft}^3\]
- Vapor:
- \[0.0669 \times 270 = 18.1 \text{ ft}^3\]
- Mixture at the lower flammable limit:
- \[\frac{18.1}{0.021} = 862 \text{ ft}^3\]
Answer: Half a gallon of liquid makes about 18 ft³ of vapor, enough to bring about 860 ft³ of air to the lower flammable limit. That is the volume of a small basement room, which is why liquid leaks are treated so seriously.
Vapor pressure and temperature
The table below gives the approximate vapor pressure of pure propane at a range of temperatures. Commercial propane is mostly propane with small amounts of propylene, butane and ethane, so a real container may read a little higher or lower, but the pattern is the same. Pressure rises quickly with temperature: from a cold winter morning to a hot summer afternoon, the pressure in a tank can change by a factor of ten. Containers, valves and regulators are built for that range. Tanks are commonly designed for a working pressure of 250 psig and fitted with relief valves set close to it, and cylinders for a service pressure of 240 psig with relief valves set higher, typically around 375 psig. Those are typical values; the nameplate or collar of each container gives its own.
| Liquid temperature | Approximate vapor pressure (gauge) |
|---|---|
| −40 °F | 1 psig |
| −20 °F | 11 psig |
| 0 °F | 23 psig |
| 20 °F | 41 psig |
| 40 °F | 65 psig |
| 60 °F | 92 psig |
| 70 °F | 109 psig |
| 80 °F | 129 psig |
| 100 °F | 174 psig |
Two practical lessons follow from the table. First, a container in the sun or near a heat source can build pressure quickly, and if the liquid fills the container completely, the pressure rises far faster still, as lesson 7 explains. That is why containers are never filled full, never stored near heat and always fitted with a relief valve. Second, on the coldest days the pressure in a tank falls, and with it the tank's ability to deliver vapor. At −40 °F propane barely boils at all. Lesson 5 shows how tanks are sized so that there is still enough pressure and enough vapor on a design winter day.
Why the container frosts: boiling takes heat
When vapor is drawn from a container, the pressure above the liquid drops slightly, and the liquid boils to replace the vapor. Boiling takes heat: about 184 Btu per pound of propane at its boiling point, and a little less at room temperature. That heat comes from the liquid itself, which cools, and from the container wall, which takes heat from the surrounding air. If vapor is drawn faster than heat can flow in through the wetted wall, the liquid cools, its vapor pressure falls and the supply pressure falls with it. Moisture in the air condenses and freezes on the cold steel at the liquid level, giving the frost band Jonah saw on the bench. Frost on a container in use is not a leak; it is a sign that the container is being worked hard. Frost on a fitting or a pipe joint, on the other hand, can mark liquid escaping and boiling at the leak, and must be investigated.
Worked problem
How much heat does the torch draw from the cylinder?
Luis's torch burned 2.4 lb of propane in the ten minutes. How much heat had to flow into the liquid to boil it, and what average rate of heat flow is that in Btu/h?
Show solution
- Heat to boil the propane:
- \[2.4 \times 184 = 442 \text{ Btu}\]
- Time in hours:
- \[\frac{10}{60} = 0.1667 \text{ h}\]
- Average rate:
- \[\frac{442}{0.1667} = 2{,}650 \text{ Btu/h}\]
Answer: About 2,650 Btu/h of heat had to flow through the steel of a small cylinder from the shop air. It could not keep up, so the liquid cooled, the frost formed and the pressure fell. A small cylinder simply cannot supply a large burner for long.
Liquid that expands
Liquid propane expands much more with temperature than water does: roughly 1.5 in 100 for every 10 °F near ordinary temperatures, and more as it gets warmer. A container filled to the brim on a cool morning would have nowhere for the liquid to go by afternoon. Liquid cannot be compressed, so the pressure in a liquid-full container rises by hundreds of psi per degree, far faster than the vapor pressure curve, until the relief valve opens and discharges liquid, or something fails. For that reason the codes limit how much propane may be put into any container, leaving a vapor space for expansion. For a typical residential tank that limit works out to about 80 parts in 100 of the container's volume at normal filling temperatures, and for a cylinder filled by weight it works out to about 42 parts in 100 of the container's water capacity by weight, because liquid propane weighs only about half as much as water. Lesson 7 covers how containers are filled so that the limit is never exceeded.
Heavier than air, and slow to disperse
Propane vapor has a specific gravity of about 1.52: it is half again as heavy as air. Natural gas, at about 0.6, rises and usually disperses through a building's upper levels and out. Propane vapor from a leak flows downhill like water. It collects in basements, crawl spaces, sumps, pits, window wells, ditches and low corners of a room, and it can travel along the ground to a pilot light, a water heater burner, a furnace or a running engine well away from the leak. In still air it can lie in a low place for a long time. The farm pit near Grove City that GAS-110 described is a textbook example: propane leaking from a buried line found its way into the one low, enclosed space on the property.
This changes how propane leaks are searched for and how spaces are tested. A combustible gas detector is held low, near the floor, in drains and in pits, not up by the ceiling. Basements are ventilated from the bottom, by blowing air in low or drawing it out at floor level. Containers are never stored or installed where escaping vapor could flow into a building opening below them, a basement window or a storm drain. And codes generally keep propane containers and propane-burning equipment with standing ignition sources out of basements and pits unless specific conditions are met. These rules all follow from a single number on the property chart.
| Property | Propane (typical) | Natural gas (typical) | What it means |
|---|---|---|---|
| Specific gravity of vapor | 1.52 | 0.60 | Propane sinks and pools; natural gas rises |
| Heating value of vapor | about 2,500 Btu/ft³ | about 1,000 Btu/ft³ | Propane needs much smaller orifices for the same input |
| Heating value of liquid | about 91,500 Btu/gal | not stored as liquid | Fuel is bought and stored by volume or weight of liquid |
| Air needed to burn one volume | about 24 volumes | about 9.6 volumes | Propane burners need much more air per volume of gas |
| Flammable range in air | 2.1 to 9.5 parts in 100 | 5 to 15 parts in 100 | A small leak reaches the lower limit quickly |
| Boiling point | about −44 °F | about −259 °F | Propane stays liquid under modest pressure |
| Liquid to vapor | about 1 to 270 | not applicable | A small liquid leak makes a large vapor cloud |
The smell of propane, and when it fades
Propane has no smell of its own. Suppliers add an odorant, normally ethyl mercaptan, so that a leak can be smelled well below the lower flammable limit. The codes require propane to be odorized before it is delivered to users, and suppliers test that the odorant is present. Most people recognize the smell at once, but not everyone does: some people have a poor sense of smell, from age, illness, smoking or some medications, and anyone's sense of smell fades after a few minutes in an odor, a process called olfactory fatigue.
The odorant can also be lost before the gas reaches the appliance. This is called odor fade. Mercaptan reacts with rust and is absorbed by the steel inside new containers and pipes, especially a new tank that was not properly purged and conditioned, or a container that was left open to air and moisture and rusted inside. It can also be absorbed by soil around a leaking underground line, so that gas escaping from a buried pipe arrives at the surface with little or no smell. A leak that the homeowner cannot smell is still a leak. For that reason suppliers condition new containers, Bayline carries a combustible gas detector on every propane job and never relies on the nose alone, and both countries' propane safety advice recommends that homes using propane have propane gas detectors as well as carbon monoxide alarms.
Where the rules for storage come from
Because propane is stored on the customer's property in a pressure vessel, storage has its own code. NFPA 58, Liquefied Petroleum Gas Code, covers cylinders and tanks, their valves and fittings, their location, filling, transfer, cylinder exchange, bulk plants and vehicle and engine fuel systems. The current edition is 2024. In Ohio it applies through the Ohio Fire Code, whose 2025 edition took effect November 20, 2025, is based on the 2021 International Fire Code and brings in NFPA 58 through its LP-gas chapter; check which edition of NFPA 58 the adopted fire code references. The IFGC, through the Ohio Mechanical Code, or the Residential Code of Ohio covers the building piping, the appliances and their venting. Cylinders are built and requalified to U.S. Department of Transportation rules in 49 CFR, and tanks are built to the ASME pressure vessel code.
The division of work follows the division of codes. On most residential jobs the propane supplier owns the tank, sets it, fills it and installs the first-stage regulator; the gas contractor installs the piping from there, the second-stage regulator where agreed, the appliances and the venting. The two must agree on where the tank goes, what loads it will serve and who tests what, as the case study in lesson 12 shows.
Common mistakes
MistakeReading a propane pressure gauge to judge how full a container is.
InsteadPressure depends on temperature, not on the amount left; use a float gauge, weight or the fixed liquid level gauge.
MistakeTreating frost on a working container as a leak.
InsteadFrost at the liquid level shows hard vapor draw; frost on a fitting or joint may be a liquid leak and must be checked.
MistakeSearching for a propane leak with the detector held high.
InsteadPropane is heavier than air; test low, in pits, drains and basements.
MistakeTrusting the customer's nose to confirm there is no leak.
InsteadOdor can fade and people's sense of smell varies; use a detector and a leak test.
MistakeFilling or allowing a container to be filled full of liquid.
InsteadLiquid expansion in a full container builds pressure rapidly; the fill limit leaves vapor space.
Summary and key terms
- Propane boils at about −44 °F, so in a closed container it is a liquid with vapor above it at a pressure set only by the liquid's temperature.
- One volume of liquid makes about 270 volumes of vapor, so small containers hold a lot of fuel and small liquid leaks make large clouds.
- Drawing vapor boils liquid, which takes heat from the container wall; drawing too fast cools the liquid, drops the pressure and frosts the container.
- Liquid propane expands strongly with temperature, so containers are never filled full.
- The vapor is about 1.52 times as heavy as air and pools in low places.
- An odorant, normally ethyl mercaptan, is added, but odor can fade through rust, new steel or soil, so detectors are used.
- NFPA 58, applied through the Ohio Fire Code, cover storage and vehicle systems, while the installation code covers piping and appliances.
- Vapor pressure
- The pressure of vapor above a liquid in a closed container, set by the liquid temperature.
- Expansion ratio
- The volume of vapor that one volume of liquid propane makes, about 270.
- Wetted surface
- The part of a container wall in contact with liquid, through which heat for boiling flows.
- Odorant
- A chemical, normally ethyl mercaptan, added so that propane can be smelled.
- Odor fade
- Loss of odorant through reaction with rust, new steel or soil, so that a leak smells weak or not at all.
- Olfactory fatigue
- The loss of the ability to smell an odor after being exposed to it for a while.
- Fill limit
- The largest amount of propane a container may hold, leaving vapor space for expansion.
Practice problems
Work each problem on paper first, then reveal the answer to check.
Why does a nearly empty cylinder read the same pressure as a full one on the same day?
Show answer
Vapor pressure depends only on the liquid temperature, not the amount of liquid.
What causes a frost band on a cylinder supplying a large burner?
Show answer
Boiling draws heat from the liquid and wall faster than it flows in, so the wall at the liquid level gets cold enough to freeze moisture.
Where would you test for a propane leak in a basement, and why?
Show answer
Near the floor and in low spots, because propane is heavier than air.
Name two things that can cause odor fade.
Show answer
Rust or new steel inside a container or pipe, and soil around a buried leak.
Why are containers never filled full of liquid?
Show answer
Liquid expands with temperature and a full container's pressure would rise rapidly.
Lesson quiz · 5 questions
Score 60% or more to complete this lesson.
Create a free account to save your progress, take quizzes and earn a certificate.