PLB-210 · Lesson 9 of 12 · 21 min
Water supply rules: pressure, sizing and protection
The café's water supply was simpler than its drainage, but the code still had plenty to say about it. The new supply would branch from the low-zone main in the parking ceiling, pass through a new submeter, feed the hand sinks, the three-compartment sink, the mop sink, the washrooms, a dishwasher, an ice machine and a coffee machine, and serve a small electric water heater under the counter. Luis asked Maya to check the design against the code's water supply rules: materials, pressure, sizing, valves and, above all, protection of the potable water.
PLB-130 taught the engineering of water supply systems. This lesson shows where the matching code rules live and how to check a design against them. Lesson 10 continues with hot water and backflow in more depth.
What the water supply rules cover
In Ontario's Part 7, Section 7.6, Potable Water Systems, covers the water supply: what must be connected to potable water, protection from contamination, backflow prevention, materials, sizes and capacities, pressure limits, valves, hot water temperature limits, and the testing and disinfection of new systems. Section 7.7 covers non-potable water systems such as rainwater and greywater.
Luis summarized the water supply rules as four questions: Is the right water going to the right fixture? Is the pressure within limits at every outlet? Is every pipe big enough? Is the potable water protected from everything that could contaminate it?
Potable water where people use it
The code requires potable water at every fixture used for drinking, cooking, bathing and washing: sinks, lavatories, showers, bathtubs, drinking fountains and so on. Non-potable water may be used only where the code allows it, typically for flushing toilets and urinals, irrigation and some industrial uses, and only through a separate, identified piping system that can never be connected to the potable system.
- Non-potable piping must be marked along its length, often in purple, with warning labels at outlets.
- Outlets on non-potable systems must be designed so that they cannot be mistaken for drinking water, such as locked or keyed hose bibbs.
- Non-potable systems need their own tests to show there is no cross-connection, such as running one system with dye or shutting off the potable supply and checking that no fixture still flows.
Kingsway Tower has no non-potable supply, but Maya noted that the code's rules would apply if the owner later added a rainwater system for the landscape irrigation, which had been discussed.
Materials for water supply
Every pipe, fitting, valve and fixture in contact with potable water must be certified as safe for drinking water and must meet lead-free limits. The code also lists which materials may be used for the water service, which for the water distribution system, and which for hot water, with any temperature and pressure limits.
Ontario's code lists permitted materials for water services and water distribution systems and requires products in contact with potable water to be certified to the health-effects standard for drinking water system components. Solder and flux must be lead-free. Some plastic materials are limited by temperature and pressure or by location, such as in buildings of noncombustible construction or in fire separations.
On the café drawing, the engineer showed type L copper for the branch from the main and PEX for the fixture connections, both permitted. The coffee machine and ice machine came with their own connection kits, and Maya made a note to check that their flexible hoses and filters were certified for potable water.
Pressure limits
Water pressure must be high enough for fixtures to work and low enough not to damage them or waste water. The code sets limits on both ends.
Ontario's code limits the static pressure at fixtures to 550 kPa, and where the supply can exceed that, a pressure-reducing valve is required. It also requires the system to provide enough pressure and flow for fixtures to operate as designed, and for flush valves and other devices that need a minimum pressure.
At Kingsway, the low zone is fed through the pressure-reducing valve station described in PLB-130, so the café is already within the pressure limit. Maya still checked the café's highest and lowest fixtures: the hand sinks at counter height had plenty of pressure, and the floor-level mop sink was within the maximum.
Worked problem
Pressure at the café's lowest fixture
The low-zone PRV station in the lower parking level is set to 450 kPa. The café's mop sink faucet is 5.5 m above the PRV outlet. What is the static pressure at the faucet, and is it within Ontario's 550 kPa limit?
Show solution
- Pressure lost to height: \(5.5 \times 9.81 \approx 54\) kPa.
- Static pressure at the faucet: \(450 - 54 = 396\) kPa.
- 396 kPa is below 550 kPa, so the limit is met.
- If the PRV failed open, the faucet could see the booster pressure; that is why PLB-130's station has a relief valve and an alarm.
Answer: About 396 kPa, within the 550 kPa limit.
Sizing rules
The code requires water pipes to be sized so that every fixture receives enough flow at enough pressure when the system is under its peak demand. Most codes give a choice of methods: a prescriptive method using tables of fixture units and pipe sizes, or an engineered method based on pressure loss, as PLB-130 described. The code also sets minimum sizes for the water service, for fixture supplies and for individual fixture connections.
Ontario's code assigns water supply fixture units to fixtures in a table, gives a method for converting them to design flow, and sets minimum sizes for supply pipes to each fixture type. It also limits velocity in some materials. Engineers designing large buildings usually use the pressure-loss method and show their calculations.
| Fixture | Practice minimum supply size |
|---|---|
| Lavatory | 10 mm (3/8 in) |
| Kitchen or bar sink | 12 mm (1/2 in) |
| Water closet, tank type | 10 mm (3/8 in) |
| Water closet, flush valve | 25 mm (1 in) |
| Mop or service sink | 12 mm (1/2 in) |
| Hose bibb | 12 mm (1/2 in) |
The program below runs a quick check that each fixture connection on the café drawing is at least the practice minimum size. The same check works with the real code table.
# Check fixture supply sizes against a minimum table (practice values, mm)
minimum = {"lavatory": 10, "sink": 12, "wc tank": 10, "wc flush valve": 25, "mop sink": 12, "hose bibb": 12}
drawing = [("hand sink 1", "sink", 12), ("hand sink 2", "sink", 10), ("lav, washroom A", "lavatory", 12),
("wc, washroom A", "wc tank", 10), ("mop sink", "mop sink", 12), ("3-comp sink", "sink", 20)]
for name, kind, size in drawing:
need = minimum[kind]
print(f"{name:16s} {size:3d} mm (min {need:2d}): {'ok' if size >= need else 'UNDERSIZED'}")hand sink 1 12 mm (min 12): ok hand sink 2 10 mm (min 12): UNDERSIZED lav, washroom A 12 mm (min 10): ok wc, washroom A 10 mm (min 10): ok mop sink 12 mm (min 12): ok 3-comp sink 20 mm (min 12): ok
The check found one undersized connection: a hand sink shown with a smaller supply than the practice minimum. On the real drawing, the engineer had made the same slip, and it was corrected before rough-in.
Valves required by code
The code requires valves so that parts of the system can be isolated for repair without shutting down the whole building. PLB-130 discussed valve layout in detail. The code sets the minimum.
- A main shutoff valve on the water service, accessible inside the building near where the service enters.
- Valves on the water supply to each dwelling unit or tenant space in multi-unit buildings, so one suite can be shut off without affecting the others.
- Valves at the base of risers or on branches in larger buildings.
- Valves on the supply to each fixture or appliance, or to groups of fixtures, depending on the code, and on the cold supply to every water heater.
- Valves must be accessible and, in many codes, identified; full-way valves are required in some locations so they do not restrict flow.
The café needed its own shutoff valve near where its branch left the low-zone main, plus fixture stops at each fixture and a valve on the cold supply to the under-counter heater. The drawing showed all of them, but Maya added a note that the tenant valve had to be accessible from inside the café, not hidden above a ceiling in the corridor.
Protecting the potable water
The most important water supply rules protect the drinking water from contamination. Backflow happens when water flows backward from a fixture, appliance or system into the potable supply, either because the supply pressure drops (back-siphonage) or because the downstream pressure rises above the supply pressure (backpressure). The code requires protection at every cross-connection, chosen to match the hazard.
- Air gap: an open vertical space between the water outlet and the flood level of the receiving fixture. It is the most reliable protection and is required in high-hazard cases.
- Atmospheric and pressure vacuum breakers: protect against back-siphonage only, used on hose bibbs, some fixtures and irrigation systems.
- Dual check valves and double check valve assemblies: for low-hazard connections, such as some boiler fills in houses and premise isolation where permitted.
- Reduced pressure principle assemblies: for high-hazard connections where the water could be contaminated with toxic substances, such as chemical dispensers and some boiler feeds.
For the café, the coffee machine and ice machine required backflow protection suited to beverage equipment; carbonated beverage dispensers in particular need protection that is not made of copper, because carbonated water can dissolve copper. The three-compartment sink filled through faucets with air gaps above the flood level rim. The dishwasher had its own internal air gap. The mop sink faucet needed a vacuum breaker. Lesson 10 covers how the code matches backflow devices to hazards.
Water service and meter rules
The code's water supply rules start at the property line. The water service must be of a permitted material, large enough for the building's demand, buried below frost or protected, and kept apart from the building sewer so that a leaking sewer cannot contaminate it. Where the service and sewer must cross or share a trench, the code sets conditions on separation, materials and elevation.
Ontario's code sets minimum separations between the water service and the building sewer and conditions for placing them in a common trench, and Hamilton's waterworks rules govern the connection to the city main, the curb stop and the meter. The city owns and installs the meter, and the plumber provides the meter setting to the city's standard drawing, with valves on both sides and support for the meter.
For the café, the water came from inside the building, so the service rules did not apply directly, but the submeter for the tenant space had to be installed to the building owner's standard so that the café could be billed fairly. Maya made sure there was a valve on each side of the submeter and room to remove it without cutting the pipe.
Common mistakes
MistakeSupplying a drinking fixture from a non-potable system.
InsteadPotable water is required at every fixture used for drinking, cooking, bathing or washing.
MistakeUsing pipe or hoses not certified for potable water.
InsteadCheck the health-effects certification and lead-free marking on everything that touches drinking water.
MistakeChecking pressure only at the top of the building.
InsteadCheck the highest and lowest outlets in each zone against the minimum and the code maximum.
MistakeUndersizing individual fixture connections.
InsteadMeet the code's minimum fixture supply sizes.
MistakeHiding a tenant shutoff valve outside the tenant's space.
InsteadMake required valves accessible to the people who need to use them.
Summary and key terms
- Ontario's water supply rules are in Section 7.6, with non-potable systems in Section 7.7.
- Potable water is required where people drink, cook, bathe or wash; non-potable systems must be separate and identified.
- Materials in contact with potable water must be certified for health effects and lead-free.
- Static pressure at fixtures is limited to 550 kPa; above that a pressure-reducing valve is required.
- Pipes must be sized for peak demand, with minimum fixture supply sizes.
- Required valves allow isolation of the service, suites, risers, fixtures and water heaters, and must be accessible.
- Every cross-connection needs backflow protection suited to the hazard.
- Potable water system
- The piping and devices that carry drinking water to fixtures.
- Non-potable water
- Water not suitable for drinking, such as rainwater, greywater or reclaimed water.
- Static pressure
- Water pressure with no water flowing.
- Back-siphonage
- Backflow caused by a drop in supply pressure, which draws water backward.
- Backpressure
- Backflow caused when downstream pressure exceeds the supply pressure.
- Air gap
- An unobstructed vertical distance between a water outlet and the flood level rim of the receiving fixture.
Practice problems
Work each problem on paper first, then reveal the answer to check.
In which section of Ontario's Part 7 are potable water systems covered?
Show answer
Section 7.6.
What is the maximum static pressure at fixtures in Ontario's code?
Show answer
550 kPa.
A PRV is set to 480 kPa and a fixture is 9 m above it. What is the static pressure at the fixture?
Show answer
About 480 minus 88, or 392 kPa.
Name two places where code-required shutoff valves are found in a multi-unit building.
Show answer
On the water service inside the building and on the supply to each suite or tenant space.
Why can a carbonated beverage dispenser not use a copper backflow device?
Show answer
Carbonated water can dissolve copper and contaminate the water.
What is the most reliable form of backflow protection?
Show answer
An air gap.
Lesson quiz · 5 questions
Score 60% or more to complete this lesson.
Create a free account to save your progress, take quizzes and earn a certificate.