PLB-320 · Lesson 8 of 12 · 20 min

Reduced pressure principle assemblies

One morning in Maya's second month on the backflow unit, the building operator called Luis about water on the boiler room floor. Maya found it first: a steady stream pouring from the relief port of the reduced pressure assembly on the boiler fill line, splashing into the floor drain below. She reached for the inlet valve to stop it, and Luis caught her arm. "Wait. That device is doing exactly what it's supposed to do. It's telling us something is wrong. Find out what before you shut it up." The fault turned out to be a sliver of solder holding the first check open, left from a boiler room repair the week before. The relief valve had opened to keep boiler water out of the building's drinking water, and dumped the incoming water to the drain instead. This lesson is about that device, the reduced pressure principle assembly: the most protective mechanical backflow preventer, and the only one whose failures announce themselves.

How a reduced pressure principle assembly works

A reduced pressure principle assembly, usually called an RP or RPZ, has two independent spring-loaded check valves in series, like a double check. Between them is a chamber called the zone, and on the zone is a hydraulically operated relief valve that opens to the atmosphere. The assembly has shutoff valves at each end and four test cocks.

The first check is loaded more heavily than in a double check, so that when water flows, the pressure in the zone is always noticeably lower than the inlet pressure, typically 35 to 50 kPa lower. That is the reduced pressure the device is named for. The relief valve senses both the inlet pressure and the zone pressure. As long as the zone stays enough below the inlet, the relief valve stays closed. If the zone pressure rises to within about 14 kPa of the inlet pressure, the relief valve opens and dumps the zone to the atmosphere.

That rule covers every way the device can be challenged.

  • If the supply pressure drops, as in backsiphonage, the inlet pressure falls toward the zone pressure. The relief valve opens, the zone drains to atmosphere, and the first check closes. Even if the first check leaked, any water coming back from downstream would go out the relief port rather than upstream.
  • If the downstream pressure rises, as in backpressure, the second check closes. If the second check leaks, the leaking water raises the zone pressure, the relief valve opens, and the backflow water discharges to the drain instead of reaching the first check.
  • If the first check is fouled open, as in Maya's boiler room, the zone pressure rises close to the inlet pressure even with normal flow. The relief valve opens and discharges continuously, which is visible and wasteful, and is exactly the warning the device is designed to give.
A cut-away of a reduced pressure principle assembly with pressure labels. From left to right: test cock 1 and shutoff valve 1, test cock 2 on the inlet side, the first check with a heavy spring, the zone chamber with test cock 3 and a relief valve at the bottom opening to an air gap above a funnel drain, the second check with a lighter spring, test cock 4, and shutoff valve 2. Boxes show example pressures: inlet, zone about one step lower, and outlet slightly lower again.
A reduced pressure principle assembly keeps the zone between its checks at a lower pressure than the inlet. If that difference shrinks, the relief valve opens.

Why the relief valve matters

The relief valve turns a silent failure into a visible one. With a double check, a fouled check can sit unnoticed for a year. With a reduced pressure assembly, a fouled first check or a leaking second check under backpressure makes water pour from the relief port. Someone sees the puddle, calls a plumber, and the problem is found in days rather than months. This is why reduced pressure assemblies are accepted for the highest hazards, and why many designers use them even where a double check would satisfy the code.

The relief valve also provides a second layer of protection in the worst case. Even if both checks were damaged, the relief valve would open as long as the inlet pressure dropped toward the zone pressure, giving an atmospheric break in the middle of the device. In effect, a reduced pressure assembly creates a small, temporary air gap inside itself whenever it is needed.

That strength comes with costs. The assembly loses more pressure than a double check because of the heavy first check, often 50 to 100 kPa at its rated flow. It discharges water whenever it is challenged, and occasionally during sharp pressure fluctuations, so it needs a drain that can carry the full discharge. It cannot be installed where it could be flooded, because floodwater could reach the relief port. And it costs more to buy, install, test and repair.

Spitting, dumping and nuisance discharge

Plumbers use informal words for relief valve discharge. A brief spit when pressure surges is normal: when a big valve closes elsewhere in the building or the city main surges, the inlet pressure can drop for a moment, and the relief valve opens just long enough to restore the difference. A continuous dump means a check is fouled or the relief valve itself is not sealing. An intermittent discharge that repeats with pressure swings often means the supply pressure fluctuates more than the device can tolerate.

Each pattern points to a different fix. A continuous dump with steady supply pressure usually means debris on the first check or a damaged first check disc. Discharge only when the downstream equipment heats up or a downstream pump starts means the second check is leaking under backpressure. Frequent spitting with surges may be cured with a pressure-reducing valve or a surge arrester upstream, or with a soft-closing valve elsewhere in the system. Simply capping or plugging the relief port, which some owners have tried to stop the water, defeats the device completely and is illegal.

\[\text{relief valve opens when} \quad P_{\text{inlet}} - P_{\text{zone}} \leq \Delta P_{\text{relief}}\]

Worked problem

Reading an RP's pressures

Maya measured the boiler fill RP after the repair. Inlet pressure: 480 kPa. Zone pressure with flow: 430 kPa. The relief valve opens when the difference falls to 17 kPa. During a later main surge, the inlet dropped to 440 kPa for two seconds. Did the relief valve open?

Show solution
  1. Normal difference across the first check: 480 − 430 = 50 kPa, well above the 17 kPa opening point.
  2. During the surge the zone holds about 430 kPa for a moment, because the first check closes as the inlet falls.
  3. Difference during the surge: 440 − 430 = 10 kPa, which is less than 17 kPa, so the relief valve opens.

Answer: The relief valve spits briefly until the zone pressure drops and the difference is restored. That is normal behaviour, not a failure. If the operator reports frequent spitting, the next step is to watch the supply pressure for surges.

# Will an RP's relief valve open? It opens when inlet - zone <= the opening point.
def relief_opens(inlet_kpa, zone_kpa, opening_kpa=14):
    return (inlet_kpa - zone_kpa) <= opening_kpa

events = [("normal flow", 480, 430), ("main surge", 440, 430), ("first check fouled", 480, 475),
          ("backsiphonage", -20, 430), ("second check leaking under backpressure", 480, 478)]
for name, inlet, zone in events:
    state = "OPEN - discharging" if relief_opens(inlet, zone, 17) else "closed"
    print(f"{name:40s} inlet {inlet:4d} kPa, zone {zone:4d} kPa -> relief {state}")
Output
normal flow                              inlet  480 kPa, zone  430 kPa -> relief closed
main surge                               inlet  440 kPa, zone  430 kPa -> relief OPEN - discharging
first check fouled                       inlet  480 kPa, zone  475 kPa -> relief OPEN - discharging
backsiphonage                            inlet  -20 kPa, zone  430 kPa -> relief OPEN - discharging
second check leaking under backpressure  inlet  480 kPa, zone  478 kPa -> relief OPEN - discharging

Every abnormal condition in the list ends with the relief valve open. That is the design goal: whatever goes wrong, the zone is opened to the atmosphere rather than letting downstream water reach the inlet.

Drainage for the relief discharge

A reduced pressure assembly must be installed where its discharge can be safely carried away. The relief port discharges through an air gap into a funnel or directly over a floor drain or receptor; the drain line must never be connected tightly to the relief port, because a blocked drain could then back up into the zone. The drain must be sized for the device's full relief discharge, which manufacturers publish. Small assemblies may discharge only 0.5 to 1 L/s at full dump, but large ones on fire lines or premise services can discharge several litres per second, far more than a single small floor drain can carry.

When Kingsway Tower's premise RP was installed in the water service room, the designer sized a dedicated floor drain and trench for its full discharge, and placed the assembly so the relief water would not hit the electrical panel on the adjacent wall. Air gap drain funnels made by assembly manufacturers make the connection neat, but the funnel's capacity must match the discharge, and the funnel's drain must be sized separately.

Detector assemblies and large RPs

Fire lines that carry antifreeze, chemical additives or other higher hazards use a reduced pressure detector assembly, the reduced pressure version of the double check detector assembly covered in Lesson 7. The same metered bypass reveals small flows. Large RPs on premise services, often 100 mm and larger, are usually installed in pairs so one can be taken out of service for testing or repair without shutting off the building. Parallel installation is common practice in hospitals, high-rise residential buildings and anywhere water cannot be shut off for the hour a test and repair may take.

Where RPs are used at Kingsway Tower

By the end of the survey, Kingsway Tower had reduced pressure assemblies at five places: the premise device at the water service, installed as a parallel pair so the building is never without water during testing; the boiler plant fill; the chilled water fill; the dental clinic's tenant supply; and a new device on a chemical feed line for the cooling tower serving the café's refrigeration. Each sits at least a step above the floor, with its test cocks facing out, its relief port over a properly sized drain, and a tag recording its serial number and last test date.

Reading an RP's behaviour on site

An RP tells you a lot by how it behaves. A device that discharges steadily, even with no demand downstream, usually has a leaking first check or a fouled relief valve seat. A device that discharges only when the supply pressure drops, then stops, may be working exactly as designed. A device that discharges in short bursts when a downstream valve closes quickly is often reacting to water hammer, which can be fixed with a hammer arrester or slower closing valves rather than by repairing the RP.

When Maya was called to look at the boiler fill RP after a complaint about a wet floor, she watched it for a full minute before touching anything. The relief port dripped slowly and steadily. Grace's diagnosis was a piece of debris under the first check, which let the zone pressure creep up to the relief opening point. Cleaning the first check stopped the discharge, and the retest passed. "If it's dripping steadily, look at the first check before you blame the relief valve," Grace said. Maya wrote that down too.

Steady discharge also wastes water and can damage the floor or equipment around the device, so it should never be ignored or plugged. Plugging the relief port, or piping it directly to a drain without an air gap, turns the device into a hazard and is a serious violation. The right response is always to find and fix the cause, then retest.

Common mistakes

  • MistakeShutting off a discharging RP and leaving it off.

    InsteadFind the cause: a fouled check, a leaking second check under backpressure, or supply surges.

  • MistakeHard-piping the relief port to a drain.

    InsteadThe relief must discharge through an air gap so a blocked drain cannot back into the zone.

  • MistakeInstalling an RP in a pit or anywhere it could flood.

    InsteadFloodwater could reach the relief port; install it above grade and above any flood level.

  • MistakeSizing the drain for normal spitting rather than full discharge.

    InsteadSize the drain for the device's published maximum relief flow.

Summary and key terms

  • A reduced pressure principle assembly has two checks with a relief valve on the zone between them.
  • The zone is held lower than the inlet; if the difference falls to about 14 kPa, the relief valve opens.
  • It protects against backsiphonage and backpressure at the highest hazards.
  • A fouled check or a leaking second check under backpressure makes it discharge visibly.
  • The relief port discharges through an air gap to a drain sized for the full discharge.
  • It must not be installed where it could be flooded, such as in a pit.
Reduced pressure principle assembly
A testable assembly of two checks with a relief valve between them that opens if the zone pressure rises too close to the inlet pressure.
Zone
The chamber between the two checks of a reduced pressure assembly.
Relief valve
The valve on the zone that opens to the atmosphere when the pressure difference across the first check becomes too small.
Reduced pressure detector assembly
A reduced pressure assembly for fire lines with a metered bypass for small flows.
Parallel installation
Two assemblies side by side so one can be serviced while the other keeps the building supplied.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What keeps the zone pressure below the inlet pressure?

    Show answer

    The heavier spring loading of the first check.

  2. An RP discharges continuously with steady supply pressure. What is the likely cause?

    Show answer

    Debris or damage on the first check, or a relief valve that is not sealing.

  3. Why must the relief port discharge through an air gap?

    Show answer

    So a blocked drain cannot back up into the zone.

  4. Why are large premise RPs often installed in parallel?

    Show answer

    So one can be tested or repaired while the other keeps the building supplied.

  5. Inlet 500 kPa, zone 488 kPa, opening point 14 kPa. Is the relief valve open?

    Show answer

    500 − 488 = 12 kPa, which is less than 14, so yes.

Lesson quiz · 5 questions

Score 60% or more to complete this lesson.

Take the quiz