CIV-421 · Lesson 6 of 12 · 20 min
Wood shear walls and diaphragms
Wind and earthquake loads push sideways on buildings, and in a wood-frame building the lateral load path runs through sheathed floors, roofs and walls. The roof and floors act as diaphragms, deep horizontal beams that collect the lateral load and deliver it to the walls. The walls parallel to the load act as shear walls, vertical cantilevers that carry it down to the foundation. Both are made of ordinary wood structural panels, plywood or oriented strand board (OSB), nailed to the framing, and their strength comes almost entirely from the nails. This lesson designs the lateral system of the two-storey office annex.
The load path
Wind on the long face of the annex pushes on the wall studs, which span from floor to floor and deliver half of their load to each diaphragm. The roof and second floor diaphragms span between the end walls, like simply supported beams lying flat. Each diaphragm delivers its end reaction to the end walls as a shear along their tops. The end walls carry the shear down through each storey, overturning tries to lift one end of each wall segment, and hold-downs at the ends of the segments carry that uplift into the foundation. Every link in the chain, from the wall studs to the anchor bolts, must be designed.
Diaphragms
A diaphragm behaves like a deep I-beam. The sheathing is the web and carries shear; the boundary members at the edges perpendicular to the load, usually the double top plates of the walls or a rim joist, are the flanges or chords, and carry the bending moment as tension and compression. For a simply supported diaphragm of span \(L\) and depth \(b\) under a uniform line load \(w\):
Here \(v\) is the unit shear along the supported edges, in force per unit length, and \(T\) and \(C\) are the chord forces. The chord must be continuous over the full length, so splices in the top plates are nailed or strapped to carry \(T\). Diaphragms are designed as blocked or unblocked: blocking under every panel edge lets the nails at those edges carry shear and roughly doubles the capacity. Openings for stairs and skylights interrupt the web and need collectors and extra chords around them.
Shear walls
A shear wall is a vertical cantilever. The sheathing nailed to studs and plates carries the shear, the end studs (chords) carry the overturning tension and compression, and the hold-downs anchor the tension chord. Only full-height segments, without openings, are counted in the simple segmented method, and each segment must have an aspect ratio of height to length within the limits of the standard, typically 3.5 to 1 for wind with a reduction above 2 to 1. Other methods, such as the perforated shear wall method and force transfer around openings, count more of the wall with extra detailing.
In O86, the factored shear resistance of a nailed shear wall comes from the nails. For a wall sheathed on one side, the unit resistance is \(v_r = \phi\,J_D\,n_u/s\,J_{us}J_{hd}\), where \(n_u\) is the unit lateral resistance of one nail from the yield equations of lesson 5, \(s\) the nail spacing along the panel edges, \(J_D = 1.3\) a factor for nailed sheathing in shear walls and diaphragms, \(J_{us}\) a factor for unblocked walls and \(J_{hd}\) a factor for hold-down restraint, with \(\phi = 0.8\). The panels must also be checked for buckling, which can govern thin panels on tall walls. Sheathing both faces roughly doubles the resistance.
The unit shear in a wall line is the shear delivered by the diaphragm divided by the total length of full-height segments. A segment's overturning moment at its base is the sum of each storey shear times its height above the base, and the hold-down force is
where \(l_s\) is the segment length and \(D_s\) the dead load on the segment. Strictly the moment arm is the distance between the chord centrelines, slightly less than the segment length, and designers allow for it.
Wind on the office annex
The annex is 16 m long, 8 m wide and two storeys of 3.0 m. With wind on the 16 m face, the factored line loads delivered to the diaphragms are 4.2 kN/m at the roof and 6.0 kN/m at the second floor, from the wind pressure on the wall area tributary to each level. Each end wall is 8 m long. In the second storey it has no full-height openings; in the first storey, a 1.6 m door in the middle leaves two 3.2 m full-height segments. The sheathing is 11 mm OSB with 3.25 mm common nails.
# Lesson 6: wind on the two-storey office annex, 16 m x 8 m, storey height 3.0 m (CSA O86 format)
import math
L, B, h = 16.0, 8.0, 3.0
w_roof, w_floor = 4.2, 6.0 # factored wind line loads on the diaphragms (kN/m)
# Diaphragms span 16 m between the 8 m end walls
for name, w in [("roof", w_roof), ("second floor", w_floor)]:
R = w * L / 2
v = R / B
T = w * L**2 / 8 / B
print(f"{name:12s}: reaction {R:.1f} kN, unit shear {v:.2f} kN/m, chord force {T:.1f} kN")
V2 = w_roof * L / 2 # shear in each end wall, second storey
V1 = V2 + w_floor * L / 2 # first storey
seg2, seg1 = [8.0], [3.2, 3.2] # full-height segments (first storey has a 1.6 m door)
v2, v1 = V2 / sum(seg2), V1 / sum(seg1)
print(f"\nEnd wall shear: second storey {V2:.1f} kN -> {v2:.2f} kN/m; first storey {V1:.1f} kN -> {v1:.2f} kN/m")
# Single-sided 11 mm OSB, 3.25 mm common nails: resistance from the nail, vd = nu / s
nu = 1.10 # kN, unit lateral resistance of one nail (approximate, yield model)
JD = 1.3 # shearwall factor for nailed sheathing
for name, v in [("second storey", v2), ("first storey", v1)]:
for s in (150, 100, 75, 50):
vr = 0.8 * JD * nu / (s / 1e3)
if vr >= v:
print(f"{name}: v = {v:.2f} kN/m, one side, nails at {s} mm: vr = 0.8 x {JD} x {nu}/{s/1e3} = {vr:.2f} kN/m")
break
# Hold-down at the end of a 3.2 m first-storey segment
lseg = 3.2
Vseg1 = V1 * lseg / sum(seg1)
Vseg2 = V2 * lseg / sum(seg2)
M = Vseg2 * 2 * h + (Vseg1 - Vseg2) * h # overturning at the base of the segment
Dres = 0.9 * 4.5 * lseg # 0.9 x dead load on the segment (4.5 kN/m)
T = M / lseg - Dres / 2
print(f"\nSegment {lseg} m: overturning {M:.0f} kN.m, hold-down tension = {M/lseg:.1f} - {Dres/2:.1f} = {T:.1f} kN")roof : reaction 33.6 kN, unit shear 4.20 kN/m, chord force 16.8 kN second floor: reaction 48.0 kN, unit shear 6.00 kN/m, chord force 24.0 kN End wall shear: second storey 33.6 kN -> 4.20 kN/m; first storey 81.6 kN -> 12.75 kN/m second storey: v = 4.20 kN/m, one side, nails at 150 mm: vr = 0.8 x 1.3 x 1.1/0.15 = 7.63 kN/m first storey: v = 12.75 kN/m, one side, nails at 75 mm: vr = 0.8 x 1.3 x 1.1/0.075 = 15.25 kN/m Segment 3.2 m: overturning 163 kN.m, hold-down tension = 50.8 - 6.5 = 44.4 kN
Worked problem
End wall design
Design the end walls of the annex: find the unit shear in each storey, choose the nail spacing for one layer of 11 mm OSB (\(n_u = 1.10\) kN per nail), and find the hold-down force at a first-storey segment with a dead load of 4.5 kN/m.
Show solution
- Second storey: \(V_2 = 4.2(16)/2 = 33.6\) kN over 8.0 m:
- \[v_2 = 4.20\ \text{kN/m} \qquad v_r = 0.8(1.3)\frac{1.10}{0.150} = 7.63\ \text{kN/m at 150 mm}\]
- First storey: \(V_1 = 33.6 + 6.0(16)/2 = 81.6\) kN over two 3.2 m segments:
- \[v_1 = \frac{81.6}{6.4} = 12.75\ \text{kN/m} \qquad v_r = 0.8(1.3)\frac{1.10}{0.075} = 15.25\ \text{kN/m at 75 mm}\]
- Hold-down at a 3.2 m segment: the segment takes 13.4 kN from the roof level (at 6.0 m) and 27.4 kN from the second floor (at 3.0 m):
- \[M = 13.4(6.0) + 27.4(3.0) = 163\ \text{kN·m} \qquad T = \frac{163}{3.2} - \frac{0.9(4.5)(3.2)}{2} = 44.4\ \text{kN}\]
Answer: Use nails at 150 mm edge spacing in the second storey and 75 mm in the first, with 300 mm in the field of the panels, all edges blocked. The first-storey hold-downs must resist 44 kN, which calls for a manufactured hold-down with an anchor rod into the foundation and a multi-stud chord, and the second storey needs a strap or rod tie through the floor to carry its own uplift down. The diaphragms carry 4.2 and 6.0 kN/m of unit shear and chord forces of 17 and 24 kN.
The door in the first storey is what drives the design: it removes a fifth of the wall length where the shear is largest, so the first-storey unit shear is three times that of the second storey. Moving the door to the end of the wall would leave one longer segment and reduce both the unit shear and the hold-down force, a good example of how architecture and structure interact in wood buildings.
Anchorage and sliding
The shear at the base of each wall must pass into the foundation. Anchor bolts through the sill plate carry it in bearing on the wood, so they are designed as bolted connections loaded parallel to grain, with plate washers that keep the sill from splitting and that hold the plate down against the uplift of the sheathing. Their spacing follows from the unit shear and the capacity of one bolt, and the first and last bolts sit close to the ends of each sill piece. At the second floor, the shear passes from the upper wall into the floor framing through nails in the bottom plate and from the floor into the wall below through blocking or rim joists. Each transfer is checked, because a wall that is strong in itself but poorly attached to what is below it does nothing.
Deflection of shear walls and diaphragms
Shear walls deflect through four mechanisms: bending of the wall as a cantilever, shear deformation of the panels, slip of the nails, and stretching and slip of the hold-down. For typical walls the nail slip and hold-down slip dominate, which is why the standards include deflection equations with a nail slip term and why tight-fitting hold-downs and shrinkage compensating devices matter in multi-storey buildings. Storey drift limits under wind protect cladding and partitions; under earthquake they protect the structure itself.
Earthquake design
Thunder Bay and Duluth have low seismic hazard, and wind governs the annex. Where earthquake governs, wood shear walls are among the most ductile lateral systems available, because the many nails yield progressively and dissipate energy. The NBC assigns nailed wood shear walls a ductility-related force modification factor \(R_d = 3.0\) and an overstrength factor \(R_o = 1.7\), and O86 adds capacity design requirements so that the nails, not the hold-downs or the anchorage, are the weak link.
Mass timber lateral systems
The pavilion has no wood-frame walls. Its CLT roof is the diaphragm, with screwed splines at the panel joints carrying shear and the edge glulam beams acting as chords, and the lateral load goes to steel rod X-bracing in two end bays and to the concrete block wall at the back of the pavilion, which joins the wash bay. For taller mass timber buildings, CLT shear walls, rocking walls with hold-downs, braced frames and concrete cores are all used, each with its own design rules.
Details that make the system work
Lateral systems in wood fail at their weakest link, and the weakest link is rarely the sheathing. Common problems are missing or under-nailed blocking at panel edges, top plate splices that cannot carry the chord force, hold-downs installed loosely or omitted, anchor bolts too close to the ends of sill plates, and penetrations cut through shear walls by other trades. Inspection during construction, especially of nail spacing and hold-down installation, is part of the design. Over-driven nails, which break the surface of the sheathing, reduce capacity markedly, so pneumatic nailers must be adjusted.
Common mistakes
MistakeCounting the full wall length, including openings, as shear wall.
InsteadIn the segmented method only full-height segments resist shear; openings reduce the effective length.
MistakeForgetting chord forces in the diaphragm.
InsteadChords carry \(M/b\) in tension and compression; top plate splices must be designed for it.
MistakeOmitting the hold-down or tie at upper storeys.
InsteadOverturning of upper storeys must be carried down through the floor by straps or rods to the hold-downs below.
MistakeIgnoring nail spacing on site.
InsteadShear wall capacity depends directly on edge nail spacing; inspect it.
Summary and key terms
- Diaphragms span between shear walls like deep beams: \(v = R/b\) in the sheathing and \(T = M/b\) in the chords.
- Shear walls: \(v_r = \phi J_D n_u/s\) per sheathed face, with \(\phi = 0.8\) and \(J_D = 1.3\); only full-height segments count.
- Hold-down force: overturning moment over segment length, less the resisting dead load.
- Annex end walls: 4.20 kN/m in the second storey (nails at 150 mm) and 12.75 kN/m in the first (nails at 75 mm), hold-down 44 kN.
- The weakest link is often a detail: blocking, splices, hold-downs and anchorage.
- Diaphragm
- A horizontal structural element, such as a sheathed floor or roof, that carries lateral load to the walls.
- Shear wall
- A wall designed to resist lateral load in its own plane.
- Chord
- A boundary member of a diaphragm or shear wall that carries tension or compression from bending.
- Unit shear
- Shear force per unit length along a diaphragm edge or shear wall.
- Hold-down
- A device that anchors the tension chord of a shear wall segment to the structure below.
- Blocking
- Framing installed under unsupported panel edges so they can be nailed.
- Collector
- A member that gathers diaphragm shear and delivers it to a shear wall.
- Segmented shear wall
- A design method that counts only full-height wall segments without openings.
Practice problems
Work each problem on paper first, then reveal the answer to check.
If the annex door moved to the end of the wall, leaving one 6.4 m segment, what would the first-storey unit shear be?
Show answer
The same 12.75 kN/m, because the total segment length is unchanged, but there would be one hold-down pair instead of two, and each would see a smaller force for the same overturning because of the longer lever arm.
What happens to the diaphragm chord force if the annex were 12 m (40 ft) wide instead of 8 m (26 ft)?
Show answer
It falls in proportion: \(T = wL^2/(8b)\), so a wider diaphragm has smaller chord forces.
Find the resistance of a wall sheathed on both faces with nails at 100 mm.
Show answer
\(2(0.8)(1.3)(1.10/0.100) = 22.9\) kN/m, subject to the standard's limits on double-sided walls.
Why are seismic unit shear values lower than wind values?
Show answer
Cyclic earthquake loading degrades nailed connections more than wind, so a controlled, lower value is used.