CON-140 · Lesson 5 of 12 · 27 min

Building size and construction type

Once the occupancy is known, the next question is how big and how tall the building may be, and what it must be built of. Codes link three things: the occupancy, the size of the building (its height in stories and meters or feet, and its area) and the construction type, which describes how combustible the structure is and how long its main elements must resist fire. Sprinklers are the fourth factor, because a sprinklered building is allowed to be larger or less fire-resistant than an unsprinklered one. Getting this combination right is one of the most consequential decisions in a building's design, because it fixes the structural system, the fire-resistance ratings of floors, roofs and walls, and much of the cost.

Construction managers meet these rules in preconstruction cost studies, value engineering and product substitutions. A proposal to change from steel to wood framing, to drop the sprinkler system or to add a story all depend on them. This lesson explains how the code sets size limits, defines construction types and treats mass timber, and how firewalls divide a large building into smaller ones for code purposes.

Measuring building size

Codes measure size with specific definitions, and the results can differ from the area on a real estate plan.

  • Building area, in the IBC, is the area included within surrounding exterior walls, or exterior walls and fire walls, exclusive of vent shafts and courts. Allowable area limits in IBC Chapter 5 apply to each story, and total building area is limited to a multiple of the allowable area per story.
  • Building height, in the IBC, is measured in feet from grade plane to the average height of the highest roof surface, and the number of stories above grade plane is limited separately. A basement is not a story above grade plane if its floor above is less than 6 ft above grade plane, or not more than 12 ft above finished ground at any point.
  • Grade plane is a reference plane representing the average of finished ground level adjoining the building at exterior walls, measured at the lowest points within 6 ft of the building or the property line if closer.

These definitions matter on sloping sites, where a basement may be partly above ground on one side, and on buildings with mezzanines, which may or may not count as stories depending on their size and openness. A construction manager who adds a mezzanine for storage during construction may unknowingly add a story for code purposes.

Types of construction in the IBC

IBC Chapter 6 defines five types of construction, numbered I to V, several divided into A and B. Type A is the protected version, with higher fire-resistance ratings, and Type B is unprotected or less protected. Table 601 sets the required fire-resistance ratings in hours for the structural frame, bearing walls, floors and roofs for each type.

  • Type I (A and B): noncombustible materials with the highest ratings, typically 3 hours for the frame in Type IA and 2 hours in IB. Used for high-rises, hospitals and large buildings.
  • Type II (A and B): noncombustible materials with lower ratings; Type IIB has no required rating for most elements. Common for steel-framed stores, warehouses and offices.
  • Type III (A and B): noncombustible exterior walls and any permitted material, usually wood, inside. Common for low-rise apartments and mixed-use buildings.

Two further types complete the system.

Type IV covers heavy timber (Type IV-HT) and, since the 2021 IBC, three mass timber types: IV-A, IV-B and IV-C, which allow tall wood buildings of cross-laminated timber and glued-laminated members with different amounts of noncombustible protection. Type V (A and B) allows any material permitted by the code, typically light wood framing; Type VA has 1-hour ratings and Type VB none. Type VB is the most common construction for small commercial buildings and houses.

A bar chart comparing tabular allowable area per story for Group B under IBC Table 506.2 for five construction types (IA unlimited, IIB, IIIB, VA, VB) with two bars each: nonsprinklered and sprinklered. Sprinklered bars are about four times the nonsprinklered bars for one-story buildings. Type IA shows unlimited.
Allowable area per story for a business occupancy rises steeply with sprinklers and more fire-resistant construction types.

Allowable height and area

The IBC sets allowable height and area in Chapter 5 using three tables. Table 504.3 gives the maximum height in feet above grade plane, Table 504.4 the maximum number of stories and Table 506.2 the allowable area per story, each for every occupancy and construction type, with separate values for nonsprinklered (NS) buildings and sprinklered buildings: S1 for one-story and S13R for some residential buildings, SM for multistory. Sprinklered buildings may generally be 20 ft taller and one story more than nonsprinklered ones, and their allowable area per story is typically three to four times larger.

Frontage also increases the allowable area. Where a building has more than 25 percent of its perimeter on a public way or open space at least 20 ft wide, Section 506.3 allows an increase factor If = [F/P − 0.25] × W/30, where F is the building perimeter fronting the open space, P is the total perimeter and W is the open space width (capped at 30 ft for the calculation in most cases). The allowable area per story is then the tabular area At plus At × If. For multistory buildings, the total allowable building area is the per-story allowable area multiplied by the number of stories above grade plane, up to a maximum of three for sprinklered buildings or two for nonsprinklered.

Selected allowable height and area values for Group B from IBC Tables 504.3, 504.4 and 506.2. Check the tables in the adopted edition.
TypeGroup B height (ft) NS / SGroup B stories NS / SGroup B area per story (ft²) NS / S1
IIB55 / 753 / 423,000 / 92,000
IIIB55 / 753 / 419,000 / 76,000
VA50 / 703 / 418,000 / 72,000
VB40 / 602 / 39,000 / 36,000

Worked problem

Checking allowable area with frontage

A proposed one-story office (Group B) of Type VB construction, nonsprinklered, has a footprint of 120 ft × 100 ft = 12,000 ft². Its perimeter is 440 ft, of which 220 ft fronts streets with open space at least 30 ft wide. Is the area permitted?

Show solution
  1. Tabular area for Group B, Type VB, NS: 9,000 ft² per story (Table 506.2).
  2. Frontage: F/P = 220 ÷ 440 = 0.50, and W = 30 ft, so If = (0.50 − 0.25) × 30 ÷ 30 = 0.25.
  3. Allowable area: Aa = 9,000 + 9,000 × 0.25 = 11,250 ft².
  4. Proposed area 12,000 ft² exceeds 11,250 ft², so the design does not comply as Type VB nonsprinklered.
  5. Options: add sprinklers (S1 area 36,000 ft²), change to Type VA (18,000 ft² NS), increase frontage, or divide the building with a fire wall.

Answer: Not permitted: the allowable area with frontage is 11,250 ft², less than 12,000 ft²; sprinklers or a more fire-resistant type would solve it.

Mass timber and tall wood buildings

Mass timber, including cross-laminated timber (CLT), glued-laminated timber (glulam), nail-laminated timber and laminated veneer lumber, has changed what codes allow. Large solid timber members char at a predictable rate in a fire, and the char layer insulates the wood behind it, so mass timber can achieve fire-resistance ratings that light wood framing cannot. Encapsulating the timber with gypsum board delays the onset of charring and reduces the fuel the structure contributes to a fire.

The 2021 IBC introduced three mass timber types. Type IV-A allows up to 18 stories for Group B and R-2 (270 ft maximum height), with full noncombustible protection of the timber. Type IV-B allows up to 12 stories (180 ft) with limited exposed timber, and Type IV-C allows up to 9 stories for Group B and 8 for R-2 (85 ft) with all timber permitted to be exposed. The 2024 IBC increased the amount of exposed timber permitted in Type IV-B. Mass timber types require sprinklers, noncombustible protection installed progressively during construction under IBC Chapter 33 and special inspections of connections and protection.

Fire walls

A firewall divides a building into two or more parts that are treated as separate buildings for the purposes of building area and construction requirements. A firewall must have a high fire-resistance rating and remain standing even if the structure on one side collapses, so it is usually concrete or masonry, extends through the roof or to a parapet, and is designed to resist the lateral forces a collapsing structure would place on it. Firewalls are a common way to build large warehouses, shopping centers and long apartment blocks in cheaper construction types.

In the IBC, Section 706 requires fire walls with ratings from Table 706.4, typically 3 hours for Groups A, B, E, H-4, I, R-1, R-2 and U (2 hours permitted in Types II and V construction), 3 hours for Groups F-1, H-3, H-5, M and S-1, 4 hours for H-1 and H-2, and 2 hours for F-2, S-2, R-3 and R-4. Fire walls must have structural stability so that collapse on either side does not cause the wall to collapse, must extend from the foundation to the roof and usually to a parapet at least 30 in above the roof, and have limited, protected openings.

Worked problem

Using a firewall to meet area limits

A one-story warehouse (Group S-1), Type IIB, sprinklered, is proposed at 140,000 ft². The allowable area per story from Table 506.2 (S1) is 70,000 ft², and frontage adds 50 %, giving 105,000 ft². How could a fire wall help, and what must it provide?

Show solution
  1. The 140,000 ft² building exceeds the 105,000 ft² allowable area.
  2. A fire wall dividing it into two 70,000 ft² buildings makes each a separate building for area purposes, each within the limit (even before frontage).
  3. For S-1, Table 706.4 requires a 3-hour fire wall.
  4. It must be structurally stable, extend to a parapet at least 30 in above the roof unless an exception applies, and have limited openings with rated fire doors.
  5. Compare the cost with the alternative of a larger allowable area, for example by increasing frontage or using unlimited area provisions for sprinklered one-story S buildings surrounded by 60 ft of open space under Section 507.

Answer: Two buildings of 70,000 ft² each, divided by a stable 3-hour fire wall with a parapet and protected openings, or consider an unlimited-area building under Section 507.

Construction type in practice

Construction managers deal with construction type every day, often without naming it. A steel deck roof on unprotected steel joists in a Type IIB or noncombustible unrated building is cheap, but adding a story may require protecting the steel with fireproofing or gypsum board. Wood blocking, furring and roofing in a noncombustible building are permitted only within the code's limits. Combustible insulation, plastic piping and cladding containing plastics need specific approval in noncombustible buildings. Substituting a product on site, such as a foam-plastic insulated panel for a mineral-wool panel, can change compliance with the construction type and with exterior wall fire spread rules.

The construction type also drives the fire-resistance ratings that must be maintained throughout construction: rated floor assemblies need listed designs, rated columns need protection to their full height, and penetrations need firestopping. Lesson 6 covers these ratings in detail.

Common mistakes

  • MistakeMeasuring building area as total floor area.

    InsteadAllowable area applies per story, and total building area is limited separately.

  • MistakeAdding a mezzanine or story on site without checking height limits.

    InsteadCheck whether the change adds a story for code purposes and whether the construction type still applies.

  • MistakeRemoving sprinklers in value engineering without reviewing size limits.

    InsteadSprinklers often allow the permitted area and height; removing them may require more fire-resistant construction.

  • MistakeSubstituting combustible products in noncombustible construction.

    InsteadCheck the code limits on combustible components and route substitutions to the designer.

  • MistakeTreating a rated wall as a firewall.

    InsteadA firewall must be structurally stable, extend to the roof and meet higher ratings; ordinary fire separations do not divide a building.

Summary and key terms

  • Occupancy, size, construction type and sprinklers are linked: larger buildings need more fire-resistant construction or sprinklers.
  • Height is limited in feet and stories above grade plane; area is limited per story with a total limit.
  • The IBC defines Types I to V with ratings in Table 601 and limits in Tables 504.3, 504.4 and 506.2.
  • Sprinklers allow larger and taller buildings.
  • Types IV-A, IV-B and IV-C allow mass timber up to 18, 12 and 9 stories.
  • Firewalls divide a building into separate buildings for area and construction purposes.
  • Site substitutions and added stories can change compliance with construction type.
Building area
Area within exterior walls and fire walls, used for allowable area limits.
Building height
Height in feet above grade plane and number of stories above grade plane.
Grade
Finished ground level; the IBC uses a grade plane averaged around the building.
Noncombustible construction
Construction in which the main elements are made of materials that do not burn under test conditions.
Combustible construction
Construction permitting wood and other combustible structural materials.
Mass timber
Large engineered wood members such as CLT and glulam.
Encapsulation
Noncombustible protection, usually gypsum board, over mass timber.
Firewall
A rated, structurally stable wall dividing a building into separate buildings.
Sprinklered
Protected throughout by an automatic sprinkler system to the referenced standard.
Frontage
Building perimeter facing a street or open space usable by fire fighters.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. Why do sprinklers allow larger buildings?

    Show answer

    They control most fires before they spread, reducing risk to occupants and property.

  2. Is a basement a story above grade plane under the IBC?

    Show answer

    Not if the floor above is less than 6 ft above grade plane and not more than 12 ft above finished ground at any point.

  3. Which IBC construction type is typical for a small wood-framed store?

    Show answer

    Type VB.

  4. How many stories does Type IV-A allow for Group B?

    Show answer

    Up to 18 stories (270 ft).

  5. What rating does a fire wall between Group M buildings need?

    Show answer

    3 hours (Table 706.4).

  6. Why must firewalls be structurally stable?

    Show answer

    So that collapse of the structure on one side does not bring down the wall and expose the other side.

  7. Calculate If for F/P = 0.75 and W = 30 ft.

    Show answer

    If = (0.75 − 0.25) × 1 = 0.50.

  8. Why can a storage mezzanine added late cause problems?

    Show answer

    It may count as a story, change the height and affect construction type and egress.

  9. Give an example of a substitution that could affect construction type compliance.

    Show answer

    Replacing mineral-wool insulated panels with foam-plastic panels in a noncombustible building.

  10. What protection is critical for mass timber during construction?

    Show answer

    Moisture protection and progressive installation of encapsulation, with fire safety measures for the combustible structure.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz